Plan Review Details - Permit 00110159
Plan Review Stops For Permit 00110159
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2001-02-08 Cont ID  
Sent By jwitmer Date 2001-02-08 Time 14:06 Rev Time 0.50
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2001-01-10 Cont ID  
Sent By hpiskura Date 2001-01-10 Time 11:25 Rev Time 0.00
Received By hpiskura Date 2001-01-10 Time 10:15 Sent To  
Notes
2001-01-10 00:00:00REVISE SHEET A1 DATED 12/1/00 DECLARES A
 GROUP B OCCUPANCY.THE ADJACENT
 TENANTS ARE GROUP F AND S.A TWO HOUR
 FIRE RATED SEPARATION IS REQUIRED BY
 SBC 704.1.1.PLEASE REVISE AS
 NECESSARY, INCLUDING OPENING
 PROTECTIVES.
  
 HAROLD PISKURA

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2000-11-28 Cont ID  
Sent By hpiskura Date 2000-11-28 Time 08:01 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2001-01-08 00:00:00LETTER ATTACHED TO APPLICATION

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2001-02-15 Cont ID  
Sent By dpalmer Date 2001-02-15 Time 16:13 Rev Time 0.00
Received By dpalmer Date 2001-02-15 Time 16:13 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2001-02-07 Cont ID  
Sent By dpalmer Date 2001-02-07 Time 22:11 Rev Time 0.00
Received By jwitmer Date 2001-02-08 Time 14:10 Sent To  
Notes
2001-02-07 00:00:00**************** UNSAT ****************
  
 1)NOTE:PLEASE NOTE THAT PLANS ARE NOW
 SIGNED AND SEALED BY AN ENGINEER, BUT
 PLANS MUST CONTAIN THE TITLE BLOCK WITH
 ALL THE INFORMATION REQUESTED UNDER
 F.A.C SECTION 61G15-23.002.
 PLEASE CORRECT.
  
 2)NOTE: PLEASE CLARIFY THE CONDUCTORS
 AND CONDUIT/RACEWAY BETWEEN METER AND
 FIRST DISCONNECT. SHOWS 6"X10"
 RACEWAY???
  
 3)NOTE:PLEASE NOTE THAT OLD PLANS
 INDICATED AIC RATING FOR NEW PANELS AND
 NEW PLANS DO NOT.
 PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRNET PER 110-9.
 PLEASE NOTE THAT THE NEW MAIN
 DISCONNECTON THE LOAD TRANSFORMER
 CONTAINS NO AIC RATING?
  
 4)NOTE: PLEASE CLARIFY HOW FIRST SET OF
 PLANS INDICATEPANEL "HV" BEING 460`
 FROM METER AND NEW PLANS DO NOT MENTION
 THIS? PLEASE CLARIFY. MAINS MUST BE
 GROUPED PER 230-72
  
 5)NOTE: PLEASE SUBMIT PLANS SHOWING
 BRANCH CIRCUITS #`S THAT CORRELATE WITH
 PANEL SCHEDULES SUBMITTED. PLEASE NOTE T
 HAT THERE ARE LIGHTING CIRCUITS SHOWN AS
 TRANSFORMER FEEDS.
 PLEASE PROVIDE CLARIFICATION.
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW AND CLARIFICATION. IF THERE
 ARE ANY QUESTIONS OR IF YOU WOULD LIKE T
 O REQUEST A MEETING TO GO OVER PLANS.
 PLEASE CALL.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2001-01-17 Cont ID  
Sent By dpalmer Date 2001-01-17 Time 22:33 Rev Time 0.00
Received By dpalmer Date 2001-01-17 Time 22:33 Sent To  
Notes
2001-01-17 00:00:00*************** UNSAT ******************
  
 1)NOTE: PLEASE NOTE THAT PER SECTION
 553.79 6 A OF THE F.A.C. PLANS FOR
 277/480 ARE TO BE SIGNED AND SEALED BY
 AN ENGINEER.
  
