| Plan Review Stops For Permit 00110258 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
9 |
Status |
F |
Date |
2002-12-30 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2002-12-30 |
Time |
15:05 |
Rev Time |
0.55 |
| Received By |
jwitmer |
Date |
2002-12-30 |
Time |
15:05 |
Sent To |
|
|
| Notes |
| 2002-12-30 00:00:00 | REVISION, DATE 12/16/02 : EMPLOYEES | | | RESTROOM | | | DENIED: | | | 4.22 OF FL HANDICAPPED CODE | | | TOLIET FACILITIES REQUIRED TO BE ACCESS- | | | IBLE BY 4.1 SHALL COMPLY WITH 4.22. | | | ACCESSIBLE TOILET ROOMS SHALL BE ON A | | | ACCESSIBLE ROUTE. | | | MINIMUM REQUIREMENTS4.1(6) IF TOLIET | | | FACILITIES ARE PROVIDED ON A SITE, THEN | | | EACH SUCH PUBLIC OR COMMON USE TOLIET | | | FACILITY SHALL COMPLY WITH 4.22. IF BATH | | | ING FACILITIES ARE PROVIDED ON A SITE, | | | THEN EACH SUCH PUBLIC OR COMMON USE | | | BATHING FACILITY SHALL COMPLY WITH 4.23. | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | (561) 659-8096 X 8412 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
8 |
Status |
P |
Date |
2002-12-30 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2002-12-30 |
Time |
15:02 |
Rev Time |
0.33 |
| Received By |
jwitmer |
Date |
2002-12-30 |
Time |
15:02 |
Sent To |
|
|
| Notes |
| 2002-12-30 00:00:00 | REVISION DATED 12-12-02 SECTION THROUGH | | | SEATING @ RAISED FLOOR, WOOD TO BE USED | | | IS REQUIRED TO BE FIRE RESISTANT TREATED | | | WOOD.609.2.1. | | | BUILDING PLAN REVIEW | | | JIM WITMER |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
7 |
Status |
P |
Date |
2002-01-11 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-12-19 |
Time |
12:40 |
Rev Time |
1.50 |
| Received By |
jwitmer |
Date |
2002-01-09 |
Time |
17:57 |
Sent To |
|
|
| Notes |
| 2002-01-11 00:00:00 | BUILDING PLAN REVIEW | | | PLANS ARE OK TO ISSUE PERMIT, THE | | | VERIFICATION OF PAYMENT FOR COUNTY | | | IMPACT FEES TO BE ADDRESSED!!!JW |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
6 |
Status |
F |
Date |
2001-11-16 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-11-16 |
Time |
15:25 |
Rev Time |
8.00 |
| Received By |
jwitmer |
Date |
2001-11-15 |
Time |
08:09 |
Sent To |
|
|
| Notes |
| 2001-11-16 00:00:00 | BUILDING PLAN EVIEW | | | PERMIT# 00110258 | | | 651 OKEECHOBEE BLVD. # 100 | | | ARCH: HARTER-ADAMS P.A. | | | TEL: (407) 647-5767 | | | FAX: (407) 647-2062 | | | "TSUNAMI" | | | 1)- ADDITIONAL INFORMATION REQUIRED | | | SBC 104.2.2: STRUCTURAL SHEETS INDICATE | | | VARIOUS FOOTINGS THAT WILL SIT UPON THE | | | FOUNDATION FOR THE SHELL OF THE WHOLE | | | BUILDING. WE WILL REQUIRE A LETTER FROM | | | THE ENGINEER OF RECORD (FOR THE SHELL OF | | | THE BUILDING) APPROVING THE ADDITIONAL | | | LOADS BEING TRANSFERRED ONTO THE EXIST- | | | ING FOUNDATION. | | | THIS WAS A REQUEST FROM PLAN REVIEW COM- | | | PLETED 01/16/2001. A LETTER WAS RECEIVED | | | BUT NOT ATTACHED TO THE CURRENT SET OF | | | PLANS. | | | | | | 2)- HEALTH DEPARTMENT APPROVAL REQUIRED | | | BEFORE THE ISSUANCE OF PLANS,PLAN REVIEW | | | COMMENT FROM 01/16/2001. | | | | | | 3)- MECHANICAL ROOM # 26: EGRESS STAIR | | | AS INDICATED ON PLAN (A2.1) 2'-6". | | | SBC TABLE 1004 EITHER OCCUPANCY ASSEMBLY | | | OR STORAGE LESS THAN 50 PEOPLE 36" STAIR | | | WELL SEE NOTE 10. | | | | | | 4)- NOTE : EQUIPMENT ROOM TO BE CONSIDER | | | ED A TRUE SECOND STORY. THE RAISED MEZZA | | | NINE AREA MEETS 1/3RD AREA OF ROOM WITH | | | ENCLOSED AREA BELOW.(STAIRS EXCLUDED) | | | | | | 5)- SHEET A2.1 CHAIRLIFT, WILL REQUIRE | | | PRODUCT INFORMATION COMPLYING WITH | | | FL ACCESIIBILITY CODE 4.11.2,4.2.4,4.5 | | | 4.27 AND ASME A17.1 SAFETY CODE FOR | | | ELEVATORS AND ESCALATORS, SEC XX,1990. | | | | | | 6)- SHEET A6.3 INDICATES A SECTION | | | THROUGH THE CEILING A8.5 BUT THE DETAIL | | | IS FOR LIGHT WELL IN FLOOR SLAB? | | | | | | 7)- SHEET A8.5 WOOD BLOCKING IN WALLS | | | MISSING FIRE RETARDANT TREATED MISSING | | | TYPE II BUILD. | | | | | | 8)- SHEET A9.3 INDICATE HOW COMPLIANCE | | | WITH SBC 604. / 609.2.1 FIRE RESISTANT | | | TREATED WOOD, SBC 803.1.2FOR DECORATIONS | | | ? | | | | | | 9)- TYPE II BUILDING REQUIRES FIRE | | | SPRINKLER DRAWINGS AS PART OF THE BUILD- | | | ING PERMIT PACKAGE, A SEPERATE PERMIT | | | & PLANS WILL BE REQUIRED FOR FIRE | | | SPRINKLER PERMIT. | | | | | | 10)- PLANS WILL BE REQUIRED TO HAVE | | | COUNTY IMPACT FEE STAMP BEFORE ISSUANCE. | | | | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | (561) 659-8096X8412 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
F |
Date |
2001-07-11 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-07-11 |
Time |
16:57 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2001-11-15 |
Time |
08:09 |
Sent To |
|
|
| Notes |
| 2001-07-11 00:00:00 | BUILDING PLAN REVIEW | | | TSUNAMI OF PALM BEACH | | | 651 OKEECHOBEE BLVD# 100 | | | PLAN REVIEW# 00110258 | | | ARCH GGA ARCHITECT | | | GUILLERMO GOMEZ | | | P: (212) 628-7276 | | | F: (212) 585-2251 | | | | | | ALL COMMENTS FROM THE REVIW COMPLETED | | | ON 4/9/01 HAVE BEEN REVIEWED AND FOUND | | | TO COMPLY WITH THE CODE. | | | THE COMMENTS ARE MINOR IN NATURE BUT | | | WILL REQUIRE ATTENTION TO COMPLY WITH | | | THE CURRENT CODES. | | | | | | 1)- ARCH SHEET A4.1 INDICATES SOME EXTER | | | IOR STORAGE UNDER THE EXTERIOR EXIT | | | STAIRWAY, E 1-5&E1-6. THESE DOORS WILL | | | REQUIRE A 3/34 HR RATING, OPENING PROTEC | | | TIVES SEE SBC 1006.2.4. | | | | | | 2)- ARCH SHEET 7.1 WEST ELEVATION: | | | KITCHEN EGRESS DOOR THE ARCH NEEDS TO BE | | | RAISED HEADROOM CLEARENCE MAINTAINED FOR | | | EXIT. | | | | | | 3)- SBC 1204.2- RESTROOMS REQUIRE | | | FLOORS & WALLS TO BE LINED WITH NONABSOR | | | BANT MATERIALS TO A HEIGTH OF 4'-0". | | | | | | 4)- FL ACCESSIBLITY CODE 1997 4.5 | | | GROUND & FLOOR SURFACES REQUIRE SURFACES | | | ALONG ACCESSIBLE ROUTES & IN ACCESS- | | | IBILE ROOMS SHALL BE FIRM, SLIP RESIST- | | | ANT SEE ADDAAG 4.5.1 A STATIC COEFICIENT | | | OF FRICTION OF 0.6 IS RECOMMENDED FOR | | | ACCESSIBILE ROUTES & 0.8 FOR RAMPS. | | | | | | 5)- ONCE PLANS ARE APPROVED AND A CON- | | | TRACTOR HAS SIGNED ON THE PLANS WILL | | | NEED TO BE TAKEN TO THE COUNTY BUILDING | | | DEPARTMENT TO BE ASSED FOR COUNTY | | | IMPACT FEES, PLANS STAMPED AND A COPY OF | | | IMPACT FEES PAID FOR THE CITY RECORDS. | | | | | | PLAN REVIEW | | | JIM WITMER | | | (561) 659-8096 EX 8412 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2001-04-09 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-04-09 |
Time |
12:40 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2001-11-15 |
Time |
08:09 |
Sent To |
|
|
| Notes |
