Plan Review Details - Permit 00110313
Plan Review Stops For Permit 00110313
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2000-12-26 Cont ID  
Sent By rmcdouga Date 2000-12-26 Time 09:31 Rev Time 1.00
Received By rmcdouga Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2000-12-04 Cont ID  
Sent By rmcdouga Date 2000-12-04 Time 14:37 Rev Time 4.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-01-08 00:00:00DENIED
  
 1)RECORDED NOTICE OF COMMENCEMENT IS
 REQUIRED PRIOR TO PERMIT BEING ISSUED.
  
 2)PROVIDE 2 CURRENT COPIES OF METRO-DADE
 OR SBCCI PRODUCT APPROVALS FOR ROOF
 COVERING MATERIALS.
  
 3)THE STRUCTURAL NOTES ON SHEET S-3 #10
 AND #11 REFER TO 1994 SOUTH FLORIDA
 BUILDING CODE. THE CITY OF W.P.B. HAS
 ADOPTED THE 1997 STANDARD BUILDING CODE
 AS AMENDED BY PALM BEACH COUNTY. THE
 ACCEPTED DESIGN CRITERIA IS SECTION 1606
 OF THE 97 SBC OR ASCE 7-95. PLEASE
 CORRECT.
  
 4)PLEASE INDICATE CONNECTORS THAT WILL
 BE USED TO PROVIDE A CONTINOUS TIE FROM
 THE ROOF OF THE GAZEBO TO THE ROOF OF
 THE CUPOLA.
  
 5)STRUCTURE IS LOCATED IN AN "AO" ZONE
 AN ELEVATION CERTIFICATE IS REQUIRED.

Review Stop Z ZONING
Rev No 1 Status P Date 2001-01-04 Cont ID  
Sent By sgraham Date 2000-11-30 Time 09:14 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
2001-01-08 00:00:00NEED MINOR AMENDMENT
 MINOR AMENDMENT APP