Plan Review Details - Permit 00110155
| Plan Review Stops For Permit 00110155 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2000-11-28 |
|
|
Cont ID |
|
| Sent By |
lsmith |
Date |
2000-11-28 |
Time |
14:02 |
Rev Time |
0.50 |
| Received By |
lsmith |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2000-11-29 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-11-29 |
Time |
15:14 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-11-29 |
Time |
15:13 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2000-11-22 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-11-22 |
Time |
08:38 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-11-22 |
Time |
08:38 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | SAME NOTES |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2000-11-20 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-11-20 |
Time |
15:23 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-11-20 |
Time |
15:23 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ************** UNSAT ******************* | | | | | | 1)NOTE: PLEASE SEE NOTES FROM FIRST RE- | | | -VIEW. NOTES WERE STILL NOT ADDRESSED. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW, | | | 659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2000-11-09 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-11-09 |
Time |
10:41 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-11-09 |
Time |
10:41 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ******************** UNSAT ************* | | | | | | 1)NOTE: PLEASE SEE PLANS,,, BOTH GAS AND | | | ELEC HEAT PUMP IS NOT SHOWN ON WIRING | | | DIAGRAM?? PLEASE DO SO. | | | | | | 2)NOTE: PLEASE SUBMIT LOAD CALCUALTION | | | FOR ALL NEW LOADS BEING INTRODUCED ON | | | EXISTING ELECTRICAL SERVICE.PLEASE SHOW | | | EXISTING SERVICE SIZE. | | | | | | PLEASE SUBMIR THE ABOVE INFORMATON FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 659-8096 EXT 8372 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2000-11-18 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2000-11-18 |
Time |
11:14 |
Rev Time |
0.33 |
| Received By |
jleech |
Date |
2000-11-18 |
Time |
11:14 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2000-11-12 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2000-11-12 |
Time |
09:27 |
Rev Time |
1.00 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | POOL & SPA PLAN REVIEW DENIED | | | (1)PIPING DIAGRAM WITH LOCATION OF | | | EQUIPMENT & PIPE SIZES. | | | (2) SHOW MINIMUM OF 3 RETURNS, LOCATION. | | | (3)ALL SUCTION LINES TO BE VALVED. | | | (4)BACK FLOW PREVENTER REQ, ON WATER | | | SERVICE, LOCAL ORDINANCE 2853-95 | | | (5) FL ENERGY CODE 612.1 ABC 2,3,2 | | | HEATED POOLS, POOL COVER REQUIRED. | | | END OF COMMENTS PAUL SCHMITZ | | | 561-659-8096 X 8233 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2000-11-06 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2000-11-06 |
Time |
12:18 |
Rev Time |
0.25 |
| Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
|