| 2001-04-09 00:00:00 | BUILDING PLAN REVIEW | | | TSUNAMI OF PALM BEACH | | | 651 OKEECHOBEE BLVD | | | PLAN REVIEW: 00110258 | | | ARCH. GGA ARCHITECT | | | GUILLERMO GOMEZ | | | P (212) 628-7276 | | | F (212) 585-2251 | | | | | | PARTIAL PLAN REVIEW A1.0/ A1.5, A2.0/ | | | A2.1M.BUILDING, FIRE & PLUMBING ARE ABLE | | | TO PROVIDE A LIMITED REVIEW SINCE THE | | | PLANS ARE OF FLOOR PLAN LAYOUT. | | | | | | 1)- SBC 503.2.3. MEZANINES CAN NOT EX- | | | CEED 1/3 THAT OF THE ROOM OR SPACE IN | | | WHICH THEY ARE LOCATED. | | | | | | 2)- SBC 1004.2.1 THERE SHAL BE NOT LESS | | | THAN (2) APPROVED INDEPENDENT EXITS, | | | ACCESSIBLE TO EACH TENANT AREA, SERVING | | | EVERY STORY. | | | | | | 3)- SBC 1004.2.2 MINIMUM NUMBER EXITS 2 | | | OCCUPANT LOAD PER FLOOR 1-500. | | | | | | 4)- SBC 1005.6.2 SMOKE PROOF ENCLOSURES. | | | A MINIMUM OF 2 HR FIRE RESISTANT CON- | | | STRUCTION, 1 1/2 HR OPENING PROTECTIVES | | | (STAIRWELL ENCLOSURES). | | | | | | 5)- SBC 704.1 (TABLE) OCCUPANCY SEPERA- | | | TION ASSEMBLY (2 HRS). | | | | | | 6)- SBC 1011.2.3 ALL OPENINGS LOCATED | | | WITHIN 10 FT. OF FIRE ESCAPES SHALL BE | | | PROTECTED WITH APPROVED OPENING PROTECT- | | | IVES OF AT LEAST 3/4HR FIRE RESISTANCE. | | | | | | THIS IS A LIMITED REVIEW OF FLOOR PLAN | | | PAGES ONLY. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | P (561) 659-8096 EX 8412 | | | F (561) 659-8026 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2001-02-21 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-02-21 |
Time |
12:59 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2001-11-15 |
Time |
08:09 |
Sent To |
|
|
| Notes |
| 2001-02-21 00:00:00 | TSUNAMI RESTRAUNT | | | 651 OKEECHOBEE BLVD. | | | PLAN REVIEW # 00110258 | | | GUILLERMO GOMEZ ARCH. | | | PHONE (212) 628-7276 | | | FAX(212) 585-2251 | | | | | | 1)- SBC104.2.2 ADDITIONAL INFO: | | | SHEET A1.1 THE SITE PLAN,PLEASE UPDATE | | | THE SITE PLAN TO SHOW EGRESS TO AN AREA | | | OF REFUGE, THE STREET OR COURTYARD. | | | THERE ARE CONCERNS AS TO EXITING THIS | | | AREA WITH THE AMOUNT OF PEOPLE USING THE | | | EXITS AT THE REAR OF THE BUILDING AND | | | BUILT IN SAFETY FACTORS, GATES ACROSS | | | THE SERVICE DRIVE, HVAC EQUIPMENT AND | | | EXHAUST VENTS ON THE REAR WALLS. | | | | | | 2)- DISCREPANCIES IN PLANS, PLEASE DE- | | | LETE THE FIRE EXIT RAMP ON THE SITE PLAN | | | B)- A3.1 RAMP AT REAR OF LOUNGE. | | | C)- A4.1 DOOR AT REAR OF LOUNGE. | | | | | | 3)- THE LEFT SIDE OF A 2.1 IS FADED, | | | NOT CLEAR AND UNREADABLE. | | | | | | 4)- SHEETS 2.1 FIRST FLOOR AND A2.1M, | | | THERE IS A CONCERN BY THE BUILDING DEPT. | | | AS WELL AS THE FIRE MARSHALL TO THE | | | EXITING OF THIS RESTRAUNT & LOUNGE,THERE | | | IS MORE THAN ADEQUATE EXITING WHEN ALL | | | ELEMENTS OF THE BUSINESS ARE OPEN. THE | | | CONCERNS ARE WHEN SEGMENTS OF THE BUSI- | | | NESS ARE CLOSED VIA DOORS OR GATES THAT | | | THE EXITING REQUIREMENTS ARE STILL MET. | | | WE CAN VISUALIZE THAT CERTAIN PORTIONS | | | OF THIS RESTRAUNT HAS THREE DISTINCT | | | AREASAND THE POSSIBILITY OF BEING OPEN | | | AT DIFFERENT TIMES OF THE DAY. PLEASE | | | PROVIDE AN OPERATION PLAN FOR THE REST- | | | RAUNT & LOUNGE AREAS. WE COULD IDENTIFY | | | A THIRD AREA, BAR "A" AND SURROUNDING | | | RESTRAUNT AREA AS A THIRD AREA FOR | | | LUNCH. ON EACH OF THESE PLANS THE ELE- | | | VATOR NEEDS TO BE ACCESIBLE FOR THE | | | HANDICAPPED. PLEASE IDENTIFY ALL DOORS & | | | GATES THAT WOULD SEGMENT THE USAGE OF | | | THESE AREAS. WE ARE LOOKING FOR ACCESS- | | | IBLE ROUTES FOR EACH AREA BASED ON THE | | | TIME EACH AREA MAY HAVE DIFFERENT HOURS | | | OF OPERATION. INDICATE THE OCCUPANT LOAD | | | ALLOWABLE FOR EACH EXIT, 50 % OF THE | | | OCCUPANT LOADS MUST EGRESS THE FRONT | | | ENTRY DOORS. | | | | | | 5)- A SECOND ISSUE IS THE EGRESS TO THE | | | LOUNGE (STAIRS), THIS DOESN'T ALLOW A | | | ACCESSIBLE ROUTE TO THE HANDICAPPED. | | | | | | 6)- DOORS THAT DO NOT MEET THE 32" CLEAR | | | WIDTH: 11-E, 11-F & 12-D. E2.1 NOT ON | | | SCHEDULE. | | | | | | 7)- LOUNGE AREA- ADDITIONAL INFO: ON THE | | | PULL OUT PLATFORM. | | | | | | 8)- LOUNGE AREA- BAR EQUIPMENT UNDER | | | PLATFORM WILL REQUIRE FIRE SPRINKLER. | | | | | | 9)- STEEL SERVICE CATWALK: STRUCTURAL DE | | | TAILS, ATTACHMENT TO THE CATWALK AS WELL | | | AS THE STRUCTURE ABOVE. SBC 1003.2.3 | | | THE CATWALK MUST MAINTAIN A 80" VERTICAL | | | CLEARENCE TO THE RAMP BELOW,MINIMUM. | | | 10)- SHEET A7.1 EXHAUST HOODS, EXHAUST | | | GRILLS AND THE COMBUSTION AIR LOUVERS | | | ARE WITHIN THE 10'-0" PROTECTED WALLS RE | | | QUIRED FOR THE EMERGENCY FIRE STAIRS. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | (561) 659-8096 EX 8412 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2001-01-17 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-01-17 |
Time |
07:21 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2001-11-15 |
Time |
08:08 |
Sent To |
|
|
| Notes |
| 2001-01-17 00:00:00 | 6). NOTE SHEET A1.2 DIVISION 17 - FIRE | | | SUPRESSION SYSTEM, NOTE "B" TO EMBED | | | PIPE IN CONCRETE THE GUIDELINES IN SBC | | | 1907.3 MUST BE ADHERRED TO. WE WILL NEED | | | THE TYPE OF PIPE, GAUGE AND SIZE OF THE | | | PIPE TO SEE IF IT CAN QUALIFY FOR EMBED- | | | MENT. | | | 7). MECHANICAL ROOM STAIRS (1007.4.2) | | | WIDTH OF LANDINGS SHALL BE NOT LESS THAN | | | THE WIDTH OF THE STAIRWAY THEY SERVE. | | | 8). MECHANICAL ROOM EGRESS (1004.2.1)- | | | THERE SHALL BE NOT LESS THAN 2 APPROVED | | | INDEPENDENT EXITS, ACCESSIBLE TO EACH | | | TENANT AREA,SERVING EVERY "STORY-BASE- | | | MENT." | | | 9). SBC 104.2.2 ADDITIONAL INFORMATION- | | | DISCREPANCY SHEET A1.4 SHOWS A REVISION | | | #1 STAIRS TO DINING PLATFORM #4. BECAUSE | | | OF THE OCCUPANT LOAD FOR THIS AREA 2 | | | EGRESSES ARE REQUIRED,SHEET A1.4 SHOWS A | | | REVISION STRIKING THE STAIRWELL AND A | | | CONTINIOUS EGRESS PATH TO THE ELEVATOR. | | | SHEET A.2.1M SHOWS THE SAME REVISION | | | WITH A STAIRS TO THE PLATFORM #4 AT A | | | HEIGTH OF 10'-6", SHEET S-2 DRAWINGS | | | ALSO SHOW A HEIGTH OF 10'-6". THERE | | | WOULD BE 2 CODE ITEMS TO RESOLVE. (1) | | | THE 2 EGRESSES REQUIRED FOR THE OCCUPANT | | | LOAD, & (2) THE ACCESSIBILITY FL ACC | | | CODE 4.1.3 VERTICAL ACCESSIBILITY SHALL | | | BE PROVIDED TO ALL LEVELS ABOVE & BELOW | | | THE OCCUPIABLE GRADE LEVEL. | | | THE SAME SITUATION WITH THE DINING BAL. | | | THE OCCUPANT LOAD WILL REQUIRE 2 MEANS | | | OF EGRESS. | | | 10). FL. ACCESSIBILITY CODE 4.8.3 EGRESS | | | RAMPS REQUIRE 44" CLEAR WIDTH. THE | | | DOWNSTAIRS RAMP TO THE VIP PLATFORM AND | | | THE EMERGENCY RAAMP BEHIND THE BUILDING | | | ARE TO NARROW. | | | 11). EMERGENCY RAMP- FL ACCESSIBILITY | | | CODE 4.8.4.2- REQUIRES THE LANDING AT | | | THE BOTTOM OF THE RAMP IS TO 72" LONG | | | AND TOBE STRAIGHT & LEVEL. | | | 12). EMERGENCY STAIRS- TO CONFORM WITH | | | SBC 1011, SUBMIT SHOP DRAWINGS. | | | 13). EMERGENCY FIRE STAIR (1006.2.4) | | | SHALL SEPERATE THE INTERIOR OF THE BUILD | | | ING BY WALLS WITH A FIRE RESISTANCE | | | RATING OF NOT LESS THAN 1 HR., WITH FIX- | | | ED OR SELF-CLOSING OPENING PROTECTIVES | | | AS REQUIRED FOR CLOSED STAIRS. THIS | | | PROTECTION SHALL EXTEND VERTICALLY FROM | | | THE GROUND TO A POINT 10 FTABOVE THE | | | TOPMOST LANDING. OPENINGS WITHIN 10 FT. | | | HORIZONTAL EXTENSION OF THE PROTECTED | | | WALLS BEYOND THE STAIRWAY SHALL BE | | | EQUIPED WITH FIXED 3/4 HR ASSEMBLIES. | | | THIS INCLUDES VENTS. | | | 14). BATHROOM WALL FINISHES- SHEET A4.2 | | | BATHROOM WALL FINISHES (SBC 1204.2) | | | WALLS & FLOORS OF ALL PUBLIC RESTROOMS | | | SHALL BE LINED WITH NONABSOREMENT | | | MATERIALS TO A HEIGTH OF 4 FT ABOVE THE | | | FLOOR. | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | (561) 659-8096 EX 8412 | | 2001-01-16 00:00:00 | 1). SBC 104.2.2SHEET A1.0 INDICATES | | | UNDER BUILDING DATA THAT THERE IS A SEC- | | | OND FLOOR OF 1,25 SQ FT? IS THIS SUPPOSE | | | TO BE THE BASEMENT? | | | 2). SBC 104.2.2 SHEET S-1 INDICATES VAR- | | | IOUS FOOTINGS THAT WILL SIT UPON THE | | | FOUNDATION FOR THE SHELL OF THE WHOLE | | | BUILDING. WE WILL REQUIRE A LETTER FROM | | | THE ENGINEER OF RECORD APPROVING THE | | | ADDITIONAL LOADS BEING TRANSFERRED ONTO | | | THE EXISTING FOUNDATION. | | | 3). SHEET A1.2 DIVISION 6 NOTE #10 - | | | ADD NOTE FOR FIRE RETARDANT TREATEDED | | | TO PLANS. | | | 4). MISSING FL. ENERGY SHEETS/ CALS- | | | SIGNED ?SEALED. | | | 5). HEALTH DEPARTMENT APPROVAL REQUIRED | | | BEFORE THE PERMIT CAN BE ISSUED. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2000-11-28 |
|
|
Cont ID |
|
| Sent By |
drunnels |
Date |
2000-11-28 |
Time |
11:31 |
Rev Time |
10.00 |
| Received By |
drunnels |
Date |
2000-11-28 |
Time |
11:31 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1] SUBMIT FIRE SPRINKLER PLAND AND | | | PERMIT APPLICATION. | | | 2]SEPERATE PERMITS REQUIRED FOR | | | STROEFRONT AS NOTED ON SHEETS A15.1& | | | A15.2. | | | 3]OBSTRUCTIONS OF ACCESSIBILE ROUTE BY | | | TABLES AND CHAIRS ON 1ST AND 2ND LEVEL | | | NEEDS TO BE ADDRESSED | | | 4]PROVIDE INFORMATION ON ACCESSIBILITY | | | TO THE CENTER SECTION OF VIP LOUNGE | | | 5]SHEET A2.1 GATE 11-G & 11-H SHALL | | | SWING IN THE DIRECTION OF THE PATH | | | OF TRAVEL | | | 6]SHEET A6.5 REFERS TO DETAIL 6 ON SHEET | | | A11.3/PLEASE PROVIDE DETAIL. | | | 7]SHEET A6.5 SECTIONS 9&10 SHOWS LINEAR | | | BOOTH RAISED 1 FOOT/ NOT TO CODE | | | 8]SUBMIT INFORMATION ON "LEATHER HATCH" | | | SHEET A11.1 RAIL ELEVATION DETAIL | | | 9]SUBMIT INFORMATION SHOWING CHAIR LIFTS | | | COMPLYING TO ANSI STANDARS AND FLORIDA | | | ACCESSIBILITY CODE FOR BUILDING | | | CONSTRUCTION. | | | 10]SUBMIT INFORMATION SHOWING ELEVATOR | | | COMPLYING TO ALL FLORIDA ACCESSIBILITY | | | CODES FOR BUILDING CONSTRUCTION. | | | 11]DEFINE WHERE COLUMN PROTUCTION SHOWN | | | ON SHEET A15.1 APPLIES. | | | 12]SHEET A13.2 DETAIL 7 DOES NOT COMPLY | | | TO UL# U465 AND DETAIL 8 DOES NOT | | | COMPLY TO UL# U412 PLEASE CORRECT | | | 13]SUBMIT STRUCTURAL DRAWINGS | | | SHEETS (S1.1, S1.2 & S2.1) | | | 14] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
9 |
Status |
P |
Date |
2002-12-20 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-12-20 |
Time |
16:19 |
Rev Time |
0.50 |
| Received By |
btrobaug |
Date |
2002-12-20 |
Time |
16:11 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
8 |
Status |
P |
Date |
2002-08-23 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-08-23 |
Time |
15:11 |
Rev Time |
5.00 |
| Received By |
btrobaug |
Date |
2002-08-23 |
Time |
10:30 |
Sent To |
|
|
| Notes |
| 2002-08-23 00:00:00 | PROVISO | | | ~~~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | | | | PLEASE PROVIDE THE FOLLOWING INFORMATION | | | AND MAKE ANY NECESSARY CHANGES IN THE | | | PLANS FOR THE NEXT REVISIONS. | | | | | | 1} THE LOAD CALCULATIONS DID NOT CHANGE | | | ON THESE REVISIONS,PLEASE MAKE CHANGES | | | IN NEXT REVISION. | | | | | | 2} WATER HEATER ON E-2 IS NOT SHOWN IN | | | THE CALC'S ON THE SCHEDULE. | | | | | | 3} WHERE IS CIRCUIT K-39 FOR THE FIRE | | | SUPPRESSION? | | | | | | 4} THE TYPE "J" FIXTURES DESIGNATIONS | | | CHANGED,AND ARE NOT LISTED ON THE | | | REVISIONS AS SHEET E-8 WAS | | | MISSING.PLEASE SUPPLY INFORMATION FOR | | | THESE FIXTURES. | | | | | | 5} CIRCUIT K-62 IS LISTED TWICE ON E-1. | | | THE CONTRACTOR INDICATED THE ONE IN THE | | | DISHWASHER AREA WAS ON CIRCUIT K-42 BUT | | | THAT CIRCUIT FEEDS THE BATH AREAS,AND | | | THE CALC FOR THAT CIRCUIT DIDN'T CHANGE. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/659-8096 EXT.8392 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
7 |
Status |
P |
Date |
2002-01-04 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-01-04 |
Time |
11:39 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2002-01-03 |
Time |
16:57 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
6 |
Status |
F |
Date |
2001-11-21 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-11-21 |
Time |
15:14 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-11-21 |
Time |
12:15 |
Sent To |
|
|
| Notes |
| 2001-11-21 00:00:00 | ***************** UNSAT **************** | | | | | | 1)NOTE: PLEASE NOTE 700-12E CIRCUITS | | | FOR EM LTS, EXIT LTS SHALL BE FROM SAME | | | PANEL. | | | | | | | | | | | | | | | | | | | | | | | | 3)NOTE: PLEASE NOTE THAT ALL CONTINUOUS | | | LOADS ARE TO BE SHOWN AT 125%. | | | 215-2/230-42 ETC. | | | | | | 4)NOTE: PLEASE SHOW LOAD CALCULATIONS, | | | PER 220-11/220-3/220-10/220-13 ETC. | | | | | | 5)NOTE: PLEASE CLARIFY ATTACHMENT FOR | | | TRANSFORMER. PER 250-24 | | | | | | 6)NOTE: PLEASE NOTE OUTLET SPACING TO | | | MEET LOCAL CODE ON ALL LEVELS. | | | 210-50 PBCAC. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR] | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
F |
Date |
2001-07-21 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-07-21 |
Time |
10:27 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-07-21 |
Time |
10:27 |
Sent To |
|
|
| Notes |
| 2001-07-21 00:00:00 | ***************** UNSAT *************** | | | | | | | | | | | | 1)NOTE: PLEASE NOTE THAT PER ART;240-21- | | | C-3, TRANSFORMER SEEMS TO BE MORE THAN | | | 10' AWAY FROM "LDP" PLEASE NOTE 10' TAP | | | RULE. PLEASE PLACE NOTE ON RISER DIAGRAM | | | THAT TAPS NEED TO MEET 240-21."10"TAP. | | | IF OVER 10', A DISCONNECT WILL BE REQ`D. | | | | | | 2)NOTE: PLEASE NOTE ART; 450-21-B FOR | | | CLEARENCE ABOUT TRANSFORMER. PLEASE | | | CALRIFY RATING OF TRANSFORMER. | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
F |
Date |
2001-07-08 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-07-08 |
Time |
12:07 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-07-08 |
Time |
12:07 |
Sent To |
|
|
| Notes |
| 2001-07-08 00:00:00 | ************** UNSAT ************** | | | | | | 1)NOTE: PLEASE NOTE THAT NO ELECTRICAL | | | PLANS WERE SUBMITTED FOR REVIEW. | | | | | | PLEASE SUBMIT FOR REVIEW. IF THERE ARE | | | ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2001-02-16 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-02-16 |
Time |
11:44 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-02-16 |
Time |
11:44 |
Sent To |
|
|
| Notes |
| 2001-02-16 00:00:00 | ***************** UNSAT ************** | | | | | | 1)NOTE: PERMIT HAS NOT BEEN ISSUED YET A | | | ND PLANS THAT WERE RE-SUBMITTED ARE NOT | | | COMPLETE. ONLY, ES1.1,E2.1,E4.1,4.2,4.3 | | | WERE SUBMITTED? NEED TO HAVEALL THE | | | ORIG PLANS. | | | | | | | | | PLEASE SUBMIT THE ABOVE. IF THERE ARE | | | ANY QUESTIONS PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2001-01-11 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-01-11 |
Time |
19:53 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-01-11 |
Time |
19:53 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2000-11-30 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-11-30 |
Time |
21:36 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-11-30 |
Time |
21:36 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | **************** UNSAT *************** | | | | | | 1)NOTE: PLEASE PROVIDE MORE INFORMATION | | | ON TRANSFORMER TO CLARIFY ALL REQ`MENTS | | | OF 450-9 AND 450-21B | | | | | | 2)NOTE: PLEASE SEE E 4.2. PLEASE SEE | | | CONDUIT/CONDUCTORS AND BREAKERS FOR | | | FEEDS TO PANELS K1A AND K1B.. | | | | | | 3)NOTE: PLEASE NOTE THAT OUTLET SPACING | | | IS TO MEET LOCAL CODE OF EVERY 20` OF | | | UNENCUMBERED WALL SPACE.210-50 OF P. BCH | | | COUNTY AMENDMENTS. | | | | | | 4)NOTE: PLEASE SEE NOTE #37 ON E4.2 | | | THE CODE ART# 250-81 IS FROM THE "96" | | | NEC. PLEASE NOTE THAT WE ARE UNDER THE | | | "99" NEC AND ALL REFERENCES ON PLANS | | | NEED TO REFLECT "99" NEC. | | | | | | 5)NOTE: PLEASE PROVIDE SOME FORM OF | | | CLARIFICATION THAT LOADS FOR TRACK | | | LIGHTING IS SHOWN PER 220-12B. | | | | | | | | | 6)NOTE: PLEASE SHOW GROUNDING REQ`D BY | | | ART: 800-40 | | | | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
8 |
Status |
P |
Date |
2002-02-01 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-02-01 |
Time |
09:30 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-02-01 |
Time |
09:30 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
7 |
Status |
F |
Date |
2001-12-20 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-12-20 |
Time |
11:39 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-12-20 |
Time |
11:39 |
Sent To |
|
|
| Notes |
| 2001-12-20 00:00:00 | 1) PLEASE DEMONSTRATE THAT FIRE | | | SPRINKLER PLANS AND APPLICABLE | | | PERMITS HAVE BEEN APPLIED FOR. | | | 2) THE SCRUBBER SYSTEM REFERENCED | | | IN THE PLANS MUST BE EQUIPPED WITH | | | A SEPARATE FIRE EXTINGUISHING SYSTEM | | | THAN THAT OF THE HOOD,DUCT, AND | | | EXTINGUISHING SYSTEM PLANNED FOR THE | | | KITCHEN. NO DOWNGRADES OF THE EXHAUST | | | DUCT CAN OCCUR BECUASE OF THE SCRUBBER | | | SYSTEMS. | | | 3) WITH REGARDS TO WALL TERMINATIONS | | | OF KITCHEN EXHAUSTS, PLEASE REVIEW | | | ALL APPLICABLE CODE SECTIONS OF NFPA | | | 96 AND ENSURE COMPLIANCE. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
6 |
Status |
F |
Date |
2001-11-26 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-11-26 |
Time |
15:03 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-11-26 |
Time |
15:03 |
Sent To |
|
|
| Notes |
| 2001-11-26 00:00:00 | 1) IT WOULD APPEAR THAT ADDITIONAL | | | EXIT SIGN(S) ARE NEEDED FOR THE | | | MEZZANINE. | | | 2) NO FIRE SPRINKLER PLANS PROVIDED | | | WITH DRAWINGS. | | | 3) TABLES AND CHAIRS IN MAIN DINING | | | AREA ARE TOO CLOSE TOGETHER. | | | 4) SOME SOFFITS ARE SHOWN AT 6 FEET 8 | | | INCHES FROM THE FLOOR WHICH CONFLICTS | | | WITH THE STANDARD BUILDING CODE, | | | MINIMUM HEADROOM REQUIREMENTS. PLEASE | | | DETERMINE PROBLEM AREAS. | | | 4) MAXIMUM TRAVEL DISTANCE IN | | | SPRINKLER PROTECTED ASSEMBLY OCCUPANCIES | | | IS 200 FEET. | | | 5) A SEPARATE FIRE ALARM PANEL IS | | | NOT NECESSARY FOR TSUNAMI. THE FIRE | | | ALARM EQUIPMENT SHOULD BE CONNECTED | | | TO THE TOWER'S FIRE ALARM CONTROL | | | PANEL. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
5 |
Status |
F |
Date |
2001-07-31 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-07-31 |
Time |
13:07 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-07-31 |
Time |
13:06 |
Sent To |
|
|
| Notes |
| 2001-07-31 00:00:00 | 1) NO FIRE SPRINKLER DRAWINGS PROVIDED | | | WITH PLANS. | | | 2) LEATHER BOUND WALLS SHOWN FOR | | | ELEVATOR. WHAT ALLOWS THIS TO OCCUR. | | | 3) FIBERGLASS HOISTWAY WALLS SHOWN | | | FOR ELEVATORS. CODE DOES NOT ALLOW FOR | | | THIS. | | | 4) NO VENT SHOWN FOR HOT WATER HEATER | | | VENT. | | | 5) MORE DETAILS NEEDED ON SMOG HOG | | | GREASE FILTER UNIT SHOWN ON M2.2. | | | 6) EXHAUST DUCT TO SLOPE SHALL BE 1" | | | PER FOOT. | | | 7) EXIT STAIRS LOCATED ON THE EXTERIOR | | | SHALL BE SLIP RESISTANT. | | | 8) PLEASE SHOW HOW THE EXITS LOCATED | | | ON THE MEZZANINE LEVEL MEET THE | | | REQUIRED 1/2 DIAGONAL DIMENSION OF THE | | | ROOM OR AREA SERVED. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
F |
Date |
2001-06-27 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-06-27 |
Time |
08:36 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-06-27 |
Time |
08:36 |
Sent To |
|
|
| Notes |
| 2001-06-27 00:00:00 | 1) NO MECHANICAL,ELECTRICAL,PLUMBING OR | | | FIRE SPRINKLER DRAWINGS PROVIDED WITH | | | PLANS. | | | 2) SITTING CHAIRS LOCATED ON THE FIRST | | | AND SECOND FLOORS STILL APPEAR TO BE | | | TOO CLOSE TOGETHER. | | | 3) PLEASE VERIFY CEILING HEIGHTS. ALL | | | CEILING HEIGHTS ARE TO BE AT LEAST 7'-6" | | | IN THE MEANS OF EGRESS. PROJECTIONS FROM | | | THE CEILINGS IN THESE AREAS CANNOT BE | | | LESS THAN 6'-8". | | | 4) SCRUBBER(S) ARE NOTED ON THE PLANS. | | | PLEASE PROVIDE MORE DETAILS. | | | 5) ALL EXTERIOR STAIRS ARE TO BE SLIP | | | RESISTANT. | | | 6) HOW WIDE IS EXTERIOR EXIT STAIR AND | | | WHAT IS ITS EXIT CAPACITY. | | | 7) HOW ARE THE PORCELAIN SOCKETS UNDER | | | THE FLOOR POWERED, PROTECTED AND ARE | | | LISTINGS PRESENT. | | | 8) MORE INFORMATION NEEDED ON KITCHEN | | | HOOD,DUCT,SCRUBBERS,AND EXTINGUISHING | | | SYSTEMS. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
F |
Date |
2001-02-28 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-02-28 |
Time |
10:16 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-02-28 |
