Plan Review Details - Permit 00110096
Plan Review Stops For Permit 00110096
Review Stop E ELECTRICAL
Rev No 3 Status F Date 2001-02-27 Cont ID  
Sent By dpalmer Date 2001-02-27 Time 19:51 Rev Time 0.00
Received By dpalmer Date 2001-02-27 Time 19:51 Sent To  
Notes
2001-02-27 00:00:00****************** UNSAT **************
  
 1)NOTE: PLEASE SUBMIT CLARIFICATION
 ON NOTE #1 OF FIRST REVIEWS. IS ALL
 ELECTRICAL EQUIPMENT RATED AT 22,000 AIC
 ? NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2)NOTE: PLEASE SEE NOTE#6 FROM FIRST
 REVIEWS, ONLT ONE DISCONNECT IS SHOWN.
  
 3)NOTE: PLEASE SHOW CLARIFICATION ON
 EQUIPMENT GROUNDING CONDUCTOR FROM MAIN
 TO PANELS. SIZE PER 250-122.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2001-01-17 Cont ID  
Sent By dpalmer Date 2001-01-17 Time 16:06 Rev Time 0.00
Received By dpalmer Date 2001-01-17 Time 16:06 Sent To  
Notes
2001-01-17 00:00:00***************** UNSAT ****************
  
 1)NOTE: PLEASE NOTE, UNDER F.A.C. ALL
 CHANGES ON PLANS ARE TO BE SIGNED AND
 DATED AT EACH CHANGE BY THE ARCH/ENG OF
 RECORD. 471.025/ 481.221 PLEASE EITHER
 REDO PLANS OR INITAL AND DATE EACH
 CHANGE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 659-8096 EXT 8372
  
  
 2)NOTE: ALSO PLEASE NOTE THAT THE RISER
 SHOWS 6-4/0`S. PLEASE SEE TABLE
 310-15-B-6.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-11-30 Cont ID  
Sent By dpalmer Date 2000-11-30 Time 18:47 Rev Time 0.00
Received By dpalmer Date 2000-11-30 Time 18:47 Sent To  
Notes
2001-01-08 00:00:00**************** UNSAT *****************
  
 1)NOTE: PLEASE SEE AIC RATING SHOWN NEXT
 TO MLO PANEL. IS THIS THE AIC RATING FOR
 THE MAIN DISC ALSO? ALSO PLEASE NOTE
 IF SO, THEN ALL BREAKERS IN THE 8-16
 PANEL ARE TO BE RATED FOR 22,00 ALSO
 OR SHOW SERIES RATING FOR THESE.
  
 2)NOTE: PLEASE SEE WIRE SIZE SHOWN FOR
 250A FEED FROM MAIN TO SUB-PANEL WITH
 1/0 AWG SHOWN. PLEASE CORRECT PER 310-16
  
 3)NOTE: PLEASE SHOW WP GFI OUTLET FOR\\
 A/C COND UNIT PER SEC 309.1 OF THE
 MECH CODE.
  
 4)NOTE: PLEASE SEE MISSING GFI OUTLET
 FOR CABANA BATH PER 210-52D AND 210-11-
 C-3. PLEASE SHOW.
  
 5)NOTE: PLEASE SEE GARAGE, AHU`S SHOWN
 IN ATTIC. PLEASE PROVIDE OUTLET PER
 210-63 OF THE NEC AND 309.1
  
 6)NOTE: PLEASE SHOW MAIN DISCONNECT ON
 PLAN NEXT TO METER AS SHOWN ON RISER
 DIAGRAM.
  
 7)NOTE: PLEASE NOTE THE MISSING SMOKE
 DETECTOR PER NFPA-72 2-2.1.1.1 IN BED-
 -ROOM #4.
  
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-11-30 Cont ID  
Sent By jleech Date 2000-11-30 Time 18:05 Rev Time 0.25
Received By jleech Date 2000-11-30 Time 18:05 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-11-30 Cont ID  
Sent By jleech Date 2000-11-30 Time 18:05 Rev Time 0.25
Received By jleech Date 2000-11-30 Time 18:05 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2001-02-20 Cont ID  
Sent By fknapp Date 2001-02-20 Time 14:49 Rev Time 2.00
Received By fknapp Date 2001-02-20 Time 14:49 Sent To  
Notes
2001-02-20 00:00:00 
  
 ***************TRUSSES UNSAT************
  
 SBC 104.2.2
  
 1) PROVIDE CONNECTORS THAT SUPPLY
 ADEQUATE UPLIFT FOR THE FOLLOWING
 TRUSSES:
 GT-1
 GT-3
 GT-5
 GT-6
  
 PLEASE REVIEW ALL CONNECTIONS FOR
 ADEQUATE UPLIFT.
  
 ANY QUESTIONS PLEASE CALL,
 FRANK KNAPP
 BUILDING PLAN REVIEW
 DEPARTMENT OF CONSTRUCTION SERVICES
 CITY OF WEST PALM BEACH
 (561) 659-8096 EXT. 8392

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2000-12-08 Cont ID  
Sent By fknapp Date 2000-12-08 Time 08:27 Rev Time 4.00
Received By fknapp Date   Time   Sent To  
Notes
2001-01-08 00:00:00 
  
 ***********BUILDING UNSAT***************
  
 SBC 104.2.2
  
 1)PROVIDE 2 CURRENT COMPLETE COPIES OF
 SBCCI OR METRO DADE PRODUCT APPROVALS
 FOR ALL EXTERIOR SWING DOORS TO BE USED
 WITH APPROVED DRAWINGS.
  
 2)PROVIDE SAFETY GLASS AS REQ PER 1997
 SBC 2405.2.1(3)
  
 3)PROVIDE ROOF FRAMING PLAN WITH UPLIFT
 CALCULATIONS WITH SPECIFIC CONNECTORS
 TO BE USED.
  
 4)PROVIDE TRUSS ENGINEERING SHEETS AND
 LAYOUT PLAN.
  
 5)PROVIDE ENGINEERING FOR ALL BUTT GLASS
 OPENINGS.

Review Stop Z ZONING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
2001-01-08 00:00:00MODEL ONLY