  
 2)NOTE: PLEASE NOTE THAT A MCB/OR MAIN
 IS REQ`D ON THE LOAD SIDE OF
 TRANSFORMER FOR A SEPARATELY DERIVED
 SYSTEM.
  
 3)NOTE: PLEASE PROVIDE CLARIFICATION ON
 TRANSFORMER. RISER SHOWS NEW? PLANS FOR
 ELECTRICAL ROOM NOTE SHOWS EXISTING
 ELECTRICAL TRANSFORMERS? PLEASE CLARIFY.
  
 4)NOTE: PLEASE PROVIDE CONDUCTOR SIZES
 FROM METER TO MAIN.??
  
 5)NOTE: PLEASE CLARIFY THE ELEC SREVICE.
 RISER SHOWS NEW DROP? A SECOND DROP AND
 MEANS OF SERVICE IS ONLY PERMITTED FOR
 SEPARATE VOLTGES NEEDED. PLEASE SHOW
 EXISTING VOLTAGES.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. PLEASE HAVE SIGNED AND SEALED
 BYENGINEER. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-11-21 Cont ID  
Sent By dpalmer Date 2000-11-21 Time 20:04 Rev Time 0.00
Received By dpalmer Date 2000-11-21 Time 20:04 Sent To  
Notes
2001-01-08 00:00:00***************** UNSAT ****************
  
 1)NOTE: PLEASE PROVIDE MORE DETAIL OF
 ELECTRICAL WORK BEING DONE. PLEASE SEE
 THE FOLLOWING NOTES. PLEASE SHOW ALL
 BRANCH CIRCUIT 3`S ON PLANS INCLUDING
 LIGHTING. PLEASE CORRELATE WITH AND
 SUBMIT A PANEL SCHEDULE.
  
 2)NOTE: PLEASE SUBMIT LOAD CALCULATIONS
 SHOWING EXISTING SERVICE SIZE AND
 ALL CONTINUOUS LOADS AT 125%.
 PANEL SCHEDULE IS PROVIDE MORE DETAIL OF
 EQUIPMENT.
  
 3)NOTE:PLEASE SHOW LOCATION OF ELECTRIC-
 -AL PANEL(S) AND WHERE FEEDS ARE COMING
 FROM.PLEASE GIVE CLARIFICATION ON
 EXISTING? OR NEW??
  
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2001-02-06 Cont ID  
Sent By mcarsill Date 2001-02-06 Time 08:48 Rev Time 0.00
Received By mcarsill Date 2001-02-06 Time 08:48 Sent To  
Notes
2001-02-06 00:00:001) ALL EXIT DOORS ARE TO SWING IN THE
 DIRECTION OF EXIT TRAVEL.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By mcarsill Date 2001-01-08 Time 13:03 Sent To  
Notes
2001-01-08 00:00:001) PLEASE VERIFY THAT DOOR SWINGS ARE
 PROPER. ACCORDING TO THE PLANS, THE
 OCCUPANT LOAD FOR THE SPACE IS LISTED
 TO BE AT LEAST 100 PERSONS. DOORS USED
 FOR EXITING MUST SWING IN THE DIRECTION
 OF EXIT TRAVEL. PLEASE CORRECT THE
 DRAWINGS.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2000-11-08 Cont ID  
Sent By mcarsill Date 2000-11-08 Time 15:25 Rev Time 0.00
Received By mcarsill Date 2000-11-08 Time 15:25 Sent To  
Notes
2001-01-08 00:00:001) EXITING DOES NOT APPEAR VERY CLEAR.
 A MINIMUM NUMBER OF EXITS IS REQUIRED
 2) NO INTERIOR FINISH INFORMATION
 PROVIDED.
 3) NO FIRE ALARM EQUIPMENT SHOWN IN
 NEW SPACE.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2001-02-06 Cont ID  
Sent By ndenmark Date 2001-02-06 Time 11:20 Rev Time 0.33
Received By ndenmark Date 2001-02-06 Time 11:20 Sent To  
Notes
2001-02-06 00:00:00PRIOR COMMENTS CORRECTED BY REVISION