Time |
10:16 |
Sent To |
|
|
| Notes |
| 2001-02-28 00:00:00 | 1) PLEASE PROVIDE THIS OFFICE A USAGE | | | PLAN FOR THE ESTABLISHMENT. IT WAS FELT | | | BY THE PLAN REVIEW STAFF THAT CERTAIN | | | AREAS OF THE ESTABLISHMENT COULD BE | | | CLOSED OFF FROM OTHER SECTIONS. HOW | | | COULD THIS EFFECT EXITING. | | | 2) PLEASE INDICATE EXIT DISCHARGE | | | ROUTES FROM GROUND LEVEL, NORTH SIDE | | | OF BUILDING. HOW DOES EXIT DISCHARGE | | | OCCUR NEAR RETAIL SERVICE DRIVE, GATES. | | | 3) SEATING LOCATED ALONG WEST WALL | | | GROUND LEVEL IS TOO TIGHT. THESE TABLES | | | AND CHAIRS DO NOT ALLOW FOR THE MINIMUM | | | OF 12" BETWEEN THE BACKS OF THE CHAIRS. | | | 4) DOOR 12D IS NOT WIDE ENOUGH. MUST BE | | | 32 INCHES IN THE CLEAR. | | | 5) DOOR 11E AND 11F NOT WIDE ENOUGH. | | | MUST BE 32 IN THE CLEAR. | | | 6) CRAWL SPACE TO BE FIRE SPRINKLER | | | PROTECTED WHERE BAR EQUIPMENT IS STORED. | | | 7) DOTTED LINE NEAR 11C ON PAGE A2.1 | | | SIGNIFIES WHAT. | | | 8) FIRE SPRINKLER HEAD DISCHARGE | | | PATTERNS ARE NOT TO BE AFFECTED BY THE | | | FIBERGLASS PANELS. | | | 9) THE KITCHEN EXHAUST DUCTS THAT | | | EXTEND HORIZONTALLY COULD INTERFERE WITH | | | EXITING FROM THE BUILDING. PLEASE | | | EXPLAIN RATIONALE. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2000-12-27 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-12-27 |
Time |
13:48 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2000-12-27 |
Time |
13:48 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1) PLEASE INDICATE WHERE THE 994 | | | ESTIMATED VISITORS TO TSUNAMI WILL | | | PARK. THE FIRE LANE LOCATED ON THE | | | SOUTH SIDE OF THE HIGH-RISE BUILDING | | | IS TO REMAIN CLEAR AND UNOBSTRUCTED. | | | PLEASE ADVISE PARKING ARRANGEMENT TO | | | THIS OFFICE. | | | 2) PLEASE PROVIDE MORE DETAILS ON | | | UNDERGROUND MECHANICAL ROOM SHOWN ON | | | PAGE A2.0. NO FIRE SPRINKLERS, EMERGENCY | | | LIGHTING, OR EXIT SIGNS ARE SHOWN, AND | | | ONLY ONE MEANS OF EGRESS IS SHOWN. | | | 3) FIBERGLASS PROJECTION SCREENS ARE TO | | | MEET APPLICABLE FLAME SPRED CRITERIA. | | | 4) DOES THE WOOD LATTICE WORK MEET | | | THE APPLICABLE FLAME SPREAD CRITERIA. | | | 5) PLEASE EXPLAIN WHAT THE ELECTRIC | | | TRANSFORMER ON PAGE A7.1 IS FOR. WHY | | | IS IT LOCATED BELOW THE EXIT STAIR. | | | 6) WHAT PROTECTION IS PROVIDED FOR THE | | | NEW FIRE RAMP SHOWN ON PAGE A7.1. IT | | | APPEARS THAT THIS RAMP PASSES BY TWO | | | WINDOWS AND POSSIBLY A DOOR. | | | 7) THE GAS INSTALLATION TO COMPLY WITH | | | NFPA 54. | | | 8) PLEASE PROVIDE SET-BACK DISTANCES | | | TO ADJACENT BUILDINGS, PROPERTY LINES, | | | EXITS FROM THE THREE GREASE HOOD | | | EXHAUST FANS. | | | 9) PLEASE EXPLAIN RATIONALE FOR SINGLE | | | MEANS OF EGRESS FROM DINING BALCONY. | | | 10) NO FIRE SPRINKLER PLANS OR HYDRAULIC | | | CALCULATIONS PROVIDED WITH PLANS. THESE | | | ITEMS MUST BE SUBMITTED PRIOR TO | | | RECEIVING A BUILDING PERMIT. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2000-11-09 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-11-07 |
Time |
11:06 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2000-11-07 |
Time |
09:16 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1) PLEASE IDENTIFY MAIN ENTRY AND EXIT. | | | THIS LOCATION IS TO PROVIDE EXITING | | | FOR AT LEAST 50 PERCENT OF THE OCCUPANT | | | LOAD. | | | 2) OCCUPANT LOAD TO BE DETERMINED BY | | | THIS OFFICE. | | | 3) PROVISIONS ARE TO BE MADE FOR AT | | | LEAST TWO HANDICAPPED PERSONS. | | | 4) ALL AWNINGS ARE TO BE FIRE RETARDANT. | | | 5) NO FIRE SPRINKLER DRAWINGS OR | | | HYDRAULIC CALCULATIONS PROVIDED WITH | | | PLANS. ENTIRE SPACE IS TO BE COMPLETELY | | | FIRE SPRINKLER PROTECTED. THIS INCLUDES | | | ALL MECHANICAL, ELECTRICAL, AND SERVICE | | | ROOMS. ALL VERTICAL SHAFTS ARE ALSO TO | | | BE PROTECTED. | | | 6) PROVIDE COMPLETE FIRE ALARM SYSTEM | | | SHOP DRAWINGS FOR FIRE ALARM EQUIPMENT | | | SHOWN ON DRAWINGS. CUT SHEETS, AND | | | WIRING DIAGRAMS ARE TO BE SUBMITTED WITH | | | SHOP DRAWINGS UNDER SEPARATE PERMIT. | | | 7) MORE DETAILS ARE NEEDED FOR THE | | | PULL OUT PLATFORM. WHAT IS IT USED FOR. | | | 8) PLEASE DEFINE CRAWL SPACE. WHAT IS | | | THIS USED FOR. | | | 9) ANY CHANGES IN ELEVATION LESS THAN | | | 21 INCHES SHALL BE BY RAMPS. STEPS WHEN | | | USED ARE TO BE A MINIMUM OF THREE. | | | 10) THERE APPEARS TO BE TWO STEPS NEAR | | | THE ELEVATOR ON THE MEZZANINE LEVEL. | | | THIS WILL NOT BE PERMITTED. | | | 11) PLEASE EXPLAIN SLIDING WALLS. | | | 12) SOME GATES SWING IN AND SOME SWING | | | OUT PLEASE EXPLAIN RATIONALE. | | | 13) PLEASE EXPLAIN SERVICE CATWALK. | | | 14) PLEASE BE ADVISED THAT TURNSTILES | | | OR OTHER DEVICES CANNOT BE INSTALLED | | | TO INTERFERE WITH THE MEANS OF EGRESS | | | IN ASSEMBLY OCCUPANCIES. | | | 15) PLEASE CHECK INTERIOR FINISH | | | NOTES. NOTES SUGGEST CLASS C, THIS | | | INFORMATION APPEARS TO BE INCORRECT. | | | 16) PLEASE EXPLAIN CEILING HEIGHT OF | | | 4'-7" ON PAGE A11.4 | | | 17) DUCT SMOKE DETECTORS REQUIRED IN | | | AIR-HANDLING SYSTEMS OVER 2000CFM. | | | 18) ADDITIONAL EMERGENCY LIGHTING | | | EQUIPMENT APPEARS TO BE NEEDED. | | | 19) PLEASE INDICATE PLATFORM | | | CONSTRUCTION. | | | 20) CLEARLY EXPLAIN EXITING FROM | | | MEZZANINE. | | | | | | PLANS REVIEWED BY CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2002-12-19 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-12-19 |
Time |
09:59 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2002-12-19 |
Time |
09:59 |
Sent To |
B |
|
| Notes |
| 2002-12-19 00:00:00 | TO JIM WITMER. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2002-12-17 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-12-17 |
Time |
13:08 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2002-12-17 |
Time |
13:08 |
Sent To |
B |
|
| Notes |
| 2002-12-17 00:00:00 | TO JIM./WRT |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
7 |
Status |
P |
Date |
2001-12-21 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-12-21 |
Time |
09:41 |
Rev Time |
2.00 |
| Received By |
pkrauss |
Date |
2001-12-21 |
Time |
10:06 |
Sent To |
|
|
| Notes |
| 2001-12-21 00:00:00 | | | | ADDITIONAL PERMITS REQUIRED FOR HOOD, | | | FIRE SUPRESSION AND WALK-IN COOLERS. | | | PROVIDE PLANS AND ALL MANUFACURER | | | SUBMITTAL DATA AND PRODUCT APPROVALS | | | WITH PERMIT APPLICATION. | | | | | | PLEASE NOTE, THE GREASE DUCT SHALL BE | | | DESIGNED AND INSTALLED IN A MANNER TO | | | PROVIDE AN AIR VELOCITY WITHIN THE DUCT | | | SUSTEM OF NOT LESS THAN 1,500 FT PER | | | MINUTE. 1997 SMC 505.7 | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
6 |
Status |
F |
Date |
2001-11-29 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-11-29 |
Time |
13:28 |
