Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2000-11-27 Cont ID  
Sent By mcarsill Date 2000-11-27 Time 14:18 Rev Time 0.00
Received By mcarsill Date 2000-11-27 Time 14:18 Sent To  
Notes
2001-01-08 00:00:001) BOLLARDS ARE REQUIRED TO PROTECT TANK
 FROM MECHANICAL DAMAGE.
 2) STORAGE TANK TO BE LABELED IN
 ACCORDANCE WITH NFPA 704. ALSO NO
 SMOKING LABELS AND PRODUCT NAME TO BE
 PLACED ON TANK.
 3) PLEASE PROVIDE CUT SHEETS ON STORAGE
 TANK.
 4) VENT PIPE TO BE AT LEAST 1 1/4 AND
 AT LEAST 12 FEET FROM THE GROUND.
 5) TANK AND ASSOCIATED PIPING TO COMPLY
 WITH CITY CODE REQUIREMENTS.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-12-04 Cont ID  
Sent By ndenmark Date 2000-12-04 Time 14:48 Rev Time 0.50
Received By ndenmark Date 2000-12-04 Time 14:47 Sent To  
Notes
***NONE***