Plan Review Details - Permit 00110256
| Plan Review Stops For Permit 00110256 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2000-12-08 |
|
|
Cont ID |
|
| Sent By |
drunnels |
Date |
2000-12-08 |
Time |
08:37 |
Rev Time |
1.00 |
| Received By |
drunnels |
Date |
2000-12-08 |
Time |
08:37 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2000-11-20 |
|
|
Cont ID |
|
| Sent By |
drunnels |
Date |
2000-11-20 |
Time |
12:34 |
Rev Time |
2.00 |
| Received By |
drunnels |
Date |
2000-11-20 |
Time |
12:34 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1]SUBMIT PRODUCT APPROVALS FOR INPACT | | | RESISTANT GLAZING FOR STOREFRONT AND | | | DOORS. METRO DADE COUNTY OR SBCCI | | | 2] SUBMIT FIRE SPRINKLER PLANS AND | | | APPLICATION FOR PERMIT. | | | 3]SUBMIT LETTER FROM SPECIAL INSPECTOR. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2000-12-11 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-12-11 |
Time |
18:20 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-12-11 |
Time |
18:20 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2000-11-21 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-11-21 |
Time |
18:58 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-11-21 |
Time |
18:55 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ***************** UNSAT **************** | | | | | | 1)NOTE: PLEASE SEE E-1. TRACK LIGHTING | | | SHOWN BUT NOT SHOWN ON LOAD CALCULATIONS | | | PER 220-12B | | | | | | 2)NOTE: PLEASE CLARIFY LOADS SHOWN FOR | | | TRACK LIGHTING, ARE THESE LOADS INCLUDED | | | IN LIGHTING CIRCUITS SHOWN ON TOP OF | | | LIGHTING PLAN??? | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 659-8096 EXT 8372 | | | | | | | | | ALSO A FIXTURE SCHEDULE IS NEEDED. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2000-11-07 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-11-07 |
Time |
13:21 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2000-11-07 |
Time |
13:17 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1) MORE ILLUMINATED EXIT SIGNS ARE | | | NEEDED AT THE REAR OF THE STORE TO | | | DIRECT PERSONS TO EXIT LOCATED IN | | | STOCKROOM. | | | 2) EXITING PERMITTED THROUGH STOCKROOM | | | IF THE FOLLOWING CONDITIONS EXIST: | | | AN AISLE OF AT 44 INCHES IS PROVIDED | | | AND MAINTAINED, DOOR LEADING FROM | | | DISPLAY AND STOCKROOM CANNOT BE SUBJECT | | | TO LOCKING, AND NO MORE THAN 50 PERCENT | | | OF EXIT ACCESS CAN BE PROVIDED THROUGH | | | STOCKROOM. | | | 3) PROVIDE SEPARATE PLAN AND PERMIT FOR | | | FIRE ALARM EQUIPMENT SHOWN ON PLANS. | | | APPROVED PROVISO: | | | | | | PLANS REVIEWED BY CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2000-11-30 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-11-30 |
Time |
11:14 |
Rev Time |
0.25 |
| Received By |
ndenmark |
Date |
2000-11-30 |
Time |
11:14 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2001-01-17 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2001-01-17 |
Time |
09:38 |
Rev Time |
0.33 |
| Received By |
jleech |
Date |
2001-01-17 |
Time |
09:38 |
Sent To |
|
|
| Notes |
| 2001-01-17 00:00:00 | AS-BUILDS |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2000-11-20 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2000-11-20 |
Time |
11:09 |
Rev Time |
0.50 |
| Received By |
jleech |
Date |
2000-11-20 |
Time |
11:09 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PROVISO; | | | 1.INSTALL CUP DISPENSER NEXT TO DRINKING | | | FOUNTAIN FOR PEOPLE WHO CANNOT BEND | | | OR STUP. | | | 2.HANDICAP DRESSING ROOM SHALL MEET | | | FACBC SEC. 4.35.4 REQUIREMENTS. | | | 3.NEW PLUMBING RISER REQUIRED SHOWING | | | FLOOR DRAINS UP STREAM OF TOILETS. | | | PLANS REVIEWED BY JOHN LEECH | | | 659-8096 EXT.8377 |
|
|
|