Plan Review Details - Permit 00110185
| Plan Review Stops For Permit 00110185 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2001-01-05 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-01-05 |
Time |
09:58 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-01-05 |
Time |
09:57 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2000-11-20 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-11-20 |
Time |
20:39 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-11-20 |
Time |
20:39 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | **************** UNSAT **************** | | | | | | 1)NOTE: PLEASE NOTE THAT NOW THE PLANS | | | ARE SHOWING A METER/MAIN COMBO, BUT NOT | | | SHOWING AIC RATING FOR THIS. PLEASE | | | SUBMIT PER 110-9 AND 215-5. | | | | | | 2)NOTE: PLEASE SEE PLANS, THE MAIN IS | | | NOT SHOWN WITH METER. PLEASE DO SO. | | | | | | 3)NOTE: ALSO PLEASE VERIFY PANEL "A" | | | YOU SHOW ON RISER AS PANEL W/ MCB. | | | YOU HAVE MAIN ALREADY. PLEASE CHECK. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 659-8096 EXT 8372 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2000-11-16 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2000-11-16 |
Time |
19:09 |
Rev Time |
0.33 |
| Received By |
jleech |
Date |
2000-11-16 |
Time |
19:08 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2000-11-16 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2000-11-16 |
Time |
19:11 |
Rev Time |
0.33 |
| Received By |
jleech |
Date |
2000-11-16 |
Time |
19:11 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
3 |
Status |
F |
Date |
2001-03-12 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2001-03-12 |
Time |
19:03 |
Rev Time |
0.25 |
| Received By |
jgomez |
Date |
2001-03-12 |
Time |
19:03 |
Sent To |
|
|
| Notes |
| 2001-03-12 00:00:00 | TRUSS DRAWINGS CHECKLIST: | | | | | | 1-ENGINEER TO PROVIDE SIGNED, SEALED AND | | | DATED GENERAL TRUSS DRAWINGS AS | | | REQUIRED BY CHAPTER 471 OF FLORIDA | | | STATUTES. | | | | | | 2-UPDATE ALL GENERAL TRUSS DRAWINGS AS | | | REQUIRED.ALSO, THERE ARE MANY | | | DIFFERENT DESIGN WIND LOADS. SEE | | | HIGHLIGHTED TRUSS DRAWINGS. | | | | | | | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ AT 659-8096 EXT. 8232. |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
2 |
Status |
P |
Date |
2001-01-08 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2001-01-08 |
Time |
10:17 |
Rev Time |
1.00 |
| Received By |
jgomez |
Date |
2001-01-08 |
Time |
10:17 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2000-12-08 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2000-12-08 |
Time |
13:31 |
Rev Time |
2.00 |
| Received By |
jgomez |
Date |
2000-12-08 |
Time |
13:31 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | CHECKLIST: | | | 1-PAY IMPACT FEES TO PALM BEACH COUNTY. | | | 2-RESUBMIT ENERGY ENERGY CALCULATIONS | | | WITH ORIGINAL SIGNATURES AND DATES BY | | | THE PERSON WHO PREPARED IT AND BY THE | | | OWNER/AGENT. SECTION 103.0 OF FLORIDA | | | ENERGY EFFICIENCY CODE FOR BUILDING | | | CONSTRUCTION. 1997 EDITION. | | | 3-OWES $774.92 FOR RADON FEES, WESTERN | | | EXPANSION AND WETLANDS FEES. | | | SEE RECEIPT ATTACHED. | | | 4-DENIED BY ELECTRICAL PLAN REVIEWER. | | | SEE COMMENTS. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2000-11-06 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2000-11-06 |
Time |
11:13 |
Rev Time |
0.25 |
| Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
|