Plan Review Details - Permit 00101258
Plan Review Stops For Permit 00101258
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2000-11-03 Cont ID  
Sent By drunnels Date 2000-11-03 Time 15:54 Rev Time 2.00
Received By drunnels Date 2000-11-03 Time 15:24 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2000-11-21 Cont ID  
Sent By dpalmer Date 2000-11-21 Time 15:55 Rev Time 0.00
Received By dpalmer Date 2000-11-21 Time 15:55 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2000-11-08 Cont ID  
Sent By mgonzale Date 2000-11-08 Time 11:13 Rev Time 0.50
Received By mgonzale Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2000-12-12 Cont ID  
Sent By mcarsill Date 2000-12-12 Time 09:26 Rev Time 0.00
Received By mcarsill Date 2000-12-12 Time 09:26 Sent To  
Notes
2001-01-08 00:00:00PLAN REVIEW COMMENTS SEEMED TO ADDRESS
 ISSUES BY THE FIRE RESCUE DEPARTMENT.
 ON DECEMBER 12, 2000, WRITER CONTACTED
 LEWIS AND ASSOCIATES AND ADVISED THEM
 THAT DOCUMENTATION COULD NOT BE LOCATED
 FOR THE GENERATOR.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2000-10-30 Cont ID  
Sent By mcarsill Date 2000-10-30 Time 11:15 Rev Time 0.00
Received By mcarsill Date 2000-10-30 Time 11:15 Sent To  
Notes
2001-01-08 00:00:001) WRONG LIFE SAFETY CODE REFERENCED
 ON PLAN. SHOULD READ NFPA 101 LIFE
 SAFETY CODE 1985 EDITION INSTEAD OF
 1994 EDITION.
 2) PLEASE PROVIDE INTERIOR FINISH
 CLASSIFICATION INFORMATION FOR SPACE.
 3) PLEASE PROVIDE MORE DETAILS ON
 EMERGENCY GENERATOR AND FUEL STORAGE
 AREA ON GENERATOR.
 4) PLANS DO NOT INDICATE IF THE EXISTING
 BUILDING IS FIRE SPRINKLER PROTECTED.
 5) PROVIDE SEPARATE PLANS AND PERMITS
 FOR NEW FIRE ALARM EQUIPMENT PLANNED
 FOR BUILDING.
 6) SEPARATE PLANS AND PERMITS REQUIRED
 FOR MEDICAL GAS SYSTEMS.
  
 PLANS REVIEWED BY CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910
 ON 10-30-00 CALLED LEWIS AND ASSOCIATES
 AND REQUESTED MORE INFORMATION.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2001-06-04 Cont ID  
Sent By ndenmark Date 2001-06-04 Time 09:38 Rev Time 0.25
Received By ndenmark Date 2001-06-04 Time 09:38 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-01-03 Cont ID  
Sent By ndenmark Date 2001-01-03 Time 15:48 Rev Time 0.33
Received By ndenmark Date 2001-01-03 Time 15:48 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2000-11-28 Cont ID  
Sent By ndenmark Date 2000-11-28 Time 15:18 Rev Time 3.00
Received By ndenmark Date 2000-11-28 Time 15:18 Sent To  
Notes
2001-01-08 00:00:00***************DENIED*******************
  
 1.EXHAUST AIR QUANTITY IS QREATER THAN
 QUANTITY OF OUTSIDE AIR PROVIDED.
 EXPLAIN RATIONAL FOR NEGATIVE BUILDING
 PRESSURE. PROVIDE AIR BALANCE SCHEDULE
 SHOWING COMPLIANCE WITH 1997 SMC 501.2
  
 NOTE: MEDICAL GAS INSTALLATION REQUIRES
 ADDITIONAL MECHANICAL PERMIT. PROVIDE
 TWO SETS OF DETAILED PLANS SHOWING
 COMPLIANCE WITH 1999 NFPA 99C SPECIFIC
 TO THIS INSTALLATION AT TIME OF MECHAN-
 ICAL PERMIT APPLICATION FOR MEDICAL GAS
 PRIOR TO ANY WORK ON THIS SYSTEM.

Review Stop P PLUMBING
Rev No 3 Status P Date 2001-01-19 Cont ID  
Sent By jleech Date 2001-01-19 Time 14:50 Rev Time 1.00
Received By jleech Date 2001-01-19 Time 14:50 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2000-12-20 Cont ID  
Sent By jleech Date 2000-12-20 Time 09:54 Rev Time 1.00
Received By jleech Date 2000-12-20 Time 09:54 Sent To  
Notes
2001-01-08 00:00:00REVIEW NOTES 2,3,AND 4 WERE NOT
 ADDRESSED;
  
 1.SUBMIT OCCUPANT LOAD BASED ON
 HABITABLE SQ. FT. AREA PER. SPC
 407.1.3.
  
 2.SUBMIT FIRE SAFING DETAILS AND UL
 ASSEMBLY # FOR PIPE PENETRATIONS THRU
 RATED WALLS. REFER TO 1996 EDITION OF
 UL FIRE RESISTIVE DIRECTORY COUNTY-
 WIDE AMENDMENTS TO SPC SEC 104.2.4
 SBC CH.35
  
 THIS PLAN REVIEW DOESNOT INCLUDE
 MEDICAL GAS.
  
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT.8377

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-11-02 Cont ID  
Sent By tlarge Date 2000-11-02 Time 13:22 Rev Time 2.25
Received By tlarge Date 2000-11-02 Time 15:20 Sent To  
Notes
2001-01-08 00:00:001)SHT.ID-1-THE PLUMBING CODE IN EFFECT
 IS THE 1994 EDITION OF THE STANDARD
 PLUMBING CODE.COUNTYWIDE AMENDMENT TO
 SPC SEC.101.
  
 2)SUBMIT OCCUPANT LOAD BASED ON
 HABITABLE SQ.FOOT AREA PER SPC SEC.
 407.1.3.NU
  
 3)FLOORS AND WALLS IN TOILET ROOMS SHALL
 BE NONABSORBENT TO A HEIGHT OF 4' PER
 SBC SEC.1204.2.
  
 4)SUBMIT FIRE SAFING DETAIL AND UL
 ASSEMBLY # FOR PIPE PENETRATIONS THRU
 RATED WALLS.REFER TO 1996 EDITION OF
 UL FIRE RESISTIVE DIRECTORY.COUNTYWIDE
 AMENDMENTS TO SPC SEC.104.2.4.,SBC CH.35
  
 5)SHT.P-1-HEATER PAN REQS.MIN.OF 1"
 DRAIN PER SPC SEC.507.8.2.
  
 6)HEATER PAN SHALL COMPLY W/SPC SEC.
 507.8.2.
  
 7)VACUUM RELIEF VALVE SHALL COMPLY W/SPC
 SEC.507.1.2.,ANSI Z21.22.
  
 8)SHT.P-5-VENT FOR SHOWER & F.D.SHALL BE
 BETWWEN THE FIXTURE DRAINS.SPC 901.2.
  
 PLAN REVIEW DOES NOT INCLUDE MEDICAL
 GAS.
  
 CALL IF YOU HAVE ANY QUESTIONS.
 561-8096 EXT.8377.
  
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.