Plan Review Details - Permit 00110151
Plan Review Stops For Permit 00110151
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-12-13 Cont ID  
Sent By dpalmer Date 2000-12-13 Time 21:41 Rev Time 0.00
Received By dpalmer Date 2000-12-13 Time 21:41 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-11-14 Cont ID  
Sent By dpalmer Date 2000-11-14 Time 18:43 Rev Time 0.00
Received By dpalmer Date 2000-11-14 Time 18:43 Sent To  
Notes
2001-01-08 00:00:00***************** UNSAT ****************
  
 1)NOTE: PLEASE SEE GARAGE PLAN, THERE IS
 A PANEL"A-1" SHOWN??? THIS IS NOT ON
 RISER OR MENTIONED IN NOTES?? PLEASE
 SUBMIT CLARIFICATION.215-5
 PANEL SCHEDULE FOR THIS PANEL ALSO.
  
 2)NOTE: PLEASE SEE RISER, GARAGE PANEL
 NOT SHOWN? WHERE IS THE NEW SERVICE
 GOING TO BE MOUNTED?
  
 3)NOTE: PLEASE NOTE PANEL A-1 WILL NEED
 MAIN AND SHOW GROUNDING PER NEC 250-50
  
 4)NOTE: WHERE IS PANEL "C" GOING??
  
 5)NOTE: PLEASE NOTE PER NEC 250 THE
 REQ`D COLD WATER BOND FOR GROUNDING
 ELECTRODE>
  
 6)NOTE: PLEASE NOTE THAT PANEL SCHEDULES
 ARE TO HAVE LISTINGS WITH WIRE SIZES,
 BREAKER SIZES TO CORRELATE.PLEASE SUBMIT
  
  
 PLEASE SUBMIT THE ABOVE INFOMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS OR
 CLARIFICATIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 659-8096 EXT 8372
  
  
  
  
 7)NOTE: PLEASE SUBMIT COMPLETE LOAD CAL-
 -CULAATION FOR SERVICE. PER 215

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2000-11-08 Cont ID  
Sent By jleech Date 2000-11-08 Time 18:21 Rev Time 0.26
Received By jleech Date 2000-11-08 Time 18:21 Sent To  
Notes
2001-01-08 00:00:00NO A/C SHOWN.

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-11-08 Cont ID  
Sent By jleech Date 2000-11-08 Time 18:22 Rev Time 0.25
Received By jleech Date 2000-11-08 Time 18:22 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2000-12-15 Cont ID  
Sent By rmcdouga Date 2000-12-15 Time 14:47 Rev Time 2.00
Received By rmcdouga Date   Time   Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2000-11-18 Cont ID  
Sent By rmcdouga Date 2000-11-18 Time 10:39 Rev Time 4.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-01-08 00:00:00DENIED
  
 1)PROVIDE 2 CURRENT COPIES OF METRO-DADE
 OR SBCCI PRODUCT APPROVALS FOR GARAGE
 DOOR, SINGLE HUNG WINDOWS,AND OUTSWING
 DOOR.
  
 2)PROVIDE PRODUCT APPROVALS,KEY PLAN AND
 INSTALLATION SCHEDULE FOR STORM PANELS.
 INDICATE SPECIFIC TYPE OF ANCHORS TO BE
 USED.
  
 3)PROVIDE PRODUCT APPROVALS FOR ROOF
 COVERING UNDER A SEPARATE PERMIT.
  
 4)SPECIFY MEAN ROOF HEIGHT AND BEAM
 ELEVATIONS ON PLANS.
  
 5)PROVIDE NEGATIVE AND POSITIVE PRESSURE
 FOR ALL EXTERIOR WINDOW AND DOOR OPEN-
 INGS.
  
 6)PLEASE CHECK SPACING OF VERTICLE
 REINFORCEMENT IN EXTERIOR WALLS AND
 PROVIDE VERTICLE REINFORCEMENT AT EACH
 SIDE OF EXTERIOR OPENINGS.
  
 7)PROVIDE DETAILS AND SAFE LOADS FOR
 PRECAST LINTELS AT ALL EXTERIOR OPENINGS
  
 8)PROVIDE DETAIL OF WINDOW AND DOOR BUCK
 CONNECTIONS FOR WINDLOAD RESISTANCE.
  
 9)PLEASE HAVE DESIGN PROFESSIONAL
 CALCULATE UPLIFTS FOR ROOF OF STRUCTURE
 AND SPECIFY SPECIFIC CONNECTORS TO BE
 USED TO ANCHOR EACH TRUSS AND GIRDER
 TO STRUCTURE. PROVIDE THIS INFORMATION
 ON PLANS SO THAT CORRECT CONNECTORS CAN
 BE INSTALLED WHEN BOND BEAM IS POURED.
 TRUSS PLANS AND DRAWINGS ARE TO BE
 REVIEWED AND APPROVED BY DESIGNER OF
 RECORD PRIOR TO INSTALLATION OF TRUSSES.

Review Stop Z ZONING
Rev No 1 Status P Date 2000-11-06 Cont ID  
Sent By sgraham Date 2000-11-06 Time 12:23 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***