Plan Review Details - Permit 00110185
Plan Review Stops For Permit 00110185
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-01-05 Cont ID  
Sent By dpalmer Date 2001-01-05 Time 09:58 Rev Time 0.00
Received By dpalmer Date 2001-01-05 Time 09:57 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-11-20 Cont ID  
Sent By dpalmer Date 2000-11-20 Time 20:39 Rev Time 0.00
Received By dpalmer Date 2000-11-20 Time 20:39 Sent To  
Notes
2001-01-08 00:00:00**************** UNSAT ****************
  
 1)NOTE: PLEASE NOTE THAT NOW THE PLANS
 ARE SHOWING A METER/MAIN COMBO, BUT NOT
 SHOWING AIC RATING FOR THIS. PLEASE
 SUBMIT PER 110-9 AND 215-5.
  
 2)NOTE: PLEASE SEE PLANS, THE MAIN IS
 NOT SHOWN WITH METER. PLEASE DO SO.
  
 3)NOTE: ALSO PLEASE VERIFY PANEL "A"
 YOU SHOW ON RISER AS PANEL W/ MCB.
 YOU HAVE MAIN ALREADY. PLEASE CHECK.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-11-16 Cont ID  
Sent By jleech Date 2000-11-16 Time 19:09 Rev Time 0.33
Received By jleech Date 2000-11-16 Time 19:08 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-11-16 Cont ID  
Sent By jleech Date 2000-11-16 Time 19:11 Rev Time 0.33
Received By jleech Date 2000-11-16 Time 19:11 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status F Date 2001-03-12 Cont ID  
Sent By jgomez Date 2001-03-12 Time 19:03 Rev Time 0.25
Received By jgomez Date 2001-03-12 Time 19:03 Sent To  
Notes
2001-03-12 00:00:00TRUSS DRAWINGS CHECKLIST:
  
 1-ENGINEER TO PROVIDE SIGNED, SEALED AND
 DATED GENERAL TRUSS DRAWINGS AS
 REQUIRED BY CHAPTER 471 OF FLORIDA
 STATUTES.
  
 2-UPDATE ALL GENERAL TRUSS DRAWINGS AS
 REQUIRED.ALSO, THERE ARE MANY
 DIFFERENT DESIGN WIND LOADS. SEE
 HIGHLIGHTED TRUSS DRAWINGS.
  
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 659-8096 EXT. 8232.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2001-01-08 Cont ID  
Sent By jgomez Date 2001-01-08 Time 10:17 Rev Time 1.00
Received By jgomez Date 2001-01-08 Time 10:17 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2000-12-08 Cont ID  
Sent By jgomez Date 2000-12-08 Time 13:31 Rev Time 2.00
Received By jgomez Date 2000-12-08 Time 13:31 Sent To  
Notes
2001-01-08 00:00:00CHECKLIST:
 1-PAY IMPACT FEES TO PALM BEACH COUNTY.
 2-RESUBMIT ENERGY ENERGY CALCULATIONS
 WITH ORIGINAL SIGNATURES AND DATES BY
 THE PERSON WHO PREPARED IT AND BY THE
 OWNER/AGENT. SECTION 103.0 OF FLORIDA
 ENERGY EFFICIENCY CODE FOR BUILDING
 CONSTRUCTION. 1997 EDITION.
 3-OWES $774.92 FOR RADON FEES, WESTERN
 EXPANSION AND WETLANDS FEES.
 SEE RECEIPT ATTACHED.
 4-DENIED BY ELECTRICAL PLAN REVIEWER.
 SEE COMMENTS.

Review Stop Z ZONING
Rev No 1 Status P Date 2000-11-06 Cont ID  
Sent By sgraham Date 2000-11-06 Time 11:13 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***