Rev Time |
6.00 |
| Received By |
pkrauss |
Date |
2001-11-29 |
Time |
12:24 |
Sent To |
|
|
| Notes |
| 2001-11-29 00:00:00 | *******************DENIED*************** | | | | | | | | | PLEASE PROVIDE THE FOLLOWING INFORMATION | | | FOR REVIEW. | | | | | | 1.PLAN SHEET AC.8, OUTSIDE AIR | | | RECAPULATION REFLECTS RTU'S.NO | | | RTU'S OR OUTSIDE AIR REFLECTED ON | | | PLANS. | | | | | | 2.PLAN SHEET AC.2, PROVIDE DETAIL OF | | | ITEM 4 SOUND LINED PLENUM. | | | | | | 3.INDICATE ACCESSIBLITY FOR SERVICE | | | FOR AHU'S 1,2, & 3. | | | | | | 4.PLEASE CLARIFY "PH-1,2,3,& 4", | | | PROVIDE DETAIL OF RISER TO PENTHOUSE | | | | | | 5.IDENTIFY KITCHEN EXHAUST TERMINATION | | | PLEASE NOTE AS PER 1997 SMC 506.1, | | | DUCTS SERVING COMMERCIAL FOOD | | | COOKING AND PROCESSING, SHALL | | | TERMINATE OUTSIDE OF THE BUILDING | | | AND BE LOCATED 10' FROM ANY ADJACENT | | | PROPERTY LINE, PARKING AREA, A | | | ADJACENT BUILDING, WINDOW, DOOR, OR | | | AIR INTAKE OPENING AND SHALL BE A | | | MIN. OF 40" ABOVE THE ROOF SURFACE. | | | | | | 5.PROVIDE MANUFACTURER SUBMITTAL DATA | | | FOR THE SMOG HOG. | | | | | | 6.FIRE DAMPER DETAIL-PLAN SHEET AC.5, | | | INDICATES VERTICLE PENERATION.FIRE | | | DAMPERS DEPICTED ON PLAN SHEET AC.3 | | | ARE FLOOR/CEILING PENETRATIONS. ALL | | | FIRE DAMPERS SHALL COMPLY WITH UL | | | 555. | | | | | | ADDITIONAL PLANS AND PERMITS REQUIRED | | | FOR HOOD, FIRE SUPRESSION AND WALK-IN | | | COOLERS.PLEASE SUBMIT MANUFACTURER | | | SUBMITTAL DATA AND PLANS WITH PERMIT | | | APPLICATION. | | | | | | PLEASE NOTE, A LETTER FROM THE ENGINEER | | | AND OR ARCHITECT ADDRESSING COMMENTS AND | | | INDICATING CHANGES AND RESPONSES TO | | | COMMENTS WOULD GREATLY HELP EXPEDITE | | | PLANS IN THE FUTURE. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
5 |
Status |
F |
Date |
2001-07-17 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-07-17 |
Time |
14:51 |
Rev Time |
1.30 |
| Received By |
pkrauss |
Date |
2001-07-17 |
Time |
13:29 |
Sent To |
|
|
| Notes |
| 2001-07-17 00:00:00 | ******************DENIED**************** | | | | | | | | | PLEASE PROVIDE INFORMATION/DETAIL ON | | | FIRE RATED ENCLOSURE AS CALLED OUT ON | | | DRAWING M2.2, HOOD EXHAUST ELEVATION. | | | | | | NOTE:GREASE HOOD DUCT SHALL HAVE A | | | MINIMUM OF 1" PER FOOT SLOPE | | | TOWARD HOOD AS PER 1997 SMC 505.4 | | | | | | EXHAUST OUTLET SHALL TERMINATE | | | 10' FROM ANY ADJACENT BUILDING, | | | PROPERTY LINE, WINDOW, DOOR, OR | | | AIR INTAKE | | | | | | | | | ADDITIONAL PERMITS REQUIRED FOR HOOD, | | | FIRE SUPRESSION, GAS, OR WALK-IN COOLER. | | | PLEASE PROVIDE PLANS AND MANUFACTURER | | | DETAIL/ENGINEERED DRAWINGS. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | | PATTY KRAUSS AT 659-8096 EXT. 8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
N |
Date |
2001-06-28 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-06-28 |
Time |
12:28 |
Rev Time |
0.20 |
| Received By |
pkrauss |
Date |
2001-06-28 |
Time |
12:12 |
Sent To |
|
|
| Notes |
| 2001-06-28 00:00:00 | ******************DENIED**************** | | | | | | | | | INSUFFICIENT INFORMATION FOR MECHANICAL | | | REVIEW.PLEASE SUBMIT PLANS WITH | | | MECHANICAL PERMIT APPLICATION. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | | PATTY KRAUSS AT 659-8096 EXT. 8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2001-03-02 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-02-20 |
Time |
14:56 |
Rev Time |
2.00 |
| Received By |
pkrauss |
Date |
2001-02-26 |
Time |
15:16 |
Sent To |
|
|
| Notes |
| 2001-02-26 00:00:00 | DETAIL OF ACCESS DOORS NEED TO BE | | | REFLECTED ON PLANS SIZE AND LOCATION TO | | | SHOW COMPLIANCE WITH 1997 SMC 304.2. | | | | | | MISSING PLAN A3.1M (MEZZANINE REFLECTED | | | CEILING).ACCESS FOR SERVICE FOR AHU'S | | | 1-4 AND AHU 7 AND 8. | | | | | | DRAWING M1.3 - NOTE 7 IS THE FRESH AIR | | | BEING BROUGHT IN BEHIND PANELS?MUST | | | COMPLY WITH 97 SMC 501.2 & ASHRAE 62-89. | | | | | | AS PER NFPA 4-4.4.3, DUCT SMOKE | | | DETECTORS WITH NOTIFICATION TO | | | HORN/STROBE IN NORMALLY OCCUPIED AREA. | | | | | | NOTE:ADDITIONAL PERMITS REQUIRED FOR | | | HOOD, FIRE SUPRESSION, SUBMIT PLANS | | | WITH APPLICATION. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2001-01-17 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2001-01-17 |
Time |
10:26 |
Rev Time |
0.33 |
| Received By |
pkrauss |
Date |
2001-01-17 |
Time |
10:25 |
Sent To |
|
|
| Notes |
| 2001-01-17 00:00:00 | 1. PROVIDE DETAIL SHOWING ACCESSIBILITY | | | FOR AHU SERVICE SMC 304.2. NO REFERENCED | | | DWG. M3.1-M3.3, ALSO NO M5.1 DWG. | | | 2. PROVIDE ELEVATION DETAIL SHOWING | | | TERMINATION OF EXHAUST FANS AND OUTSIDE | | | AIR INTAKE OPENINGS IN RELATION TO EACH | | | OTHER & OTHER OPENINGS INTO THE | | | BUILDING INCLUDING DOORS & OPERABLE | | | WINDOWS.HAVE MINIMUM REQUIRED | | | DISTANCES SHOWN ON PLAN, PERNFPA 96 | | | 4-8.3. | | | 3. PROVIDE INFORMATION ON GREASE | | | EXHAUST DUCT LOCATION & TERMINATION | | | INCLUDING | | | SIZES SHOWING PROXIMITITY TO OTHER | | | BUILDING COMPONENTS FOR REVIEW FOR | | | COMPLIANCE WITH 1997 SMC CHAPTER 5 & | | | NFPA 96.YOUR RESPONSE (12/18/00), | | | REF. DETAIL ON DWG. M3.1., THERE WAS NO | | | SUCH DWG. SUBMITTED. | | | 4.NO VENTILATION FOR UNDERGROUND MECH. | | | RM. AS PER SMC 501.2.ALSO, THERE IS | | | NOIB-B DOOR ON SCHEDULE. | | | 5. DWG. M1.1 HAS NO NOTE #14. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2000-11-30 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-11-30 |
Time |
08:15 |
Rev Time |
2.50 |
| Received By |
jleech |
Date |
2001-07-12 |
Time |
19:25 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ************DENIED********************** | | | | | | 1.PROVIDE OUTSIDE AIR SCHEDULE PER | | | ASHRAE 62-89 | | | 2. PROVIDE AIR BALANCE SCHEDULE SHOWING | | | COMPLIANCE WITH 1997 SMC 501.2. | | | 3. PROVIDE DETAIL SHOWING REQUIRED | | | ACCESSIBILITY FOR AHU SERVICE AND MANUF- | | | ACTURES REQUIRED COIL PULL AND OTHER | | | MAINTAINANCE CLEARANCE REQUIREMENTS ARE | | | DEDICATED CLEAR AREAS FOR UNIT ACCESS | | | PER 1997 SMC 304.2 AND NEC FOR ELECTRICA | | | CLEARANCE REQUIREMENTS | | | 4. AHU #6 RETURN AIR PLENUM IS LOCATED | | | IN A ROOM WITH GAS WATER HEATER. 1997 | | | SMC 609.1.3 PROHIBITS WATER HEATERS USE- | | | ING GAS FUEL BEING LOCATED IN THIS TYPE | | | LOCATION. | | | 5. PROVIDE ELEVATION DETAIL SHOWING | | | TERMINATION OF EXHAUST FANS AND OUTSIDE | | | AIR INTAKE OPENINGS IN RELATION TO EACH | | | OTHER AND OTHER OPENINGS INTO THE BUILD- | | | ING INCLUDING DOORS AND OPERABLE WINDOWS | | | HAVE MINIMUM REQUIRED DISTANCES SHOWN ON | | | PLAN. | | | 6. PROVIDE INFORMATION ON GREASE EXHAUST | | | DUCT LOCATION AND TERMINATION INCLUDING | | | SIZES SHOWING PROXIMITY TO OTHER BUILD- | | | ING COMPONENTS FOR REVIEW FOR COMPLIANCE | | | WITH 1997 SMC CHAPTER 5 AND 1994 NFPA 96 | | | 7. NOTE: SEPARATE PERMITS ARE REQUIRED | | | FOR THE FOLLOWING SYSTEMS; HOODS, INCLUD | | | ING GREASE DUCT AND MAKE UP AIR DUCTS AN | | | WALKIN COOLERS AND FREEZERS. COMPLETE | | | PLANS SHALL BE PROVIDED FOR THESE SYSTEM | | | COMPONENTS AT TIME OF MECHANICAL PERMIT | | | APPLICATION FOR THESE ADDITIONAL PERMITS | | | 8. AHU 5 AND AHU 6 HAVE NO RETURN AIR | | | PATH FROM AREA SERVED BY AHU'S | | | 9. PRIVATE ROOM OFF BATHROOMS ON MEZZAN- | | | INE LEVEL DOES NOT HAVE VENTILATION TO | | | SPACE. | | | 10.PROVIDE LOCATION OF ALL REQUIRED | | | MANUAL VOLUME DAMPERS FOR TEST AND BALA- | | | NACE PURPOSES. | | | 11. SHOW LOCATIONS OF ALL FIRE DAMPERS | | | AT RATED WALLS PER 1997 SMC 610.6 AND | | | 610.1.2 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
