| Notes |
| 2001-01-08 00:00:00 | 1) BOLLARDS ARE REQUIRED TO PROTECT TANK | | | FROM MECHANICAL DAMAGE. | | | 2) STORAGE TANK TO BE LABELED IN | | | ACCORDANCE WITH NFPA 704. ALSO NO | | | SMOKING LABELS AND PRODUCT NAME TO BE | | | PLACED ON TANK. | | | 3) PLEASE PROVIDE CUT SHEETS ON STORAGE | | | TANK. | | | 4) VENT PIPE TO BE AT LEAST 1 1/4 AND | | | AT LEAST 12 FEET FROM THE GROUND. | | | 5) TANK AND ASSOCIATED PIPING TO COMPLY | | | WITH CITY CODE REQUIREMENTS. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|