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2001-01-19 Cont ID  
Sent By ndenmark Date 2001-01-19 Time 11:11 Rev Time 0.33
Received By ndenmark Date 2001-01-19 Time 11:11 Sent To  
Notes
2001-01-19 00:00:00**************DENIED********************
 1. SHEET A-1 SHOWS OCCUPANT LOAD OVER
 100 PEOPLE. THIS NEEDS TO BE A SIGNED
 AND SEALED PLAN BY A STATE OF FLORIDA
 ENGINEER.
 2.EXISTING DUCT TO BE REUSED TO BE
 INSPECTED FOR CLEANLINESS AND CLEANED
 AND SANITIZED IN DEEMED NEED BY THE
 MECHANICAL INSPECTOR.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2000-11-30 Cont ID  
Sent By ndenmark Date 2000-11-30 Time 14:26 Rev Time 0.25
Received By ndenmark Date 2000-11-30 Time 14:25 Sent To  
Notes
2001-01-08 00:00:00**************DENIED********************
 1.DUCTS PENETRATING RATED WALLS ARE TO
 PROTECTED PER 1997 SMC 610.1.2 AND FIRE
 DAMPERS LOCATION AND INSTALLATION DETAIL
 IS TO BE SHOWN ON THE PLAN BY THE DESIGN
 PROFESSIONAL.
 2. PROVIDE INFORMATION ON EXISTING
 EQUIPMENT SHOWING CAPACITY TO COVER NEW
 DISTRIBUTION.
 3. EXISTING DUCTWORK TO INSPECTED FOR
 CLEANLINESS AND CLEANED AND SANITIZED IF
 DEEMED NEEDED BY THE MECHANICAL INSPECTO

Review Stop P PLUMBING
Rev No 3 Status P Date 2001-02-06 Cont ID  
Sent By jleech Date 2001-02-06 Time 14:37 Rev Time 1.00
Received By jleech Date 2001-02-06 Time 14:36 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2001-01-16 Cont ID  
Sent By jleech Date 2001-01-16 Time 07:15 Rev Time 0.75
Received By jleech Date 2001-01-16 Time 07:14 Sent To  
Notes
2001-01-16 00:00:00DENIED;
  
 1.OCCUPANT LOAD OVER 101 PEOPLE IN 94
 SPC REQUIRES 4 W/C'S AND 3 LAVATORIES,
 IN WOMANS ROOM AND 2 DRINKING
 FOUNTAINS.
  
 JOHN LEECH
 659-8096 EXT. 8377

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-11-30 Cont ID  
Sent By jleech Date 2000-11-30 Time 15:58 Rev Time 1.00
Received By jleech Date 2000-11-30 Time 15:58 Sent To  
Notes
2001-01-08 00:00:00DENIED;
 1.PLUMBING RIZER NOT TO CODE;
 A.NO HORIZONTAL DRY VENTS.
 B.NO MORE THAN TWO TOILETS ON 3"
 HORIZONTAL PIPING.
 C.MINIMUM PIPE SIZE UNDER SLAB IS 2".
  
 2.DRINKING FOUNTAIN TO BE HIGH-LOW
 HANDICAP APPROVED DRINKING FOUNTAIN
 PER 97 FACBC.
  
 3.NEED OCCUPANT CONTENT TO FIGURE OUT
 MINIMUM PLUMBING FIXTURES.
  
 4.NEED H2O RISER DIAGRAM SIZE PIPE AND
 SHOW ALL SHUT OFF VALVES.
  
 5.HANDICAP TOILET STALLS DO NOT COMPLY
 WITH 97 FACBC CLEAR FLOOR SPACE FOR
 TOILET AND LAVITORY.
  
 6.URINAL TO BE HANDICAP ALSO PER 4.18.3.
 ELONGATED RIM AND MAX 17" OFF FLOOR
 TO RIM.
  
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT.8377


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved