Plan Review Details - Permit 00110256
Plan Review Stops For Permit 00110256
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2000-12-08 Cont ID  
Sent By drunnels Date 2000-12-08 Time 08:37 Rev Time 1.00
Received By drunnels Date 2000-12-08 Time 08:37 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2000-11-20 Cont ID  
Sent By drunnels Date 2000-11-20 Time 12:34 Rev Time 2.00
Received By drunnels Date 2000-11-20 Time 12:34 Sent To  
Notes
2001-01-08 00:00:001]SUBMIT PRODUCT APPROVALS FOR INPACT
 RESISTANT GLAZING FOR STOREFRONT AND
 DOORS. METRO DADE COUNTY OR SBCCI
 2] SUBMIT FIRE SPRINKLER PLANS AND
 APPLICATION FOR PERMIT.
 3]SUBMIT LETTER FROM SPECIAL INSPECTOR.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-12-11 Cont ID  
Sent By dpalmer Date 2000-12-11 Time 18:20 Rev Time 0.00
Received By dpalmer Date 2000-12-11 Time 18:20 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-11-21 Cont ID  
Sent By dpalmer Date 2000-11-21 Time 18:58 Rev Time 0.00
Received By dpalmer Date 2000-11-21 Time 18:55 Sent To  
Notes
2001-01-08 00:00:00***************** UNSAT ****************
  
 1)NOTE: PLEASE SEE E-1. TRACK LIGHTING
 SHOWN BUT NOT SHOWN ON LOAD CALCULATIONS
 PER 220-12B
  
 2)NOTE: PLEASE CLARIFY LOADS SHOWN FOR
 TRACK LIGHTING, ARE THESE LOADS INCLUDED
 IN LIGHTING CIRCUITS SHOWN ON TOP OF
 LIGHTING PLAN???
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 659-8096 EXT 8372
  
  
 ALSO A FIXTURE SCHEDULE IS NEEDED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2000-11-07 Cont ID  
Sent By mcarsill Date 2000-11-07 Time 13:21 Rev Time 0.00
Received By mcarsill Date 2000-11-07 Time 13:17 Sent To  
Notes
2001-01-08 00:00:001) MORE ILLUMINATED EXIT SIGNS ARE
 NEEDED AT THE REAR OF THE STORE TO
 DIRECT PERSONS TO EXIT LOCATED IN
 STOCKROOM.
 2) EXITING PERMITTED THROUGH STOCKROOM
 IF THE FOLLOWING CONDITIONS EXIST:
 AN AISLE OF AT 44 INCHES IS PROVIDED
 AND MAINTAINED, DOOR LEADING FROM
 DISPLAY AND STOCKROOM CANNOT BE SUBJECT
 TO LOCKING, AND NO MORE THAN 50 PERCENT
 OF EXIT ACCESS CAN BE PROVIDED THROUGH
 STOCKROOM.
 3) PROVIDE SEPARATE PLAN AND PERMIT FOR
 FIRE ALARM EQUIPMENT SHOWN ON PLANS.
 APPROVED PROVISO:
  
 PLANS REVIEWED BY CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-11-30 Cont ID  
Sent By ndenmark Date 2000-11-30 Time 11:14 Rev Time 0.25
Received By ndenmark Date 2000-11-30 Time 11:14 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-01-17 Cont ID  
Sent By jleech Date 2001-01-17 Time 09:38 Rev Time 0.33
Received By jleech Date 2001-01-17 Time 09:38 Sent To  
Notes
2001-01-17 00:00:00AS-BUILDS

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-11-20 Cont ID  
Sent By jleech Date 2000-11-20 Time 11:09 Rev Time 0.50
Received By jleech Date 2000-11-20 Time 11:09 Sent To  
Notes
2001-01-08 00:00:00PROVISO;
 1.INSTALL CUP DISPENSER NEXT TO DRINKING
 FOUNTAIN FOR PEOPLE WHO CANNOT BEND
 OR STUP.
 2.HANDICAP DRESSING ROOM SHALL MEET
 FACBC SEC. 4.35.4 REQUIREMENTS.
 3.NEW PLUMBING RISER REQUIRED SHOWING
 FLOOR DRAINS UP STREAM OF TOILETS.
 PLANS REVIEWED BY JOHN LEECH
 659-8096 EXT.8377