Plan Review Details - Permit 00110257
Plan Review Stops For Permit 00110257
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2000-12-08 Cont ID  
Sent By drunnels Date 2000-12-08 Time 15:10 Rev Time 1.00
Received By drunnels Date 2000-12-08 Time 15:10 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2000-11-27 Cont ID  
Sent By drunnels Date 2000-11-27 Time 09:25 Rev Time 1.00
Received By drunnels Date 2000-11-27 Time 09:25 Sent To  
Notes
2001-01-08 00:00:001]SUBMIT FIRE SPRINKLER PLANS AND PERMIT
 APPLICATION.
 2]SUBMIT LETTER FROM SPECIAL INSPECTOR
 3]SUBMIT PRODUCT APPROVALS FOR IMPACT
 RESISTANT GLAZING FOR STOREFRONT
 WINDOWS AND DOORS. METRO DADE COUNTY
 OR SBCCI.
 4] NOTE: WRAP DESK SHALL COMPLY TO
 SECTION 7.2 OF THE ACCESSIBILITY CODE
 FOR BUILDING CONSTRUCTION 1997EDITION

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-03-26 Cont ID  
Sent By dpalmer Date 2001-03-26 Time 16:28 Rev Time 0.00
Received By dpalmer Date 2001-03-26 Time 16:28 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2000-11-21 Cont ID  
Sent By dpalmer Date 2000-11-21 Time 17:42 Rev Time 0.00
Received By dpalmer Date 2000-11-21 Time 17:42 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2000-11-07 Cont ID  
Sent By mcarsill Date 2000-11-07 Time 13:38 Rev Time 0.00
Received By mcarsill Date 2000-11-07 Time 13:38 Sent To  
Notes
2001-01-08 00:00:001) PROVIDE FIRE ALARM SYSTEM SHOP
 DRAWINGS FOR FIRE ALARM EQUIPMENT SHOWN
 ON DRAWINGS. CUT SHEETS AND WIRING
 DIAGRAM ARE REQUIRED.
 2) A FIRE SPRINKLER HEAD IS REQUIRED FOR
 OUTSIDE SOFFIT.
 APPROVED PROVISO:
  
 PLANS REVIEWED BY CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-03-07 Cont ID  
Sent By pkrauss Date 2001-03-07 Time 13:27 Rev Time 0.30
Received By pkrauss Date 2001-03-07 Time 13:27 Sent To  
Notes
2001-03-07 00:00:00CHANGE R/A GRILLE FROM 30" X 8" TO
 10" X 20" AS PER ENGINEER OF RECORD.
  
 APPROVED.PHK

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-11-30 Cont ID  
Sent By ndenmark Date 2000-11-30 Time 11:25 Rev Time 0.25
Received By ndenmark Date 2000-11-30 Time 11:25 Sent To  
Notes
2001-01-08 00:00:00PROVISO :
 LOCATE AHU WITH RESPECT TO BUILDING
 CONSTRUCTION TO ALLOW SERVICE AND
 REMOVAL OF EQUIPMENT AND COMPONENTS

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-11-20 Cont ID  
Sent By jleech Date 2000-11-20 Time 09:36 Rev Time 0.33
Received By jleech Date 2000-11-20 Time 09:36 Sent To  
Notes
2001-01-08 00:00:00PROVISO;
 1.INSTALL CUP DISPENSER NEXT TO DRINKING
 FOUNTAIN FOR PEOPLE WHO CANNOT BEND OR
 STUP.
 2.HANDICAP DRESSING ROOM SHALL MEET
 FACBC SEC. 4.35.4 BENCH MUST BE FIXED
 TO WALL.