| Plan Review Stops For Permit 00101295 |
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2000-10-27 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-10-27 |
Time |
16:26 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2000-10-27 |
Time |
16:26 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1) FIRE ALARM CONTROL PANEL IN TAMAYO | | | IS TO BE CONNECTED TO C BASE BUILDING | | | FIRE ALARM SYSTEM. | | | 2) FIRE ALARM SYSTEM IS TO BE AUDIBLE | | | THROUGHOUT TENANT SPACE WHEN ACTIVATED. | | | 3) DUCT SMOKE DETECTORS WHEN ACTIVATED | | | ARE TO SHUT DOWN AIR HANDLING DEVICES | | | AND ACTIVATE FIRE ALARM SYSTEM. | | | 4) FIRE ALARM SYSTEM IS TO BE TESTED | | | AFTER INSTALLATION WITH FIRE RESCUE | | | PERSONNEL. |
|
|
|