Plan Review Details - Permit 00110106
Plan Review Stops For Permit 00110106
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-01-17 Cont ID  
Sent By dpalmer Date 2001-01-17 Time 18:53 Rev Time 0.00
Received By dpalmer Date 2001-01-17 Time 18:53 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-11-20 Cont ID  
Sent By dpalmer Date 2000-11-20 Time 18:28 Rev Time 0.00
Received By dpalmer Date 2000-11-20 Time 18:27 Sent To  
Notes
2001-01-08 00:00:00******************* UNSAT *************
  
 1)NOTE:PLEASE AIC RATINGS FOR ALL NEW
 EQUIPMENT BEING INSTALLED. ALL MUST BE
 RATED FOR THE AVAILABLE FAULT CURRENT
 PER 110-9..
  
 2)NOTE: PLEASE SEE RISER DIAGRAM. YOU
 SHOW 200A DISC TO 200A PANEL W/ #1 AWG??
 PLEASE SEE 310-15 AND 310-16.
  
 3)NOTE: PLEASE SEE PANEL SCHEDULES AND
 RISER DIAGRAMS. ONE SHOWS PANEL BEING
 MLO AND THE OTHER MCB?? PLEASE CORRELATE
 THE TWO.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-11-14 Cont ID  
Sent By jleech Date 2000-11-14 Time 19:05 Rev Time 0.33
Received By jleech Date 2000-11-14 Time 19:05 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-06-08 Cont ID  
Sent By kstevens Date 2002-06-08 Time 10:30 Rev Time 0.00
Received By kstevens Date 2002-06-08 Time 10:30 Sent To  
Notes
2002-06-08 00:00:00REVISION OK - SANITARY RISER DIAGRAM

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-11-14 Cont ID  
Sent By jleech Date 2000-11-14 Time 19:05 Rev Time 0.33
Received By jleech Date 2000-11-14 Time 19:05 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2001-01-23 Cont ID  
Sent By rmcdouga Date 2001-01-23 Time 10:44 Rev Time 4.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-01-23 00:00:00PROVISO
  
 1) PROVIDE 2 CURRENT COMPLETE COPIES OF
 SBCCI OR METRO DADE PRODUCT APPROVALS
 FOR:
 - OUTSWING RESIDENTIAL STEEL DOOR
  
 2) PROVIDE KEY PLAN AND INSTALLATION
 SCHEDULE FOR STORM PANELS.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2000-12-06 Cont ID  
Sent By rmcdouga Date 2000-12-06 Time 13:10 Rev Time 4.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-01-08 00:00:00DENIED
  
 1)RECORDED COPY OF NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE
 PERMIT CAN BE ISSUED.
  
 2)IMPACT FEES MUST BE PAID TO PALM BEACH
 COUNTY,PLANS STAMPED BY THEM AND RECEIPT
 SUBMITTED TO CITY BUILDING DEPT. BEFORE
 PERMIT CAN BE ISSUED.
  
 3)PROVIDE UL APPROVAL FOR BBQ.
  
 4)PROVIDE 2 COMPLETED COPIES OF DESIGN
 COMPLIANCE FORM SIGNED,SEALED AND DATED
 BY THE DESIGNER OF RECORD.
  
 5)PLEASE INDICATE MEAN ROOF HEIGHT ON
 PLANS.
  
 6)THE TRUSS ANCHOR SCHEDULE ON SHEET A7
 LISTS (A) FOR ALL ENTRIES. PLEASE REVIEW
 AND CORRECT.
  
 7)THE ANCHOR FOR THE GIRDER TRUSS AT THE
 RIGHT REAR OF THE LIVING ROOM IS INDICAT
 -ED AS 10/A8. PLEASE RECHECK AND CORRECT
  
 8)PLEASE SPECIFY TRUSS ANCHORS TO BE
 USED ON HIP TRUSSES.
  
 9)CASEMENT WINDOWS IN BEDROOM #3 MUST
 COMPLY WITH WITH EGRESS REQUIREMENTS.
 1997 SBC 1005.4
  
 10)PROVIDE 2 CURRENT COPIES OF SBCCI OR
 METRO-DADE PRODUCT APPROVALS,KEY PLAN
 AND INSTALLATION SCHEDULE,INDICATING
 SPECIFIC ANCHORS TO BE USED,FOR STORM
 PANELS.
  
 11)PROVIDE ENGINEERING FOR BUTT GLASS
 ASSEMBLIES.97 SBC 2406.2.
  
 12)PROVIDE 2 CURRENT COPIES OF SBCCI OR
 METRO-DADE PRODUCT APPROVALS FOR THE
 FOLLOWING ITEMS:
 -STRUCTURAL MULLIONS (SEE 8 ON A9)
 -STOREFRONT FIXED GLASS IN LIVING ROOM
 -METAL DOOR TO AHU #3
 -RECTANGULAR FIXED GLASS WINDOWS
 -FIXED GLASS W/ARCHED TOP ABOVE FRONT
 DOOR.
 -ROOF COVERING

Review Stop Z ZONING
Rev No 1 Status P Date 2000-11-07 Cont ID  
Sent By sgraham Date 2000-11-07 Time 16:25 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved