Plan Review Details - Permit 00110258
Plan Review Stops For Permit 00110258
Review Stop B BUILDING (STRUCTURAL)
Rev No 9 Status F Date 2002-12-30 Cont ID  
Sent By jwitmer Date 2002-12-30 Time 15:05 Rev Time 0.55
Received By jwitmer Date 2002-12-30 Time 15:05 Sent To  
Notes
2002-12-30 00:00:00REVISION, DATE 12/16/02 : EMPLOYEES
 RESTROOM
 DENIED:
 4.22 OF FL HANDICAPPED CODE
 TOLIET FACILITIES REQUIRED TO BE ACCESS-
 IBLE BY 4.1 SHALL COMPLY WITH 4.22.
 ACCESSIBLE TOILET ROOMS SHALL BE ON A
 ACCESSIBLE ROUTE.
 MINIMUM REQUIREMENTS4.1(6) IF TOLIET
 FACILITIES ARE PROVIDED ON A SITE, THEN
 EACH SUCH PUBLIC OR COMMON USE TOLIET
 FACILITY SHALL COMPLY WITH 4.22. IF BATH
 ING FACILITIES ARE PROVIDED ON A SITE,
 THEN EACH SUCH PUBLIC OR COMMON USE
 BATHING FACILITY SHALL COMPLY WITH 4.23.
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 X 8412

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status P Date 2002-12-30 Cont ID  
Sent By jwitmer Date 2002-12-30 Time 15:02 Rev Time 0.33
Received By jwitmer Date 2002-12-30 Time 15:02 Sent To  
Notes
2002-12-30 00:00:00REVISION DATED 12-12-02 SECTION THROUGH
 SEATING @ RAISED FLOOR, WOOD TO BE USED
 IS REQUIRED TO BE FIRE RESISTANT TREATED
 WOOD.609.2.1.
 BUILDING PLAN REVIEW
 JIM WITMER

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2002-01-11 Cont ID  
Sent By btrobaug Date 2002-12-19 Time 12:40 Rev Time 1.50
Received By jwitmer Date 2002-01-09 Time 17:57 Sent To  
Notes
2002-01-11 00:00:00BUILDING PLAN REVIEW
 PLANS ARE OK TO ISSUE PERMIT, THE
 VERIFICATION OF PAYMENT FOR COUNTY
 IMPACT FEES TO BE ADDRESSED!!!JW

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2001-11-16 Cont ID  
Sent By jwitmer Date 2001-11-16 Time 15:25 Rev Time 8.00
Received By jwitmer Date 2001-11-15 Time 08:09 Sent To  
Notes
2001-11-16 00:00:00BUILDING PLAN EVIEW
 PERMIT# 00110258
 651 OKEECHOBEE BLVD. # 100
 ARCH: HARTER-ADAMS P.A.
 TEL: (407) 647-5767
 FAX: (407) 647-2062
 "TSUNAMI"
 1)- ADDITIONAL INFORMATION REQUIRED
 SBC 104.2.2: STRUCTURAL SHEETS INDICATE
 VARIOUS FOOTINGS THAT WILL SIT UPON THE
 FOUNDATION FOR THE SHELL OF THE WHOLE
 BUILDING. WE WILL REQUIRE A LETTER FROM
 THE ENGINEER OF RECORD (FOR THE SHELL OF
 THE BUILDING) APPROVING THE ADDITIONAL
 LOADS BEING TRANSFERRED ONTO THE EXIST-
 ING FOUNDATION.
 THIS WAS A REQUEST FROM PLAN REVIEW COM-
 PLETED 01/16/2001. A LETTER WAS RECEIVED
 BUT NOT ATTACHED TO THE CURRENT SET OF
 PLANS.
  
 2)- HEALTH DEPARTMENT APPROVAL REQUIRED
 BEFORE THE ISSUANCE OF PLANS,PLAN REVIEW
 COMMENT FROM 01/16/2001.
  
 3)- MECHANICAL ROOM # 26: EGRESS STAIR
 AS INDICATED ON PLAN (A2.1) 2'-6".
 SBC TABLE 1004 EITHER OCCUPANCY ASSEMBLY
 OR STORAGE LESS THAN 50 PEOPLE 36" STAIR
 WELL SEE NOTE 10.
  
 4)- NOTE : EQUIPMENT ROOM TO BE CONSIDER
 ED A TRUE SECOND STORY. THE RAISED MEZZA
 NINE AREA MEETS 1/3RD AREA OF ROOM WITH
 ENCLOSED AREA BELOW.(STAIRS EXCLUDED)
  
 5)- SHEET A2.1 CHAIRLIFT, WILL REQUIRE
 PRODUCT INFORMATION COMPLYING WITH
 FL ACCESIIBILITY CODE 4.11.2,4.2.4,4.5
 4.27 AND ASME A17.1 SAFETY CODE FOR
 ELEVATORS AND ESCALATORS, SEC XX,1990.
  
 6)- SHEET A6.3 INDICATES A SECTION
 THROUGH THE CEILING A8.5 BUT THE DETAIL
 IS FOR LIGHT WELL IN FLOOR SLAB?
  
 7)- SHEET A8.5 WOOD BLOCKING IN WALLS
 MISSING FIRE RETARDANT TREATED MISSING
 TYPE II BUILD.
  
 8)- SHEET A9.3 INDICATE HOW COMPLIANCE
 WITH SBC 604. / 609.2.1 FIRE RESISTANT
 TREATED WOOD, SBC 803.1.2FOR DECORATIONS
 ?
  
 9)- TYPE II BUILDING REQUIRES FIRE
 SPRINKLER DRAWINGS AS PART OF THE BUILD-
 ING PERMIT PACKAGE, A SEPERATE PERMIT
 & PLANS WILL BE REQUIRED FOR FIRE
 SPRINKLER PERMIT.
  
 10)- PLANS WILL BE REQUIRED TO HAVE
 COUNTY IMPACT FEE STAMP BEFORE ISSUANCE.
  
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096X8412

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2001-07-11 Cont ID  
Sent By jwitmer Date 2001-07-11 Time 16:57 Rev Time 0.00
Received By jwitmer Date 2001-11-15 Time 08:09 Sent To  
Notes
2001-07-11 00:00:00BUILDING PLAN REVIEW
 TSUNAMI OF PALM BEACH
 651 OKEECHOBEE BLVD# 100
 PLAN REVIEW# 00110258
 ARCH GGA ARCHITECT
 GUILLERMO GOMEZ
 P: (212) 628-7276
 F: (212) 585-2251
  
 ALL COMMENTS FROM THE REVIW COMPLETED
 ON 4/9/01 HAVE BEEN REVIEWED AND FOUND
 TO COMPLY WITH THE CODE.
 THE COMMENTS ARE MINOR IN NATURE BUT
 WILL REQUIRE ATTENTION TO COMPLY WITH
 THE CURRENT CODES.
  
 1)- ARCH SHEET A4.1 INDICATES SOME EXTER
 IOR STORAGE UNDER THE EXTERIOR EXIT
 STAIRWAY, E 1-5&E1-6. THESE DOORS WILL
 REQUIRE A 3/34 HR RATING, OPENING PROTEC
 TIVES SEE SBC 1006.2.4.
  
 2)- ARCH SHEET 7.1 WEST ELEVATION:
 KITCHEN EGRESS DOOR THE ARCH NEEDS TO BE
 RAISED HEADROOM CLEARENCE MAINTAINED FOR
 EXIT.
  
 3)- SBC 1204.2- RESTROOMS REQUIRE
 FLOORS & WALLS TO BE LINED WITH NONABSOR
 BANT MATERIALS TO A HEIGTH OF 4'-0".
  
 4)- FL ACCESSIBLITY CODE 1997 4.5
 GROUND & FLOOR SURFACES REQUIRE SURFACES
 ALONG ACCESSIBLE ROUTES & IN ACCESS-
 IBILE ROOMS SHALL BE FIRM, SLIP RESIST-
 ANT SEE ADDAAG 4.5.1 A STATIC COEFICIENT
 OF FRICTION OF 0.6 IS RECOMMENDED FOR
 ACCESSIBILE ROUTES & 0.8 FOR RAMPS.
  
 5)- ONCE PLANS ARE APPROVED AND A CON-
 TRACTOR HAS SIGNED ON THE PLANS WILL
 NEED TO BE TAKEN TO THE COUNTY BUILDING
 DEPARTMENT TO BE ASSED FOR COUNTY
 IMPACT FEES, PLANS STAMPED AND A COPY OF
 IMPACT FEES PAID FOR THE CITY RECORDS.
  
 PLAN REVIEW
 JIM WITMER
 (561) 659-8096 EX 8412

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2001-04-09 Cont ID  
Sent By jwitmer Date 2001-04-09 Time 12:40 Rev Time 0.00
Received By jwitmer Date 2001-11-15 Time 08:09 Sent To  
Notes
2001-04-09 00:00:00BUILDING PLAN REVIEW
 TSUNAMI OF PALM BEACH
 651 OKEECHOBEE BLVD
 PLAN REVIEW: 00110258
 ARCH. GGA ARCHITECT
 GUILLERMO GOMEZ
 P (212) 628-7276
 F (212) 585-2251
  
 PARTIAL PLAN REVIEW A1.0/ A1.5, A2.0/
 A2.1M.BUILDING, FIRE & PLUMBING ARE ABLE
 TO PROVIDE A LIMITED REVIEW SINCE THE
 PLANS ARE OF FLOOR PLAN LAYOUT.
  
 1)- SBC 503.2.3. MEZANINES CAN NOT EX-
 CEED 1/3 THAT OF THE ROOM OR SPACE IN
 WHICH THEY ARE LOCATED.
  
 2)- SBC 1004.2.1 THERE SHAL BE NOT LESS
 THAN (2) APPROVED INDEPENDENT EXITS,
 ACCESSIBLE TO EACH TENANT AREA, SERVING
 EVERY STORY.
  
 3)- SBC 1004.2.2 MINIMUM NUMBER EXITS 2
 OCCUPANT LOAD PER FLOOR 1-500.
  
 4)- SBC 1005.6.2 SMOKE PROOF ENCLOSURES.
 A MINIMUM OF 2 HR FIRE RESISTANT CON-
 STRUCTION, 1 1/2 HR OPENING PROTECTIVES
 (STAIRWELL ENCLOSURES).
  
 5)- SBC 704.1 (TABLE) OCCUPANCY SEPERA-
 TION ASSEMBLY (2 HRS).
  
 6)- SBC 1011.2.3 ALL OPENINGS LOCATED
 WITHIN 10 FT. OF FIRE ESCAPES SHALL BE
 PROTECTED WITH APPROVED OPENING PROTECT-
 IVES OF AT LEAST 3/4HR FIRE RESISTANCE.
  
 THIS IS A LIMITED REVIEW OF FLOOR PLAN
 PAGES ONLY.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 P (561) 659-8096 EX 8412
 F (561) 659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2001-02-21 Cont ID  
Sent By jwitmer Date 2001-02-21 Time 12:59 Rev Time 0.00
Received By jwitmer Date 2001-11-15 Time 08:09 Sent To  
Notes
2001-02-21 00:00:00TSUNAMI RESTRAUNT
 651 OKEECHOBEE BLVD.
 PLAN REVIEW # 00110258
 GUILLERMO GOMEZ ARCH.
 PHONE (212) 628-7276
 FAX(212) 585-2251
  
 1)- SBC104.2.2 ADDITIONAL INFO:
 SHEET A1.1 THE SITE PLAN,PLEASE UPDATE
 THE SITE PLAN TO SHOW EGRESS TO AN AREA
 OF REFUGE, THE STREET OR COURTYARD.
 THERE ARE CONCERNS AS TO EXITING THIS
 AREA WITH THE AMOUNT OF PEOPLE USING THE
 EXITS AT THE REAR OF THE BUILDING AND
 BUILT IN SAFETY FACTORS, GATES ACROSS
 THE SERVICE DRIVE, HVAC EQUIPMENT AND
 EXHAUST VENTS ON THE REAR WALLS.
  
 2)- DISCREPANCIES IN PLANS, PLEASE DE-
 LETE THE FIRE EXIT RAMP ON THE SITE PLAN
 B)- A3.1 RAMP AT REAR OF LOUNGE.
 C)- A4.1 DOOR AT REAR OF LOUNGE.
  
 3)- THE LEFT SIDE OF A 2.1 IS FADED,
 NOT CLEAR AND UNREADABLE.
  
 4)- SHEETS 2.1 FIRST FLOOR AND A2.1M,
 THERE IS A CONCERN BY THE BUILDING DEPT.
 AS WELL AS THE FIRE MARSHALL TO THE
 EXITING OF THIS RESTRAUNT & LOUNGE,THERE
 IS MORE THAN ADEQUATE EXITING WHEN ALL
 ELEMENTS OF THE BUSINESS ARE OPEN. THE
 CONCERNS ARE WHEN SEGMENTS OF THE BUSI-
 NESS ARE CLOSED VIA DOORS OR GATES THAT
 THE EXITING REQUIREMENTS ARE STILL MET.
 WE CAN VISUALIZE THAT CERTAIN PORTIONS
 OF THIS RESTRAUNT HAS THREE DISTINCT
 AREASAND THE POSSIBILITY OF BEING OPEN
 AT DIFFERENT TIMES OF THE DAY. PLEASE
 PROVIDE AN OPERATION PLAN FOR THE REST-
 RAUNT & LOUNGE AREAS. WE COULD IDENTIFY
 A THIRD AREA, BAR "A" AND SURROUNDING
 RESTRAUNT AREA AS A THIRD AREA FOR
 LUNCH. ON EACH OF THESE PLANS THE ELE-
 VATOR NEEDS TO BE ACCESIBLE FOR THE
 HANDICAPPED. PLEASE IDENTIFY ALL DOORS &
 GATES THAT WOULD SEGMENT THE USAGE OF
 THESE AREAS. WE ARE LOOKING FOR ACCESS-
 IBLE ROUTES FOR EACH AREA BASED ON THE
 TIME EACH AREA MAY HAVE DIFFERENT HOURS
 OF OPERATION. INDICATE THE OCCUPANT LOAD
 ALLOWABLE FOR EACH EXIT, 50 % OF THE
 OCCUPANT LOADS MUST EGRESS THE FRONT
 ENTRY DOORS.
  
 5)- A SECOND ISSUE IS THE EGRESS TO THE
 LOUNGE (STAIRS), THIS DOESN'T ALLOW A
 ACCESSIBLE ROUTE TO THE HANDICAPPED.
  
 6)- DOORS THAT DO NOT MEET THE 32" CLEAR
 WIDTH: 11-E, 11-F & 12-D. E2.1 NOT ON
 SCHEDULE.
  
 7)- LOUNGE AREA- ADDITIONAL INFO: ON THE
 PULL OUT PLATFORM.
  
 8)- LOUNGE AREA- BAR EQUIPMENT UNDER
 PLATFORM WILL REQUIRE FIRE SPRINKLER.
  
 9)- STEEL SERVICE CATWALK: STRUCTURAL DE
 TAILS, ATTACHMENT TO THE CATWALK AS WELL
 AS THE STRUCTURE ABOVE. SBC 1003.2.3
 THE CATWALK MUST MAINTAIN A 80" VERTICAL
 CLEARENCE TO THE RAMP BELOW,MINIMUM.
 10)- SHEET A7.1 EXHAUST HOODS, EXHAUST
 GRILLS AND THE COMBUSTION AIR LOUVERS
 ARE WITHIN THE 10'-0" PROTECTED WALLS RE
 QUIRED FOR THE EMERGENCY FIRE STAIRS.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 EX 8412

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2001-01-17 Cont ID  
Sent By jwitmer Date 2001-01-17 Time 07:21 Rev Time 0.00
Received By jwitmer Date 2001-11-15 Time 08:08 Sent To  
Notes
2001-01-17 00:00:006). NOTE SHEET A1.2 DIVISION 17 - FIRE
 SUPRESSION SYSTEM, NOTE "B" TO EMBED
 PIPE IN CONCRETE THE GUIDELINES IN SBC
 1907.3 MUST BE ADHERRED TO. WE WILL NEED
 THE TYPE OF PIPE, GAUGE AND SIZE OF THE
 PIPE TO SEE IF IT CAN QUALIFY FOR EMBED-
 MENT.
 7). MECHANICAL ROOM STAIRS (1007.4.2)
 WIDTH OF LANDINGS SHALL BE NOT LESS THAN
 THE WIDTH OF THE STAIRWAY THEY SERVE.
 8). MECHANICAL ROOM EGRESS (1004.2.1)-
 THERE SHALL BE NOT LESS THAN 2 APPROVED
 INDEPENDENT EXITS, ACCESSIBLE TO EACH
 TENANT AREA,SERVING EVERY "STORY-BASE-
 MENT."
 9). SBC 104.2.2 ADDITIONAL INFORMATION-
 DISCREPANCY SHEET A1.4 SHOWS A REVISION
 #1 STAIRS TO DINING PLATFORM #4. BECAUSE
 OF THE OCCUPANT LOAD FOR THIS AREA 2
 EGRESSES ARE REQUIRED,SHEET A1.4 SHOWS A
 REVISION STRIKING THE STAIRWELL AND A
 CONTINIOUS EGRESS PATH TO THE ELEVATOR.
 SHEET A.2.1M SHOWS THE SAME REVISION
 WITH A STAIRS TO THE PLATFORM #4 AT A
 HEIGTH OF 10'-6", SHEET S-2 DRAWINGS
 ALSO SHOW A HEIGTH OF 10'-6". THERE
 WOULD BE 2 CODE ITEMS TO RESOLVE. (1)
 THE 2 EGRESSES REQUIRED FOR THE OCCUPANT
 LOAD, & (2) THE ACCESSIBILITY FL ACC
 CODE 4.1.3 VERTICAL ACCESSIBILITY SHALL
 BE PROVIDED TO ALL LEVELS ABOVE & BELOW
 THE OCCUPIABLE GRADE LEVEL.
 THE SAME SITUATION WITH THE DINING BAL.
 THE OCCUPANT LOAD WILL REQUIRE 2 MEANS
 OF EGRESS.
 10). FL. ACCESSIBILITY CODE 4.8.3 EGRESS
 RAMPS REQUIRE 44" CLEAR WIDTH. THE
 DOWNSTAIRS RAMP TO THE VIP PLATFORM AND
 THE EMERGENCY RAAMP BEHIND THE BUILDING
 ARE TO NARROW.
 11). EMERGENCY RAMP- FL ACCESSIBILITY
 CODE 4.8.4.2- REQUIRES THE LANDING AT
 THE BOTTOM OF THE RAMP IS TO 72" LONG
 AND TOBE STRAIGHT & LEVEL.
 12). EMERGENCY STAIRS- TO CONFORM WITH
 SBC 1011, SUBMIT SHOP DRAWINGS.
 13). EMERGENCY FIRE STAIR (1006.2.4)
 SHALL SEPERATE THE INTERIOR OF THE BUILD
 ING BY WALLS WITH A FIRE RESISTANCE
 RATING OF NOT LESS THAN 1 HR., WITH FIX-
 ED OR SELF-CLOSING OPENING PROTECTIVES
 AS REQUIRED FOR CLOSED STAIRS. THIS
 PROTECTION SHALL EXTEND VERTICALLY FROM
 THE GROUND TO A POINT 10 FTABOVE THE
 TOPMOST LANDING. OPENINGS WITHIN 10 FT.
 HORIZONTAL EXTENSION OF THE PROTECTED
 WALLS BEYOND THE STAIRWAY SHALL BE
 EQUIPED WITH FIXED 3/4 HR ASSEMBLIES.
 THIS INCLUDES VENTS.
 14). BATHROOM WALL FINISHES- SHEET A4.2
 BATHROOM WALL FINISHES (SBC 1204.2)
 WALLS & FLOORS OF ALL PUBLIC RESTROOMS
 SHALL BE LINED WITH NONABSOREMENT
 MATERIALS TO A HEIGTH OF 4 FT ABOVE THE
 FLOOR.
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 EX 8412
2001-01-16 00:00:001). SBC 104.2.2SHEET A1.0 INDICATES
 UNDER BUILDING DATA THAT THERE IS A SEC-
 OND FLOOR OF 1,25 SQ FT? IS THIS SUPPOSE
 TO BE THE BASEMENT?
 2). SBC 104.2.2 SHEET S-1 INDICATES VAR-
 IOUS FOOTINGS THAT WILL SIT UPON THE
 FOUNDATION FOR THE SHELL OF THE WHOLE
 BUILDING. WE WILL REQUIRE A LETTER FROM
 THE ENGINEER OF RECORD APPROVING THE
 ADDITIONAL LOADS BEING TRANSFERRED ONTO
 THE EXISTING FOUNDATION.
 3). SHEET A1.2 DIVISION 6 NOTE #10 -
 ADD NOTE FOR FIRE RETARDANT TREATEDED
 TO PLANS.
 4). MISSING FL. ENERGY SHEETS/ CALS-
 SIGNED ?SEALED.
 5). HEALTH DEPARTMENT APPROVAL REQUIRED
 BEFORE THE PERMIT CAN BE ISSUED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2000-11-28 Cont ID  
Sent By drunnels Date 2000-11-28 Time 11:31 Rev Time 10.00
Received By drunnels Date 2000-11-28 Time 11:31 Sent To  
Notes
2001-01-08 00:00:001] SUBMIT FIRE SPRINKLER PLAND AND
 PERMIT APPLICATION.
 2]SEPERATE PERMITS REQUIRED FOR
 STROEFRONT AS NOTED ON SHEETS A15.1&
 A15.2.
 3]OBSTRUCTIONS OF ACCESSIBILE ROUTE BY
 TABLES AND CHAIRS ON 1ST AND 2ND LEVEL
 NEEDS TO BE ADDRESSED
 4]PROVIDE INFORMATION ON ACCESSIBILITY
 TO THE CENTER SECTION OF VIP LOUNGE
 5]SHEET A2.1 GATE 11-G & 11-H SHALL
 SWING IN THE DIRECTION OF THE PATH
 OF TRAVEL
 6]SHEET A6.5 REFERS TO DETAIL 6 ON SHEET
 A11.3/PLEASE PROVIDE DETAIL.
 7]SHEET A6.5 SECTIONS 9&10 SHOWS LINEAR
 BOOTH RAISED 1 FOOT/ NOT TO CODE
 8]SUBMIT INFORMATION ON "LEATHER HATCH"
 SHEET A11.1 RAIL ELEVATION DETAIL
 9]SUBMIT INFORMATION SHOWING CHAIR LIFTS
 COMPLYING TO ANSI STANDARS AND FLORIDA
 ACCESSIBILITY CODE FOR BUILDING
 CONSTRUCTION.
 10]SUBMIT INFORMATION SHOWING ELEVATOR
 COMPLYING TO ALL FLORIDA ACCESSIBILITY
 CODES FOR BUILDING CONSTRUCTION.
 11]DEFINE WHERE COLUMN PROTUCTION SHOWN
 ON SHEET A15.1 APPLIES.
 12]SHEET A13.2 DETAIL 7 DOES NOT COMPLY
 TO UL# U465 AND DETAIL 8 DOES NOT
 COMPLY TO UL# U412 PLEASE CORRECT
 13]SUBMIT STRUCTURAL DRAWINGS
 SHEETS (S1.1, S1.2 & S2.1)
 14]