9 |
Status |
F |
Date |
2002-12-30 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-12-30 |
Time |
16:45 |
Rev Time |
0.25 |
| Received By |
kstevens |
Date |
2002-12-30 |
Time |
16:45 |
Sent To |
|
|
| Notes |
| 2002-12-30 00:00:00 | DENIED | | | REFERENCE: FBC-2001 CHAPTER 11 | | | | | | 1) REVISION OF EMPLOYEES RESTROOM NOT | | | APPROVED. SECTION 11-4.1(6) IF TOILET | | | FACILITIES ARE PROVIDED ON A SITE, THEN | | | EACH SUCH PUBLIC OR COMMON USE TOILET | | | FACILITY SHALL COMPLY WITH 4.22. IF BATH | | | ING FACILITIES ARE PROVIDED ON A SITE, | | | THEN EACH SUCH PUBLIC OR COMMON USE | | | BATHING FACILITY SHALL COMPLY WITH SEC | | | 4.23. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
8 |
Status |
N |
Date |
2002-01-13 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2002-01-13 |
Time |
14:41 |
Rev Time |
3.00 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-01-13 00:00:00 | PROVISO: 8TH PLBG PLAN REVIEW | | | DEPT OF HOTEL BUSINESS REGULATION REVIEW | | | AND COMMENTS, ATTACHED TO PLANS BEFORE | | | ISSUING PLUMBING PERMIT. | | | END OF COMMENTS PAUL SCHMITZ | | | 561-659-8096X8233 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
7 |
Status |
F |
Date |
2001-11-28 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-11-28 |
Time |
13:01 |
Rev Time |
6.00 |
| Received By |
kstevens |
Date |
2001-11-28 |
Time |
13:01 |
Sent To |
|
|
| Notes |
| 2001-11-28 00:00:00 | DENIED (SEVENTH TIME) | | | REFERENCE: SPC-94 - SGC-97 - FACBC-97 | | | | | | 1) DEPT OF HOTEL BUSINESS REGULATION | | | PLAN REVIEW W/COMMENTS REQUIRED BEFORE | | | PLUMBING PLAN REVIEW. CONTACT FOR | | | APPOINTMENT. (954) 958-5520 | | | 2) SHT A1.3 (CHANGED FROM A2.1) MEN & | | | WOMEN RESTROOMS PREVIOUS COMMENT RE: | | | DCA-FLBC RULE 9B-7.0042 FL ADM. CODE, | | | SEC 4.17.3 FIG 30(E). CLEAR FLOOR SPACE | | | FOR W/C AND LAV. | | | 3) SHT A10.1, EMPLOYEE REST RM, SHOWER | | | STALL, COMPLY W/SEC 4.21 ADA SHOWER | | | STALL. SHOW DETAILS (FM PREVIOUS P-REV.) | | | 4) FM PREVIOUS REVIEW, SHT A2.1, A2.M1, | | | COMPLY WITH SEC 4.1.3(19)(A). ADA FIXED | | | SEATING IN A RESTURANT. NO DETAILS SHOWN | | | 5) FM PREVIOUS REVIEW,SHT M2.1.2.3, CON- | | | DENSATE FROM 7-AHU, PROVIDE AN ISOMETRIC | | | DRAWING OF A COMMON COLLECTION SYSTEM TO | | | A DRY WELL OR STORM DRAIN WITH A RELIEF | | | VINT. SEC 804.3, 104. | | | 6) FM PREVIOUS REVIEW. SEE ATTACHED GAS | | | PERMIT APPLICATION REQUIREMENTS. ADDRESS | | | #'S 1-3-7 & 9 FOR PLAN REVIEW. (ELECT. | | | W/HEATER) | | | 7) FM PREVIOUS REVIEW. SHT P1.7 DETAIL | | | #10 FUNNEL DRAIN, FLOOR SINKS REQUIRED | | | FOR ALL INDIRECT WASTE. S-802. FD STILL | | | SHOWN FOR WALK IN COOLERS SHT'S P1, P4, | | | & P6. | | | 8) FM PREVIOUS REVIEW. DETAIL FOR ICE | | | MACHINE NOT SHOWN. CONDENSER UNIT AND | | | ICE BIN DRAINS TO BE SEPARATED. CROSS | | | CONNECTION OF CONTAMINATED WASTE. SEC | | | 804 FOOD HANDLING. | | | 9) SHT P.1 ITEM #14 SMOKE HOG. INDIRECT | | | WASTE TO COMPLY WITH SPC SEC 805.1.1 & | | | 805.1.2 | | | 10) SHT P.1 ITEMS # 6 AND 22 NOT FOUND. | | | 11) SHT P.3 #'S 6 & 7, WATER HAMMERAR- | | | RESTORS TO BE LOCATED NEAR FIXTURES NOT | | | AT TOP OF DROPS AS SHOWN. "IN AN EFFECT- | | | IVE RANGE OF FIXTURE." | | | 12) SHT P.4 BACK TO BACK LAVS NOT VENTED | | | (LAV-2) | | | 13) SHT P.4 GAS ISOMETRIC DIAGRAM. UNION | | | REQUIRED BETWEEN MANUAL VALVE AND SOLIN- | | | OID VALVE.(#'S 7 AND 8). ALSO RE: FS-1 | | | ITEM #7 NOT SHOWN ON ISOMETRIC. | | | 14) SHT P.8 #58 HUB DRAIN NOT APPROVED. | | | 15) SHT P.8 #53 NO POLYETHYLENE JACKET | | | FOR UNDERGROUND PIPING. REF STD GAS CODE | | | 1997 ONLY FOR GAS INSTALLATION. | | | 16) SHT P.8 #14 BACKFLOW REQUIRED FOR | | | TEMP CONSTRUCTION WATER. | | | 17) SHT FS-1 ITEM #2, DEEP FAT FRYER | | | SHALL NOT DRAIN INTO GREASE LINE. | | | 18) SHT FS-1 ITME #4, CHINESE RANGE. | | | WASTE WATER WHEN DISCHARGED INTO THE | | | BUILDING DRAINAGE SYSTEM SHALL BE AT A | | | TEMPERATURE NOT HIGHER THAN 140 DEGREES | | | F. SPC SEC 717.8 | | | 19) SHT FS-1 ITEM #20.1 NSF APPROVAL RE- | | | QUIRED FOR FILTER. PROVIDE DETAILS. | | | 20) SHT FS-1 ITEM #41.2, 43.1 & 43.2 NOT | | | SHOWN. | | | 21) SHEETS REFERED TO IN PREVIOUS REVIEW | | | (6TH) DO NOT APPEAR ON PLANS SUBMITTED | | | FOR THIS REVIEW. PLEASE KEEP PAGES UNI- | | | FORM FROM REVIEW TO REVIEW TO EXPIDITE | | | THE REVIEW PROCESS. | | | | | | REVIEW BY KEN STEVENS | | | (561)- 659-8096 EXT 8377 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
6 |
Status |
F |
Date |
2001-07-22 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2001-07-22 |
Time |
06:38 |
Rev Time |
3.00 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-07-22 00:00:00 | PLUMBING PLAN REVIEW DENIED (SIXTH TIME) | | | NOTE ON PLANS,NEW PLANS SUBMITTED. | | | (1) DEPT. OF HOTEL BUSINESS REGULATION | | | PLAN REVIEW W/COMMENTS REQUIRED, BEFORE | | | PLUMBING PLAN REVIEW.CONTACT FOR APPOINT | | | MENT 954-958-5520. | | | (2) SHT A2.1,A2.M1 MEN & WOMEN REST RM'S | | | PREVIOUS COMMENT RE: HANDICAP STALLS | | | SEE REVISION: DCA-FLBC,RULE 9B-7.0042, | | | FL ADM.CODE, SEC 4.17.3.FIG 30(E). | | | CLEAR FLOOR SPACE FOR W/C AND LAVATORY. | | | (3) SHT A2.1 EMPLOYEE REST RM, SHOWER | | | STALL, COMPLY W/SEC 4.21, ADA SHO.STALL. | | | (3)SHT A2.1,A2.M1, COMPLY WITH SEC 4.1.3 | | | (19)(A).ADA FIXED SEATING IN A RESTURANT | | | (4) SHT A1.2 DETAIL ADA (A)(A1).NOT CUR- | | | RENT.SEE NOTE 2 ABOVE. | | | (5) SHT A10.2 HANDICAP URINAL SEC 4.18.3 | | | CLEAR FLR SPACE 30"X 48". | | | (6) SHT E3.3 LOCATION OF WTR/HTR, TYPE | | | IS NOT CLEAR IF THIS IS ELECTRIC OR GAS | | | W/H, SHT A2.0 SHOWS ELECTRIC, SHT P1.6 | | | SHOWS GWH ON A ELECTRIC W/H SCHEDULE? | | | (7) SHT M2.1.2.3, CONDENSATE FROM 7-AHU. | | | PROVIDE A ISOMETRIC DRAWING OF A COMMON | | | COLLECTION SYSTEM TO A DRY WELL OR STORM | | | DRAIN, WITH A RELIEF VENT,SEC,804.3,104. | | | (8A) SHT P1.5 SEC 104.3 PLANS REQUIRED. | | | PROVIDE ISOMETRIC DRAWINGS FOR THE GAS | | | PIPING AND SANITARY DWV. | | | (8B) SEE ATTACHED GAS PERMIT APPLICATIO | | | REQUIRMENTS, ADDRESS EA OF (10) ITEMS, | | | FOR PLAN REVIEW. | | | (9) SEC 104.3 PROVIDE KITCHEN EQUIPMENT | | | PLANS , WITH EQUIPMENT SCHEDULE,LAY OUT. | | | (10A)SHT P1.3,SEC 802 ALL INDIRECT WASTE | | | TO FLR SINKS,SAFE WASTE NOT ALLOWED. | | | (10B) SUSHI BAR, STILL NO VENT SHOWN. | | | (11A) SHT P1,4 WATER PIPING ISOMETRIC. | | | (MCWC94) SHOW PIPE SIZES, NO MORE THAN 2 | | | FIXTURES ON 1/2" C/W, NO MORE THAN 4 | | | FIXTURES ON 1/2" H/W. | | | (11B) SHT-P1.4 SHOWS AIR CHAMBERS, | | | SHT P1.6 REFERENCES WATER HAMMER ARREST- | | | ORS, REMOVE AIR CHAMBERS AND REFERENCE | | | THE WATER HAMMER ARRESTORS, AS LISTED. | | | (12) SHT P1.5 ISOMETRIC INCORRECTLY | | | LABLED,SHOULD BE GREASE WASTE. | | | (13A)SHT P1.6 PLBG NOTES #14, DIELECTRIC | | | UNIONS, NOT ALLOWED, SEC 608,MATERIALS. | | | (13B) FOOD SERVICE NOTE #2-7"TO 11" W/C, | | | FL PUBLIC UTILITIES SUPPLIES 12"-14"W/C. | | | (14A) SHT P1.7 DETAIL #10 FUNNEL DRAIN, | | | FLOOR SINKS FOR ALL INDIRECT WASTE.S-802 | | | (14B) DETAIL #18 UNIONS IN CEILING, NOT | | | PERMITED. NFPA-54 SEC 3.4.2 | | | (14C) DETAIL #21 ICE MACHINE, CONDENSER | | | UNIT & ICE BIN DRAINS,TO BE SEPERATED, | | | CROSS CONNECTION OF CONTAMINATED WASTE. | | | SEC 804 FOOD HANDLING. | | | (14D) DETAIL #22, NO VENT ON WATER HTR. | | | (15)SHT P1.3 DISHWASHER DRAIN CONNECT | | | I/D TO SANI.SEWER, LOCAL ORD.#2938-96. | | | END OF COMMENTSPAUL SCHMITZ | | | QUESTIONS 561-659-8096X8233 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
5 |
Status |
F |
Date |
2001-07-12 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2001-07-12 |
Time |
19:33 |
Rev Time |
2.50 |
| Received By |
pschmitz |
Date |
2001-07-12 |
Time |
19:33 |
Sent To |
|
|
| Notes |
| 2001-07-12 00:00:00 | DENIED; | | | | | | 1.RISER DIAGRAMS; | | | A.GREASY WASTE RISER DIAGRAM; | | | 1.MOP SINK SHALL DISCHARGE TOH | | | GREASY WASTE. | | | 2.NO INDIRECT WASTES. FLOOR | | | SINKS SHALL BE USED TO RECIEVE | | | DISCHARGE FROM PLUMBING | | | FIXTURES. | | | B.SANITARY RISER DIAGRAM REQUIRED. | | | C.WATER RISER DIAGRAM; | | | 1.SIZE PIPE. | | | 2.DISHWASHER SHOULD BE 3/4" | | | D.GAS RISER DIAGRAM REQUIRED. | | | | | | 2.WHERE IS WATER HEATER LOCATED? SHOW | | | EXHAUST AND MAKE UP AIR REQUIRED. | | | | | | 3.HOW IS PLUMBING IN SUSHI BAR VENTED? | | | | | | 4.SEE ATTACHED SHEET (GAS PERMIT | | | APPLICATION REQUIREMENTS) | | | | | | PLAN REVIEW BY; | | | JOHN LEECH | | | 659-8096 EXT 8369 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
N |
Date |
2001-07-07 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2001-07-07 |
Time |
10:54 |
Rev Time |
1.00 |
| Received By |
jleech |
Date |
2001-07-07 |
Time |
10:53 |
Sent To |
|
|
| Notes |
| 2001-07-07 00:00:00 | PLUMBING PAGES MISSING FROM PLANS. NO | | | PLUMBING PLAN REVIEW DONE. | | | JOHN LEECH | | | 659-8096 EXT. 8369 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2001-03-02 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2001-03-02 |
Time |
07:21 |
Rev Time |
4.00 |
| Received By |
jleech |
Date |
2001-03-02 |
Time |
07:21 |
Sent To |
|
|
| Notes |
| 2001-03-02 00:00:00 | DENIED; | | | | | | 1.P5 & P6 GAS SHUTOFF FOR COOKING APPL. | | | MUST BE READLY ACCESSIBLE AND | | | PROTECTED FROM DAMAGE. SGC 310.1. | | | | | | 2.SHOW SHUTOFF VALVE,AUTOMATIC SHUTOFF | | | VALVE AND UNION ONE GAS RISER DIAGRAM. | | | | | | 3.P3 NOTE 8 WASTE PIPE SHALL NOT BE | | | REDUCED BETWEEN THE CONNECTION OF THE | | | EQUIPMENT AND THE DISCHARGE POINT. | | | | | | 4.FLOOR SINKS ARE REQUIRED IN PLACE OF | | | HUB DRAINS; PLEASE MAKE THE FOLLOWING | | | CHANGES. | | | A.P3 NOTE 11 | | | B.P3 NOTE 1 | | | C.P5 GREASE WASTE RISER DIAGRAM | | | D.P6 DETAIL 10 | | | E.P7 FLOOR DRAIN SCHEDULE | | | | | | 5.P6 (9)D/M WASTE DETAIL. DISHWASHER | | | SHALL DISCHARGE TO SANITARY. DELETE | | | GREASE WASTE FROM DETAIL. | | | | | | 6.P6 (18) COOKING APPL. GAS PIPE. SHOW | | | UNION DOWN STREAM OF SOLENOID VALVE. | | | | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 659-8096 EXT. 8377 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2001-01-10 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2001-01-10 |
Time |
15:59 |
Rev Time |
3.00 |
| Received By |
jleech |
Date |
2001-01-10 |
Time |
15:58 |
Sent To |
|
|
| Notes |
| 2001-01-10 00:00:00 | DENIED; | | | | | | 1.ALL HANDICAP TOILET STALLS SHALL | | | COMPLY TO 4.17 (EXCEPTION; NEW | | | CONSTRUCTION) PAGE 50. | | | | | | 2.ELEVATION DRAWING (5) PAGE A10.2 | | | HANDICAP URINALS CLEAR FLOOR SPACE IS | | | 30" NOT 29". | | | | | | 3.P-7 PLUMBING SPECIFICATIONS WATER | | | (ASSEMBLY) CHANGE NOTE ABOUT 50/50 | | | SOLDER AND FLUX TO NO LEAD AND WATER | | | SOLUBLE FLUX. | | | | | | 4.P-1 AND P5 DRAWINGS DO NOT MATCH | | | ARCHITECTURAL DRAWINGS. | | | | | | 5.FLOOR DRAINSOR FLOOR SINKS TO BE USED | | | PLACE OF FUNNEL DRAINS. | | | | | | 6.NEED LONGEST RUN OF GAS PIPE WITH | | | GAS RISER DIAGRAM. | | | | | | 7.FIRST FLOOR RISER DIAGRAM NOT TO FLOOR | | | PLAN. | | | | | | 8.MEZZANINE RISER DIAGRAM NOT TO FLOOR | | | PLAN. | | | | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 659-8096 EXT. 8377 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2000-11-20 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2000-11-20 |
Time |
15:27 |
Rev Time |
3.00 |
| Received By |
jleech |
Date |
2000-11-20 |
Time |
15:26 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1.BATHROOM FACILITYS ON FIRST FLOOR MUST | | | COMPLY WITH 97 FL0RIDA ACCESSIBILITY | | | CODE FOR BUILDING CONSTRUTION #11 | | | PAGE 21 AND 4.17. | | | | | | 2.HANDICAP LAVATORIES MUST MEET | | | CLEARANCES PER FIG. #31. | | | | | | 3.KITCHEN EQUIPMENT SCHEDULE.MINIMUM | | | WASTE PIPEPIPE FROM SINKES IS 1 1/2. | | | DISHWASHER AND WATER HEATER NOT LISTED | | | | | | 4.NEED RISER DIAGRAMS FOR | | | 1.GREASY WASTE | | | 2.SANITARY WASTE | | | 3.WATER | | | 4.GAS | | | 5.CONDENSAT | | | 5.FLOOR SINKS MUST BE USED IN PLACE OF | | | FLOOR DRAINS FOR INDIRECT WASTE. | | | | | | 6.TRAP PRIMERS ARE REQUIRED FOR FLOOR | | | DRAINS IN PUBLIC REST ROOMS 409.4.1. | | | | | | 7.HOT WATER MUST BE TEMPERED TO 110F | | | FOR HAND SINKS AND BATHROOM LAVATORIES | | | | | | 8.SHOW MAKE-UP AIR AND EXHAUST FOR GAS | | | WATER HEATER. | | | | | | 9.SUBMIT GREASE TRAP DRAWINGS TO BE | | | APPROVED BY RODNEY COMPO. CITY ORDIN- | | | ANCE, GREASY WASTE #2938-96. | | | | | | 10.CONDENSATE FROM AIR HANDLERS AND | | | COOLERS ARE NOT PERMITED TO DUMP | | | INTO CITY SEWER SYSTEM. |
|
|