Review Stop E ELECTRICAL
Rev No 9 Status P Date 2002-12-20 Cont ID  
Sent By btrobaug Date 2002-12-20 Time 16:19 Rev Time 0.50
Received By btrobaug Date 2002-12-20 Time 16:11 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 8 Status P Date 2002-08-23 Cont ID  
Sent By btrobaug Date 2002-08-23 Time 15:11 Rev Time 5.00
Received By btrobaug Date 2002-08-23 Time 10:30 Sent To  
Notes
2002-08-23 00:00:00PROVISO
 ~~~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
  
 PLEASE PROVIDE THE FOLLOWING INFORMATION
 AND MAKE ANY NECESSARY CHANGES IN THE
 PLANS FOR THE NEXT REVISIONS.
  
 1} THE LOAD CALCULATIONS DID NOT CHANGE
 ON THESE REVISIONS,PLEASE MAKE CHANGES
 IN NEXT REVISION.
  
 2} WATER HEATER ON E-2 IS NOT SHOWN IN
 THE CALC'S ON THE SCHEDULE.
  
 3} WHERE IS CIRCUIT K-39 FOR THE FIRE
 SUPPRESSION?
  
 4} THE TYPE "J" FIXTURES DESIGNATIONS
 CHANGED,AND ARE NOT LISTED ON THE
 REVISIONS AS SHEET E-8 WAS
 MISSING.PLEASE SUPPLY INFORMATION FOR
 THESE FIXTURES.
  
 5} CIRCUIT K-62 IS LISTED TWICE ON E-1.
 THE CONTRACTOR INDICATED THE ONE IN THE
 DISHWASHER AREA WAS ON CIRCUIT K-42 BUT
 THAT CIRCUIT FEEDS THE BATH AREAS,AND
 THE CALC FOR THAT CIRCUIT DIDN'T CHANGE.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/659-8096 EXT.8392

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2002-01-04 Cont ID  
Sent By dpalmer Date 2002-01-04 Time 11:39 Rev Time 0.00
Received By dpalmer Date 2002-01-03 Time 16:57 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2001-11-21 Cont ID  
Sent By dpalmer Date 2001-11-21 Time 15:14 Rev Time 0.00
Received By dpalmer Date 2001-11-21 Time 12:15 Sent To  
Notes
2001-11-21 00:00:00***************** UNSAT ****************
  
 1)NOTE: PLEASE NOTE 700-12E CIRCUITS
 FOR EM LTS, EXIT LTS SHALL BE FROM SAME
 PANEL.
  
  
  
  
  
  
  
 3)NOTE: PLEASE NOTE THAT ALL CONTINUOUS
 LOADS ARE TO BE SHOWN AT 125%.
 215-2/230-42 ETC.
  
 4)NOTE: PLEASE SHOW LOAD CALCULATIONS,
 PER 220-11/220-3/220-10/220-13 ETC.
  
 5)NOTE: PLEASE CLARIFY ATTACHMENT FOR
 TRANSFORMER. PER 250-24
  
 6)NOTE: PLEASE NOTE OUTLET SPACING TO
 MEET LOCAL CODE ON ALL LEVELS.
 210-50 PBCAC.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR]
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2001-07-21 Cont ID  
Sent By dpalmer Date 2001-07-21 Time 10:27 Rev Time 0.00
Received By dpalmer Date 2001-07-21 Time 10:27 Sent To  
Notes
2001-07-21 00:00:00***************** UNSAT ***************
  
  
  
 1)NOTE: PLEASE NOTE THAT PER ART;240-21-
 C-3, TRANSFORMER SEEMS TO BE MORE THAN
 10' AWAY FROM "LDP" PLEASE NOTE 10' TAP
 RULE. PLEASE PLACE NOTE ON RISER DIAGRAM
 THAT TAPS NEED TO MEET 240-21."10"TAP.
 IF OVER 10', A DISCONNECT WILL BE REQ`D.
  
 2)NOTE: PLEASE NOTE ART; 450-21-B FOR
 CLEARENCE ABOUT TRANSFORMER. PLEASE
 CALRIFY RATING OF TRANSFORMER.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2001-07-08 Cont ID  
Sent By dpalmer Date 2001-07-08 Time 12:07 Rev Time 0.00
Received By dpalmer Date 2001-07-08 Time 12:07 Sent To  
Notes
2001-07-08 00:00:00************** UNSAT **************
  
 1)NOTE: PLEASE NOTE THAT NO ELECTRICAL
 PLANS WERE SUBMITTED FOR REVIEW.
  
 PLEASE SUBMIT FOR REVIEW. IF THERE ARE
 ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2001-02-16 Cont ID  
Sent By dpalmer Date 2001-02-16 Time 11:44 Rev Time 0.00
Received By dpalmer Date 2001-02-16 Time 11:44 Sent To  
Notes
2001-02-16 00:00:00***************** UNSAT **************
  
 1)NOTE: PERMIT HAS NOT BEEN ISSUED YET A
 ND PLANS THAT WERE RE-SUBMITTED ARE NOT
 COMPLETE. ONLY, ES1.1,E2.1,E4.1,4.2,4.3
 WERE SUBMITTED? NEED TO HAVEALL THE
 ORIG PLANS.
  
  
 PLEASE SUBMIT THE ABOVE. IF THERE ARE
 ANY QUESTIONS PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-01-11 Cont ID  
Sent By dpalmer Date 2001-01-11 Time 19:53 Rev Time 0.00
Received By dpalmer Date 2001-01-11 Time 19:53 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-11-30 Cont ID  
Sent By dpalmer Date 2000-11-30 Time 21:36 Rev Time 0.00
Received By dpalmer Date 2000-11-30 Time 21:36 Sent To  
Notes
2001-01-08 00:00:00**************** UNSAT ***************
  
 1)NOTE: PLEASE PROVIDE MORE INFORMATION
 ON TRANSFORMER TO CLARIFY ALL REQ`MENTS
 OF 450-9 AND 450-21B
  
 2)NOTE: PLEASE SEE E 4.2. PLEASE SEE
 CONDUIT/CONDUCTORS AND BREAKERS FOR
 FEEDS TO PANELS K1A AND K1B..
  
 3)NOTE: PLEASE NOTE THAT OUTLET SPACING
 IS TO MEET LOCAL CODE OF EVERY 20` OF
 UNENCUMBERED WALL SPACE.210-50 OF P. BCH
 COUNTY AMENDMENTS.
  
 4)NOTE: PLEASE SEE NOTE #37 ON E4.2
 THE CODE ART# 250-81 IS FROM THE "96"
 NEC. PLEASE NOTE THAT WE ARE UNDER THE
 "99" NEC AND ALL REFERENCES ON PLANS
 NEED TO REFLECT "99" NEC.
  
 5)NOTE: PLEASE PROVIDE SOME FORM OF
 CLARIFICATION THAT LOADS FOR TRACK
 LIGHTING IS SHOWN PER 220-12B.
  
  
 6)NOTE: PLEASE SHOW GROUNDING REQ`D BY
 ART: 800-40
  
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 8 Status P Date 2002-02-01 Cont ID  
Sent By mcarsill Date 2002-02-01 Time 09:30 Rev Time 0.00
Received By mcarsill Date 2002-02-01 Time 09:30 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 7 Status F Date 2001-12-20 Cont ID  
Sent By mcarsill Date 2001-12-20 Time 11:39 Rev Time 0.00
Received By mcarsill Date 2001-12-20 Time 11:39 Sent To  
Notes
2001-12-20 00:00:001) PLEASE DEMONSTRATE THAT FIRE
 SPRINKLER PLANS AND APPLICABLE
 PERMITS HAVE BEEN APPLIED FOR.
 2) THE SCRUBBER SYSTEM REFERENCED
 IN THE PLANS MUST BE EQUIPPED WITH
 A SEPARATE FIRE EXTINGUISHING SYSTEM
 THAN THAT OF THE HOOD,DUCT, AND
 EXTINGUISHING SYSTEM PLANNED FOR THE
 KITCHEN. NO DOWNGRADES OF THE EXHAUST
 DUCT CAN OCCUR BECUASE OF THE SCRUBBER
 SYSTEMS.
 3) WITH REGARDS TO WALL TERMINATIONS
 OF KITCHEN EXHAUSTS, PLEASE REVIEW
 ALL APPLICABLE CODE SECTIONS OF NFPA
 96 AND ENSURE COMPLIANCE.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 6 Status F Date 2001-11-26 Cont ID  
Sent By mcarsill Date 2001-11-26 Time 15:03 Rev Time 0.00
Received By mcarsill Date 2001-11-26 Time 15:03 Sent To  
Notes
2001-11-26 00:00:001) IT WOULD APPEAR THAT ADDITIONAL
 EXIT SIGN(S) ARE NEEDED FOR THE
 MEZZANINE.
 2) NO FIRE SPRINKLER PLANS PROVIDED
 WITH DRAWINGS.
 3) TABLES AND CHAIRS IN MAIN DINING
 AREA ARE TOO CLOSE TOGETHER.
 4) SOME SOFFITS ARE SHOWN AT 6 FEET 8
 INCHES FROM THE FLOOR WHICH CONFLICTS
 WITH THE STANDARD BUILDING CODE,
 MINIMUM HEADROOM REQUIREMENTS. PLEASE
 DETERMINE PROBLEM AREAS.
 4) MAXIMUM TRAVEL DISTANCE IN
 SPRINKLER PROTECTED ASSEMBLY OCCUPANCIES
 IS 200 FEET.
 5) A SEPARATE FIRE ALARM PANEL IS
 NOT NECESSARY FOR TSUNAMI. THE FIRE
 ALARM EQUIPMENT SHOULD BE CONNECTED
 TO THE TOWER'S FIRE ALARM CONTROL
 PANEL.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status F Date 2001-07-31 Cont ID  
Sent By mcarsill Date 2001-07-31 Time 13:07 Rev Time 0.00
Received By mcarsill Date 2001-07-31 Time 13:06 Sent To  
Notes
2001-07-31 00:00:001) NO FIRE SPRINKLER DRAWINGS PROVIDED
 WITH PLANS.
 2) LEATHER BOUND WALLS SHOWN FOR
 ELEVATOR. WHAT ALLOWS THIS TO OCCUR.
 3) FIBERGLASS HOISTWAY WALLS SHOWN
 FOR ELEVATORS. CODE DOES NOT ALLOW FOR
 THIS.
 4) NO VENT SHOWN FOR HOT WATER HEATER
 VENT.
 5) MORE DETAILS NEEDED ON SMOG HOG
 GREASE FILTER UNIT SHOWN ON M2.2.
 6) EXHAUST DUCT TO SLOPE SHALL BE 1"
 PER FOOT.
 7) EXIT STAIRS LOCATED ON THE EXTERIOR
 SHALL BE SLIP RESISTANT.
 8) PLEASE SHOW HOW THE EXITS LOCATED
 ON THE MEZZANINE LEVEL MEET THE
 REQUIRED 1/2 DIAGONAL DIMENSION OF THE
 ROOM OR AREA SERVED.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status F Date 2001-06-27 Cont ID  
Sent By mcarsill Date 2001-06-27 Time 08:36 Rev Time 0.00
Received By mcarsill Date 2001-06-27 Time 08:36 Sent To  
Notes
2001-06-27 00:00:001) NO MECHANICAL,ELECTRICAL,PLUMBING OR
 FIRE SPRINKLER DRAWINGS PROVIDED WITH
 PLANS.
 2) SITTING CHAIRS LOCATED ON THE FIRST
 AND SECOND FLOORS STILL APPEAR TO BE
 TOO CLOSE TOGETHER.
 3) PLEASE VERIFY CEILING HEIGHTS. ALL
 CEILING HEIGHTS ARE TO BE AT LEAST 7'-6"
 IN THE MEANS OF EGRESS. PROJECTIONS FROM
 THE CEILINGS IN THESE AREAS CANNOT BE
 LESS THAN 6'-8".
 4) SCRUBBER(S) ARE NOTED ON THE PLANS.
 PLEASE PROVIDE MORE DETAILS.
 5) ALL EXTERIOR STAIRS ARE TO BE SLIP
 RESISTANT.
 6) HOW WIDE IS EXTERIOR EXIT STAIR AND
 WHAT IS ITS EXIT CAPACITY.
 7) HOW ARE THE PORCELAIN SOCKETS UNDER
 THE FLOOR POWERED, PROTECTED AND ARE
 LISTINGS PRESENT.
 8) MORE INFORMATION NEEDED ON KITCHEN
 HOOD,DUCT,SCRUBBERS,AND EXTINGUISHING
 SYSTEMS.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2001-02-28 Cont ID  
Sent By mcarsill Date 2001-02-28 Time 10:16 Rev Time 0.00
Received By mcarsill Date 2001-02-28 Time 10:16 Sent To  
Notes
2001-02-28 00:00:001) PLEASE PROVIDE THIS OFFICE A USAGE
 PLAN FOR THE ESTABLISHMENT. IT WAS FELT
 BY THE PLAN REVIEW STAFF THAT CERTAIN
 AREAS OF THE ESTABLISHMENT COULD BE
 CLOSED OFF FROM OTHER SECTIONS. HOW
 COULD THIS EFFECT EXITING.
 2) PLEASE INDICATE EXIT DISCHARGE
 ROUTES FROM GROUND LEVEL, NORTH SIDE
 OF BUILDING. HOW DOES EXIT DISCHARGE
 OCCUR NEAR RETAIL SERVICE DRIVE, GATES.
 3) SEATING LOCATED ALONG WEST WALL
 GROUND LEVEL IS TOO TIGHT. THESE TABLES
 AND CHAIRS DO NOT ALLOW FOR THE MINIMUM
 OF 12" BETWEEN THE BACKS OF THE CHAIRS.
 4) DOOR 12D IS NOT WIDE ENOUGH. MUST BE
 32 INCHES IN THE CLEAR.
 5) DOOR 11E AND 11F NOT WIDE ENOUGH.
 MUST BE 32 IN THE CLEAR.
 6) CRAWL SPACE TO BE FIRE SPRINKLER
 PROTECTED WHERE BAR EQUIPMENT IS STORED.
 7) DOTTED LINE NEAR 11C ON PAGE A2.1
 SIGNIFIES WHAT.
 8) FIRE SPRINKLER HEAD DISCHARGE
 PATTERNS ARE NOT TO BE AFFECTED BY THE
 FIBERGLASS PANELS.
 9) THE KITCHEN EXHAUST DUCTS THAT
 EXTEND HORIZONTALLY COULD INTERFERE WITH
 EXITING FROM THE BUILDING. PLEASE
 EXPLAIN RATIONALE.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2000-12-27 Cont ID  
Sent By mcarsill Date 2000-12-27 Time 13:48 Rev Time 0.00
Received By mcarsill Date 2000-12-27 Time 13:48 Sent To  
Notes
2001-01-08 00:00:001) PLEASE INDICATE WHERE THE 994
 ESTIMATED VISITORS TO TSUNAMI WILL
 PARK. THE FIRE LANE LOCATED ON THE
 SOUTH SIDE OF THE HIGH-RISE BUILDING
 IS TO REMAIN CLEAR AND UNOBSTRUCTED.
 PLEASE ADVISE PARKING ARRANGEMENT TO
 THIS OFFICE.
 2) PLEASE PROVIDE MORE DETAILS ON
 UNDERGROUND MECHANICAL ROOM SHOWN ON
 PAGE A2.0. NO FIRE SPRINKLERS, EMERGENCY
 LIGHTING, OR EXIT SIGNS ARE SHOWN, AND
 ONLY ONE MEANS OF EGRESS IS SHOWN.
 3) FIBERGLASS PROJECTION SCREENS ARE TO
 MEET APPLICABLE FLAME SPRED CRITERIA.
 4) DOES THE WOOD LATTICE WORK MEET
 THE APPLICABLE FLAME SPREAD CRITERIA.
 5) PLEASE EXPLAIN WHAT THE ELECTRIC
 TRANSFORMER ON PAGE A7.1 IS FOR. WHY
 IS IT LOCATED BELOW THE EXIT STAIR.
 6) WHAT PROTECTION IS PROVIDED FOR THE
 NEW FIRE RAMP SHOWN ON PAGE A7.1. IT
 APPEARS THAT THIS RAMP PASSES BY TWO
 WINDOWS AND POSSIBLY A DOOR.
 7) THE GAS INSTALLATION TO COMPLY WITH
 NFPA 54.
 8) PLEASE PROVIDE SET-BACK DISTANCES
 TO ADJACENT BUILDINGS, PROPERTY LINES,
 EXITS FROM THE THREE GREASE HOOD
 EXHAUST FANS.
 9) PLEASE EXPLAIN RATIONALE FOR SINGLE
 MEANS OF EGRESS FROM DINING BALCONY.
 10) NO FIRE SPRINKLER PLANS OR HYDRAULIC
 CALCULATIONS PROVIDED WITH PLANS. THESE
 ITEMS MUST BE SUBMITTED PRIOR TO
 RECEIVING A BUILDING PERMIT.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2000-11-09 Cont ID  
Sent By mcarsill Date 2000-11-07 Time 11:06 Rev Time 0.00
Received By mcarsill Date 2000-11-07 Time 09:16 Sent To  
Notes
2001-01-08 00:00:001) PLEASE IDENTIFY MAIN ENTRY AND EXIT.
 THIS LOCATION IS TO PROVIDE EXITING
 FOR AT LEAST 50 PERCENT OF THE OCCUPANT
 LOAD.
 2) OCCUPANT LOAD TO BE DETERMINED BY
 THIS OFFICE.
 3) PROVISIONS ARE TO BE MADE FOR AT
 LEAST TWO HANDICAPPED PERSONS.
 4) ALL AWNINGS ARE TO BE FIRE RETARDANT.
 5) NO FIRE SPRINKLER DRAWINGS OR
 HYDRAULIC CALCULATIONS PROVIDED WITH
 PLANS. ENTIRE SPACE IS TO BE COMPLETELY
 FIRE SPRINKLER PROTECTED. THIS INCLUDES
 ALL MECHANICAL, ELECTRICAL, AND SERVICE
 ROOMS. ALL VERTICAL SHAFTS ARE ALSO TO
 BE PROTECTED.
 6) PROVIDE COMPLETE FIRE ALARM SYSTEM
 SHOP DRAWINGS FOR FIRE ALARM EQUIPMENT
 SHOWN ON DRAWINGS. CUT SHEETS, AND
 WIRING DIAGRAMS ARE TO BE SUBMITTED WITH
 SHOP DRAWINGS UNDER SEPARATE PERMIT.
 7) MORE DETAILS ARE NEEDED FOR THE
 PULL OUT PLATFORM. WHAT IS IT USED FOR.
 8) PLEASE DEFINE CRAWL SPACE. WHAT IS
 THIS USED FOR.
 9) ANY CHANGES IN ELEVATION LESS THAN
 21 INCHES SHALL BE BY RAMPS. STEPS WHEN
 USED ARE TO BE A MINIMUM OF THREE.
 10) THERE APPEARS TO BE TWO STEPS NEAR
 THE ELEVATOR ON THE MEZZANINE LEVEL.
 THIS WILL NOT BE PERMITTED.
 11) PLEASE EXPLAIN SLIDING WALLS.
 12) SOME GATES SWING IN AND SOME SWING
 OUT PLEASE EXPLAIN RATIONALE.
 13) PLEASE EXPLAIN SERVICE CATWALK.
 14) PLEASE BE ADVISED THAT TURNSTILES
 OR OTHER DEVICES CANNOT BE INSTALLED
 TO INTERFERE WITH THE MEANS OF EGRESS
 IN ASSEMBLY OCCUPANCIES.
 15) PLEASE CHECK INTERIOR FINISH
 NOTES. NOTES SUGGEST CLASS C, THIS
 INFORMATION APPEARS TO BE INCORRECT.
 16) PLEASE EXPLAIN CEILING HEIGHT OF
 4'-7" ON PAGE A11.4
 17) DUCT SMOKE DETECTORS REQUIRED IN
 AIR-HANDLING SYSTEMS OVER 2000CFM.
 18) ADDITIONAL EMERGENCY LIGHTING
 EQUIPMENT APPEARS TO BE NEEDED.
 19) PLEASE INDICATE PLATFORM
 CONSTRUCTION.
 20) CLEARLY EXPLAIN EXITING FROM
 MEZZANINE.
  
 PLANS REVIEWED BY CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2002-12-19 Cont ID  
Sent By dpalmer Date 2002-12-19 Time 09:59 Rev Time 0.00
Received By dpalmer Date 2002-12-19 Time 09:59 Sent To B
Notes
2002-12-19 00:00:00TO JIM WITMER.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-12-17 Cont ID  
Sent By btrobaug Date 2002-12-17 Time 13:08 Rev Time 0.00
Received By btrobaug Date 2002-12-17 Time 13:08 Sent To B
Notes
2002-12-17 00:00:00TO JIM./WRT

Review Stop M MECHANICAL (A/C)
Rev No 7 Status P Date 2001-12-21 Cont ID  
Sent By pkrauss Date 2001-12-21 Time 09:41 Rev Time 2.00
Received By pkrauss Date 2001-12-21 Time 10:06 Sent To  
Notes
2001-12-21 00:00:00 
 ADDITIONAL PERMITS REQUIRED FOR HOOD,
 FIRE SUPRESSION AND WALK-IN COOLERS.
 PROVIDE PLANS AND ALL MANUFACURER
 SUBMITTAL DATA AND PRODUCT APPROVALS
 WITH PERMIT APPLICATION.
  
 PLEASE NOTE, THE GREASE DUCT SHALL BE
 DESIGNED AND INSTALLED IN A MANNER TO
 PROVIDE AN AIR VELOCITY WITHIN THE DUCT
 SUSTEM OF NOT LESS THAN 1,500 FT PER
 MINUTE. 1997 SMC 505.7
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 6 Status F Date 2001-11-29 Cont ID  
Sent By pkrauss Date 2001-11-29 Time 13:28 Rev Time 6.00
Received By pkrauss Date 2001-11-29 Time 12:24 Sent To  
Notes
2001-11-29 00:00:00*******************DENIED***************
  
  
 PLEASE PROVIDE THE FOLLOWING INFORMATION
 FOR REVIEW.
  
 1.PLAN SHEET AC.8, OUTSIDE AIR
 RECAPULATION REFLECTS RTU'S.NO
 RTU'S OR OUTSIDE AIR REFLECTED ON
 PLANS.
  
 2.PLAN SHEET AC.2, PROVIDE DETAIL OF
 ITEM 4 SOUND LINED PLENUM.
  
 3.INDICATE ACCESSIBLITY FOR SERVICE
 FOR AHU'S 1,2, & 3.
  
 4.PLEASE CLARIFY "PH-1,2,3,& 4",
 PROVIDE DETAIL OF RISER TO PENTHOUSE
  
 5.IDENTIFY KITCHEN EXHAUST TERMINATION
 PLEASE NOTE AS PER 1997 SMC 506.1,
 DUCTS SERVING COMMERCIAL FOOD
 COOKING AND PROCESSING, SHALL
 TERMINATE OUTSIDE OF THE BUILDING
 AND BE LOCATED 10' FROM ANY ADJACENT
 PROPERTY LINE, PARKING AREA, A
 ADJACENT BUILDING, WINDOW, DOOR, OR
 AIR INTAKE OPENING AND SHALL BE A
 MIN. OF 40" ABOVE THE ROOF SURFACE.
  
 5.PROVIDE MANUFACTURER SUBMITTAL DATA
 FOR THE SMOG HOG.
  
 6.FIRE DAMPER DETAIL-PLAN SHEET AC.5,
 INDICATES VERTICLE PENERATION.FIRE
 DAMPERS DEPICTED ON PLAN SHEET AC.3
 ARE FLOOR/CEILING PENETRATIONS. ALL
 FIRE DAMPERS SHALL COMPLY WITH UL
 555.
  
 ADDITIONAL PLANS AND PERMITS REQUIRED
 FOR HOOD, FIRE SUPRESSION AND WALK-IN
 COOLERS.PLEASE SUBMIT MANUFACTURER
 SUBMITTAL DATA AND PLANS WITH PERMIT
 APPLICATION.
  
 PLEASE NOTE, A LETTER FROM THE ENGINEER
 AND OR ARCHITECT ADDRESSING COMMENTS AND
 INDICATING CHANGES AND RESPONSES TO
 COMMENTS WOULD GREATLY HELP EXPEDITE
 PLANS IN THE FUTURE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 5 Status F Date 2001-07-17 Cont ID  
Sent By pkrauss Date 2001-07-17 Time 14:51 Rev Time 1.30
Received By pkrauss Date 2001-07-17 Time 13:29 Sent To  
Notes
2001-07-17 00:00:00******************DENIED****************
  
  
 PLEASE PROVIDE INFORMATION/DETAIL ON
 FIRE RATED ENCLOSURE AS CALLED OUT ON
 DRAWING M2.2, HOOD EXHAUST ELEVATION.
  
 NOTE:GREASE HOOD DUCT SHALL HAVE A
 MINIMUM OF 1" PER FOOT SLOPE
 TOWARD HOOD AS PER 1997 SMC 505.4
  
 EXHAUST OUTLET SHALL TERMINATE
 10' FROM ANY ADJACENT BUILDING,
 PROPERTY LINE, WINDOW, DOOR, OR
 AIR INTAKE
  
  
 ADDITIONAL PERMITS REQUIRED FOR HOOD,
 FIRE SUPRESSION, GAS, OR WALK-IN COOLER.
 PLEASE PROVIDE PLANS AND MANUFACTURER
 DETAIL/ENGINEERED DRAWINGS.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status N Date 2001-06-28 Cont ID  
Sent By pkrauss Date 2001-06-28 Time 12:28 Rev Time 0.20
Received By pkrauss Date 2001-06-28 Time 12:12 Sent To  
Notes
2001-06-28 00:00:00******************DENIED****************
  
  
 INSUFFICIENT INFORMATION FOR MECHANICAL
 REVIEW.PLEASE SUBMIT PLANS WITH
 MECHANICAL PERMIT APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2001-03-02 Cont ID  
Sent By pkrauss Date 2001-02-20 Time 14:56 Rev Time 2.00
Received By pkrauss Date 2001-02-26 Time 15:16 Sent To  
Notes
2001-02-26 00:00:00DETAIL OF ACCESS DOORS NEED TO BE
 REFLECTED ON PLANS SIZE AND LOCATION TO
 SHOW COMPLIANCE WITH 1997 SMC 304.2.
  
 MISSING PLAN A3.1M (MEZZANINE REFLECTED
 CEILING).ACCESS FOR SERVICE FOR AHU'S
 1-4 AND AHU 7 AND 8.
  
 DRAWING M1.3 - NOTE 7 IS THE FRESH AIR
 BEING BROUGHT IN BEHIND PANELS?MUST
 COMPLY WITH 97 SMC 501.2 & ASHRAE 62-89.
  
 AS PER NFPA 4-4.4.3, DUCT SMOKE
 DETECTORS WITH NOTIFICATION TO
 HORN/STROBE IN NORMALLY OCCUPIED AREA.
  
 NOTE:ADDITIONAL PERMITS REQUIRED FOR
 HOOD, FIRE SUPRESSION, SUBMIT PLANS
 WITH APPLICATION.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2001-01-17 Cont ID  
Sent By ndenmark Date 2001-01-17 Time 10:26 Rev Time 0.33
Received By pkrauss Date 2001-01-17 Time 10:25 Sent To  
Notes
2001-01-17 00:00:001. PROVIDE DETAIL SHOWING ACCESSIBILITY
 FOR AHU SERVICE SMC 304.2. NO REFERENCED
 DWG. M3.1-M3.3, ALSO NO M5.1 DWG.
 2. PROVIDE ELEVATION DETAIL SHOWING
 TERMINATION OF EXHAUST FANS AND OUTSIDE
 AIR INTAKE OPENINGS IN RELATION TO EACH
 OTHER & OTHER OPENINGS INTO THE
 BUILDING INCLUDING DOORS & OPERABLE
 WINDOWS.HAVE MINIMUM REQUIRED
 DISTANCES SHOWN ON PLAN, PERNFPA 96
 4-8.3.
 3. PROVIDE INFORMATION ON GREASE
 EXHAUST DUCT LOCATION & TERMINATION
 INCLUDING
 SIZES SHOWING PROXIMITITY TO OTHER
 BUILDING COMPONENTS FOR REVIEW FOR
 COMPLIANCE WITH 1997 SMC CHAPTER 5 &
 NFPA 96.YOUR RESPONSE (12/18/00),
 REF. DETAIL ON DWG. M3.1., THERE WAS NO
 SUCH DWG. SUBMITTED.
 4.NO VENTILATION FOR UNDERGROUND MECH.
 RM. AS PER SMC 501.2.ALSO, THERE IS
 NOIB-B DOOR ON SCHEDULE.
 5. DWG. M1.1 HAS NO NOTE #14.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2000-11-30 Cont ID  
Sent By ndenmark Date 2000-11-30 Time 08:15 Rev Time 2.50
Received By jleech Date 2001-07-12 Time 19:25 Sent To  
Notes
2001-01-08 00:00:00************DENIED**********************
  
 1.PROVIDE OUTSIDE AIR SCHEDULE PER
 ASHRAE 62-89
 2. PROVIDE AIR BALANCE SCHEDULE SHOWING
 COMPLIANCE WITH 1997 SMC 501.2.
 3. PROVIDE DETAIL SHOWING REQUIRED
 ACCESSIBILITY FOR AHU SERVICE AND MANUF-
 ACTURES REQUIRED COIL PULL AND OTHER
 MAINTAINANCE CLEARANCE REQUIREMENTS ARE
 DEDICATED CLEAR AREAS FOR UNIT ACCESS
 PER 1997 SMC 304.2 AND NEC FOR ELECTRICA
 CLEARANCE REQUIREMENTS
 4. AHU #6 RETURN AIR PLENUM IS LOCATED
 IN A ROOM WITH GAS WATER HEATER. 1997
 SMC 609.1.3 PROHIBITS WATER HEATERS USE-
 ING GAS FUEL BEING LOCATED IN THIS TYPE
 LOCATION.
 5. PROVIDE ELEVATION DETAIL SHOWING
 TERMINATION OF EXHAUST FANS AND OUTSIDE
 AIR INTAKE OPENINGS IN RELATION TO EACH
 OTHER AND OTHER OPENINGS INTO THE BUILD-
 ING INCLUDING DOORS AND OPERABLE WINDOWS
 HAVE MINIMUM REQUIRED DISTANCES SHOWN ON
 PLAN.
 6. PROVIDE INFORMATION ON GREASE EXHAUST
 DUCT LOCATION AND TERMINATION INCLUDING
 SIZES SHOWING PROXIMITY TO OTHER BUILD-
 ING COMPONENTS FOR REVIEW FOR COMPLIANCE
 WITH 1997 SMC CHAPTER 5 AND 1994 NFPA 96
 7. NOTE: SEPARATE PERMITS ARE REQUIRED
 FOR THE FOLLOWING SYSTEMS; HOODS, INCLUD
 ING GREASE DUCT AND MAKE UP AIR DUCTS AN
 WALKIN COOLERS AND FREEZERS. COMPLETE
 PLANS SHALL BE PROVIDED FOR THESE SYSTEM
 COMPONENTS AT TIME OF MECHANICAL PERMIT
 APPLICATION FOR THESE ADDITIONAL PERMITS
 8. AHU 5 AND AHU 6 HAVE NO RETURN AIR
 PATH FROM AREA SERVED BY AHU'S
 9. PRIVATE ROOM OFF BATHROOMS ON MEZZAN-
 INE LEVEL DOES NOT HAVE VENTILATION TO
 SPACE.
 10.PROVIDE LOCATION OF ALL REQUIRED
 MANUAL VOLUME DAMPERS FOR TEST AND BALA-
 NACE PURPOSES.
 11. SHOW LOCATIONS OF ALL FIRE DAMPERS
 AT RATED WALLS PER 1997 SMC 610.6 AND
 610.1.2

Review Stop P PLUMBING
Rev No 9 Status F Date 2002-12-30 Cont ID  
Sent By kstevens Date 2002-12-30 Time 16:45 Rev Time 0.25
Received By kstevens Date 2002-12-30 Time 16:45 Sent To  
Notes
2002-12-30 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
  
 1) REVISION OF EMPLOYEES RESTROOM NOT
 APPROVED. SECTION 11-4.1(6) IF TOILET
 FACILITIES ARE PROVIDED ON A SITE, THEN
 EACH SUCH PUBLIC OR COMMON USE TOILET
 FACILITY SHALL COMPLY WITH 4.22. IF BATH
 ING FACILITIES ARE PROVIDED ON A SITE,
 THEN EACH SUCH PUBLIC OR COMMON USE
 BATHING FACILITY SHALL COMPLY WITH SEC
 4.23.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 8 Status N Date 2002-01-13 Cont ID  
Sent By pschmitz Date 2002-01-13 Time 14:41 Rev Time 3.00
Received By pschmitz Date   Time   Sent To  
Notes
2002-01-13 00:00:00PROVISO: 8TH PLBG PLAN REVIEW
 DEPT OF HOTEL BUSINESS REGULATION REVIEW
 AND COMMENTS, ATTACHED TO PLANS BEFORE
 ISSUING PLUMBING PERMIT.
 END OF COMMENTS PAUL SCHMITZ
 561-659-8096X8233

Review Stop P PLUMBING
Rev No 7 Status F Date 2001-11-28 Cont ID  
Sent By kstevens Date 2001-11-28 Time 13:01 Rev Time 6.00
Received By kstevens Date 2001-11-28 Time 13:01 Sent To  
Notes
2001-11-28 00:00:00DENIED (SEVENTH TIME)
 REFERENCE: SPC-94 - SGC-97 - FACBC-97
  
 1) DEPT OF HOTEL BUSINESS REGULATION
 PLAN REVIEW W/COMMENTS REQUIRED BEFORE
 PLUMBING PLAN REVIEW. CONTACT FOR
 APPOINTMENT. (954) 958-5520
 2) SHT A1.3 (CHANGED FROM A2.1) MEN &
 WOMEN RESTROOMS PREVIOUS COMMENT RE:
 DCA-FLBC RULE 9B-7.0042 FL ADM. CODE,
 SEC 4.17.3 FIG 30(E). CLEAR FLOOR SPACE
 FOR W/C AND LAV.
 3) SHT A10.1, EMPLOYEE REST RM, SHOWER
 STALL, COMPLY W/SEC 4.21 ADA SHOWER
 STALL. SHOW DETAILS (FM PREVIOUS P-REV.)
 4) FM PREVIOUS REVIEW, SHT A2.1, A2.M1,
 COMPLY WITH SEC 4.1.3(19)(A). ADA FIXED
 SEATING IN A RESTURANT. NO DETAILS SHOWN
 5) FM PREVIOUS REVIEW,SHT M2.1.2.3, CON-
 DENSATE FROM 7-AHU, PROVIDE AN ISOMETRIC
 DRAWING OF A COMMON COLLECTION SYSTEM TO
 A DRY WELL OR STORM DRAIN WITH A RELIEF
 VINT. SEC 804.3, 104.
 6) FM PREVIOUS REVIEW. SEE ATTACHED GAS
 PERMIT APPLICATION REQUIREMENTS. ADDRESS
 #'S 1-3-7 & 9 FOR PLAN REVIEW. (ELECT.
 W/HEATER)
 7) FM PREVIOUS REVIEW. SHT P1.7 DETAIL
 #10 FUNNEL DRAIN, FLOOR SINKS REQUIRED
 FOR ALL INDIRECT WASTE. S-802. FD STILL
 SHOWN FOR WALK IN COOLERS SHT'S P1, P4,
 & P6.
 8) FM PREVIOUS REVIEW. DETAIL FOR ICE
 MACHINE NOT SHOWN. CONDENSER UNIT AND
 ICE BIN DRAINS TO BE SEPARATED. CROSS
 CONNECTION OF CONTAMINATED WASTE. SEC
 804 FOOD HANDLING.
 9) SHT P.1 ITEM #14 SMOKE HOG. INDIRECT
 WASTE TO COMPLY WITH SPC SEC 805.1.1 &
 805.1.2
 10) SHT P.1 ITEMS # 6 AND 22 NOT FOUND.
 11) SHT P.3 #'S 6 & 7, WATER HAMMERAR-
 RESTORS TO BE LOCATED NEAR FIXTURES NOT
 AT TOP OF DROPS AS SHOWN. "IN AN EFFECT-
 IVE RANGE OF FIXTURE."
 12) SHT P.4 BACK TO BACK LAVS NOT VENTED
 (LAV-2)
 13) SHT P.4 GAS ISOMETRIC DIAGRAM. UNION
 REQUIRED BETWEEN MANUAL VALVE AND SOLIN-
 OID VALVE.(#'S 7 AND 8). ALSO RE: FS-1
 ITEM #7 NOT SHOWN ON ISOMETRIC.
 14) SHT P.8 #58 HUB DRAIN NOT APPROVED.
 15) SHT P.8 #53 NO POLYETHYLENE JACKET
 FOR UNDERGROUND PIPING. REF STD GAS CODE
 1997 ONLY FOR GAS INSTALLATION.
 16) SHT P.8 #14 BACKFLOW REQUIRED FOR
 TEMP CONSTRUCTION WATER.
 17) SHT FS-1 ITEM #2, DEEP FAT FRYER
 SHALL NOT DRAIN INTO GREASE LINE.
 18) SHT FS-1 ITME #4, CHINESE RANGE.
 WASTE WATER WHEN DISCHARGED INTO THE
 BUILDING DRAINAGE SYSTEM SHALL BE AT A
 TEMPERATURE NOT HIGHER THAN 140 DEGREES
 F. SPC SEC 717.8
 19) SHT FS-1 ITEM #20.1 NSF APPROVAL RE-
 QUIRED FOR FILTER. PROVIDE DETAILS.
 20) SHT FS-1 ITEM #41.2, 43.1 & 43.2 NOT
 SHOWN.
 21) SHEETS REFERED TO IN PREVIOUS REVIEW
 (6TH) DO NOT APPEAR ON PLANS SUBMITTED
 FOR THIS REVIEW. PLEASE KEEP PAGES UNI-
 FORM FROM REVIEW TO REVIEW TO EXPIDITE
 THE REVIEW PROCESS.
  
 REVIEW BY KEN STEVENS
 (561)- 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 6 Status F Date 2001-07-22 Cont ID  
Sent By pschmitz Date 2001-07-22 Time 06:38 Rev Time 3.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-07-22 00:00:00PLUMBING PLAN REVIEW DENIED (SIXTH TIME)
 NOTE ON PLANS,NEW PLANS SUBMITTED.
 (1) DEPT. OF HOTEL BUSINESS REGULATION
 PLAN REVIEW W/COMMENTS REQUIRED, BEFORE
 PLUMBING PLAN REVIEW.CONTACT FOR APPOINT
 MENT 954-958-5520.
 (2) SHT A2.1,A2.M1 MEN & WOMEN REST RM'S
 PREVIOUS COMMENT RE: HANDICAP STALLS
 SEE REVISION: DCA-FLBC,RULE 9B-7.0042,
 FL ADM.CODE, SEC 4.17.3.FIG 30(E).
 CLEAR FLOOR SPACE FOR W/C AND LAVATORY.
 (3) SHT A2.1 EMPLOYEE REST RM, SHOWER
 STALL, COMPLY W/SEC 4.21, ADA SHO.STALL.
 (3)SHT A2.1,A2.M1, COMPLY WITH SEC 4.1.3
 (19)(A).ADA FIXED SEATING IN A RESTURANT
 (4) SHT A1.2 DETAIL ADA (A)(A1).NOT CUR-
 RENT.SEE NOTE 2 ABOVE.
 (5) SHT A10.2 HANDICAP URINAL SEC 4.18.3
 CLEAR FLR SPACE 30"X 48".
 (6) SHT E3.3 LOCATION OF WTR/HTR, TYPE
 IS NOT CLEAR IF THIS IS ELECTRIC OR GAS
 W/H, SHT A2.0 SHOWS ELECTRIC, SHT P1.6
 SHOWS GWH ON A ELECTRIC W/H SCHEDULE?
 (7) SHT M2.1.2.3, CONDENSATE FROM 7-AHU.
 PROVIDE A ISOMETRIC DRAWING OF A COMMON
 COLLECTION SYSTEM TO A DRY WELL OR STORM
 DRAIN, WITH A RELIEF VENT,SEC,804.3,104.
 (8A) SHT P1.5 SEC 104.3 PLANS REQUIRED.
 PROVIDE ISOMETRIC DRAWINGS FOR THE GAS
 PIPING AND SANITARY DWV.
 (8B) SEE ATTACHED GAS PERMIT APPLICATIO
 REQUIRMENTS, ADDRESS EA OF (10) ITEMS,
 FOR PLAN REVIEW.
 (9) SEC 104.3 PROVIDE KITCHEN EQUIPMENT
 PLANS , WITH EQUIPMENT SCHEDULE,LAY OUT.
 (10A)SHT P1.3,SEC 802 ALL INDIRECT WASTE
 TO FLR SINKS,SAFE WASTE NOT ALLOWED.
 (10B) SUSHI BAR, STILL NO VENT SHOWN.
 (11A) SHT P1,4 WATER PIPING ISOMETRIC.
 (MCWC94) SHOW PIPE SIZES, NO MORE THAN 2
 FIXTURES ON 1/2" C/W, NO MORE THAN 4
 FIXTURES ON 1/2" H/W.
 (11B) SHT-P1.4 SHOWS AIR CHAMBERS,
 SHT P1.6 REFERENCES WATER HAMMER ARREST-
 ORS, REMOVE AIR CHAMBERS AND REFERENCE
 THE WATER HAMMER ARRESTORS, AS LISTED.
 (12) SHT P1.5 ISOMETRIC INCORRECTLY
 LABLED,SHOULD BE GREASE WASTE.
 (13A)SHT P1.6 PLBG NOTES #14, DIELECTRIC
 UNIONS, NOT ALLOWED, SEC 608,MATERIALS.
 (13B) FOOD SERVICE NOTE #2-7"TO 11" W/C,
 FL PUBLIC UTILITIES SUPPLIES 12"-14"W/C.
 (14A) SHT P1.7 DETAIL #10 FUNNEL DRAIN,
 FLOOR SINKS FOR ALL INDIRECT WASTE.S-802
 (14B) DETAIL #18 UNIONS IN CEILING, NOT
 PERMITED. NFPA-54 SEC 3.4.2
 (14C) DETAIL #21 ICE MACHINE, CONDENSER
 UNIT & ICE BIN DRAINS,TO BE SEPERATED,
 CROSS CONNECTION OF CONTAMINATED WASTE.
 SEC 804 FOOD HANDLING.
 (14D) DETAIL #22, NO VENT ON WATER HTR.
 (15)SHT P1.3 DISHWASHER DRAIN CONNECT
 I/D TO SANI.SEWER, LOCAL ORD.#2938-96.
 END OF COMMENTSPAUL SCHMITZ
 QUESTIONS 561-659-8096X8233

Review Stop P PLUMBING
Rev No 5 Status F Date 2001-07-12 Cont ID  
Sent By jleech Date 2001-07-12 Time 19:33 Rev Time 2.50
Received By pschmitz Date 2001-07-12 Time 19:33 Sent To  
Notes
2001-07-12 00:00:00DENIED;
  
 1.RISER DIAGRAMS;
 A.GREASY WASTE RISER DIAGRAM;
 1.MOP SINK SHALL DISCHARGE TOH
 GREASY WASTE.
 2.NO INDIRECT WASTES. FLOOR
 SINKS SHALL BE USED TO RECIEVE
 DISCHARGE FROM PLUMBING
 FIXTURES.
 B.SANITARY RISER DIAGRAM REQUIRED.
 C.WATER RISER DIAGRAM;
 1.SIZE PIPE.
 2.DISHWASHER SHOULD BE 3/4"
 D.GAS RISER DIAGRAM REQUIRED.
  
 2.WHERE IS WATER HEATER LOCATED? SHOW
 EXHAUST AND MAKE UP AIR REQUIRED.
  
 3.HOW IS PLUMBING IN SUSHI BAR VENTED?
  
 4.SEE ATTACHED SHEET (GAS PERMIT
 APPLICATION REQUIREMENTS)
  
 PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT 8369

Review Stop P PLUMBING
Rev No 4 Status N Date 2001-07-07 Cont ID  
Sent By jleech Date 2001-07-07 Time 10:54 Rev Time 1.00
Received By jleech Date 2001-07-07 Time 10:53 Sent To  
Notes
2001-07-07 00:00:00PLUMBING PAGES MISSING FROM PLANS. NO
 PLUMBING PLAN REVIEW DONE.
 JOHN LEECH
 659-8096 EXT. 8369

Review Stop P PLUMBING
Rev No 3 Status F Date 2001-03-02 Cont ID  
Sent By jleech Date 2001-03-02 Time 07:21 Rev Time 4.00
Received By jleech Date 2001-03-02 Time 07:21 Sent To  
Notes
2001-03-02 00:00:00DENIED;
  
 1.P5 & P6 GAS SHUTOFF FOR COOKING APPL.
 MUST BE READLY ACCESSIBLE AND
 PROTECTED FROM DAMAGE. SGC 310.1.
  
 2.SHOW SHUTOFF VALVE,AUTOMATIC SHUTOFF
 VALVE AND UNION ONE GAS RISER DIAGRAM.
  
 3.P3 NOTE 8 WASTE PIPE SHALL NOT BE
 REDUCED BETWEEN THE CONNECTION OF THE
 EQUIPMENT AND THE DISCHARGE POINT.
  
 4.FLOOR SINKS ARE REQUIRED IN PLACE OF
 HUB DRAINS; PLEASE MAKE THE FOLLOWING
 CHANGES.
 A.P3 NOTE 11
 B.P3 NOTE 1
 C.P5 GREASE WASTE RISER DIAGRAM
 D.P6 DETAIL 10
 E.P7 FLOOR DRAIN SCHEDULE
  
 5.P6 (9)D/M WASTE DETAIL. DISHWASHER
 SHALL DISCHARGE TO SANITARY. DELETE
 GREASE WASTE FROM DETAIL.
  
 6.P6 (18) COOKING APPL. GAS PIPE. SHOW
 UNION DOWN STREAM OF SOLENOID VALVE.
  
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT. 8377

Review Stop P PLUMBING
Rev No 2 Status F Date 2001-01-10 Cont ID  
Sent By jleech Date 2001-01-10 Time 15:59 Rev Time 3.00
Received By jleech Date 2001-01-10 Time 15:58 Sent To  
Notes
2001-01-10 00:00:00DENIED;
  
 1.ALL HANDICAP TOILET STALLS SHALL
 COMPLY TO 4.17 (EXCEPTION; NEW
 CONSTRUCTION) PAGE 50.
  
 2.ELEVATION DRAWING (5) PAGE A10.2
 HANDICAP URINALS CLEAR FLOOR SPACE IS
 30" NOT 29".
  
 3.P-7 PLUMBING SPECIFICATIONS WATER
 (ASSEMBLY) CHANGE NOTE ABOUT 50/50
 SOLDER AND FLUX TO NO LEAD AND WATER
 SOLUBLE FLUX.
  
 4.P-1 AND P5 DRAWINGS DO NOT MATCH
 ARCHITECTURAL DRAWINGS.
  
 5.FLOOR DRAINSOR FLOOR SINKS TO BE USED
 PLACE OF FUNNEL DRAINS.
  
 6.NEED LONGEST RUN OF GAS PIPE WITH
 GAS RISER DIAGRAM.
  
 7.FIRST FLOOR RISER DIAGRAM NOT TO FLOOR
 PLAN.
  
 8.MEZZANINE RISER DIAGRAM NOT TO FLOOR
 PLAN.
  
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT. 8377

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-11-20 Cont ID  
Sent By jleech Date 2000-11-20 Time 15:27 Rev Time 3.00
Received By jleech Date 2000-11-20 Time 15:26 Sent To  
Notes
2001-01-08 00:00:001.BATHROOM FACILITYS ON FIRST FLOOR MUST
 COMPLY WITH 97 FL0RIDA ACCESSIBILITY
 CODE FOR BUILDING CONSTRUTION #11
 PAGE 21 AND 4.17.
  
 2.HANDICAP LAVATORIES MUST MEET
 CLEARANCES PER FIG. #31.
  
 3.KITCHEN EQUIPMENT SCHEDULE.MINIMUM
 WASTE PIPEPIPE FROM SINKES IS 1 1/2.
 DISHWASHER AND WATER HEATER NOT LISTED
  
 4.NEED RISER DIAGRAMS FOR
 1.GREASY WASTE
 2.SANITARY WASTE
 3.WATER
 4.GAS
 5.CONDENSAT
 5.FLOOR SINKS MUST BE USED IN PLACE OF
 FLOOR DRAINS FOR INDIRECT WASTE.
  
 6.TRAP PRIMERS ARE REQUIRED FOR FLOOR
 DRAINS IN PUBLIC REST ROOMS 409.4.1.
  
 7.HOT WATER MUST BE TEMPERED TO 110F
 FOR HAND SINKS AND BATHROOM LAVATORIES
  
 8.SHOW MAKE-UP AIR AND EXHAUST FOR GAS
 WATER HEATER.
  
 9.SUBMIT GREASE TRAP DRAWINGS TO BE
 APPROVED BY RODNEY COMPO. CITY ORDIN-
 ANCE, GREASY WASTE #2938-96.
  
 10.CONDENSATE FROM AIR HANDLERS AND
 COOLERS ARE NOT PERMITED TO DUMP
 INTO CITY SEWER SYSTEM.