Plan Review Details - Permit 00101172
Plan Review Stops For Permit 00101172
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2001-11-14 Cont ID  
Sent By jwitmer Date 2001-11-14 Time 10:06 Rev Time 1.00
Received By jwitmer Date   Time   Sent To  
Notes
2001-11-14 00:00:00PROVISO: SEE PROVISO ON PLANS/ REVISION

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2001-07-20 Cont ID  
Sent By jwitmer Date 2001-07-20 Time 11:04 Rev Time 0.75
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-07-08 Cont ID  
Sent By jwitmer Date 2001-07-08 Time 10:45 Rev Time 7.00
Received By jwitmer Date 2001-06-21 Time 09:19 Sent To  
Notes
2001-07-08 00:00:00BUILDING PLAN REVIEW
 921 ORTEGA RD
 J L HAWKINS
 P: 966-6383
  
 SBC= REFRENCES TO STANDARD BUILDING CODE
 1997 EDITION
  
 1)- SBC 1606.4.1/1707.4.1 AMEND. REQUIES
 PRODUCT TESTING FOR COMPONENTS & CLAD-
 DING MISSING ARE THE PRODUCT APPROVAL
 REPORTS FOR THE NEW FRONT ENTRY DOORS.
  
 1B)- STORM SHUTTERS : THERE IS NO FASTEN
 ING SCHEDULE NOR IS THERE AND INSTALLA-T
 ION KEY FOR WINDOW TO SHUTTER LOCATION.
  
 1C)- DISCREPANCY: THE WINDOW PRODUCT APP
 ROVAL REPORT IS FOR CASEMENT WINDOWS BUT
 THE PLANS INDICATE SINGLE HUNG OR AWNING
 TYPE WINDOW IN ELEVATION VIEW? SLEEPING
 ROOMS REQUIRE EMERGENCY ESCAPE & RESCUE
 OPENINGS MINIMUM SIZES SBC 1005.4.
  
 ROOF FRAMING PLAN : MANSARD ROOF- NOTE-
 SBC TABLE 2308.1"D"NOTE 4 ALLOWS 5/8"
 DIRECT APPLICATION ONTO 2X4 STUDS, THE
 PLYWOOD IF GROOVED, GROOVES NO WIDER
 THAN 1 1/2" & SPACED NO CLOSER THAN 12"
 O.C. WHAT WILL BE USED FOR BACKING FOR
 THE FLASHING SINCE THERE IS NO SUB-
 SUBSHEATHING AND THE FINISH SIDING CAN'T
 GO TO THE ROOF DECK AS INDICATED ON THE
 NEW DETAIL? NEW ROOF PLAN SECTION A DOES
 NOT GIVE ANY STRAPPING INFO?
  
 3)- PROVIDE NOTICE OF COMMENCEMENT
 RECORDED AT THE CLEAK OF THE COUNTY
 COURT OFFICE BEEFORE THE PERMIT CAN BE
 ISSUED.
  
 PLAN REVIEW
 JIM WITMER
 (561) 659-8096 EX 8412

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2000-11-06 Cont ID  
Sent By dpalmer Date 2000-11-06 Time 07:57 Rev Time 0.00
Received By dpalmer Date 2000-11-06 Time 07:57 Sent To  
Notes
2001-01-08 00:00:00***************** PROVISO **************
  
 1)NOTE: PLEASE SUBMIT AIC RATING OF MAIN
 /PANEL BEFORE FINAL. PER 110-9 AND 215-5
  
 2)NOTE;PLEASE REVISED PLANS TO CORRELATE
 WITHRELINED ITEMS AND ANY AS-BUILTS.
 215-5
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW BEFORE FINAL ELECTRICAL INSPE
 -CTION IS CALLED IN. IF THERE ARE ANY
 QUESTIONS PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2001-06-21 Cont ID  
Sent By pkrauss Date 2001-06-21 Time 09:17 Rev Time 0.25
Received By pkrauss Date 2001-06-21 Time 09:17 Sent To  
Notes
2001-06-21 00:00:00NO REVISION TO MECHANICAL - J. LEECH
 APPROVED 3/10/01.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-03-10 Cont ID  
Sent By jleech Date 2001-03-10 Time 08:42 Rev Time 0.33
Received By jleech Date 2001-03-10 Time 08:42 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2000-11-06 Cont ID  
Sent By jleech Date 2000-11-06 Time 17:29 Rev Time 0.50
Received By jleech Date 2000-11-06 Time 17:29 Sent To  
Notes
2001-01-08 00:00:00DENIED;
 1.SIZE ALL DUCTWORK AND DROPS.
 2.LIST CFM'S FOR EACH DROP.
 3.SHOW RETURN AIR LOCATIONS AND SIZE.
 4.LIST EQUIPMENT SPECIFICATIONS;
 A.MANUFACTOR
 B.MODEL NUMBERS
 C.HEAT STRIP SIZE AND FUSE SIZE
 D.SEER RATE

Review Stop P PLUMBING
Rev No 4 Status P Date 2001-11-07 Cont ID  
Sent By kstevens Date 2001-11-07 Time 16:17 Rev Time 0.00
Received By kstevens Date 2001-11-07 Time 16:17 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2001-11-06 Cont ID  
Sent By kstevens Date 2001-11-06 Time 19:55 Rev Time 0.50
Received By kstevens Date 2001-11-06 Time 19:54 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2001-10-30 Cont ID  
Sent By kstevens Date 2001-10-30 Time 19:58 Rev Time 0.50
Received By kstevens Date 2001-10-30 Time 19:58 Sent To  
Notes
2001-10-30 00:00:00DENIED
  
 SIGNED AND SEALED PLANS SHALL HAVE SIGN-
 ED AND SEALED REVISIONS.

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-11-15 Cont ID  
Sent By fknapp Date 2000-11-15 Time 13:22 Rev Time 0.00
Received By fknapp Date   Time   Sent To  
Notes
2001-01-08 00:00:00OK PER T.LARGE

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2001-07-20 Cont ID  
Sent By jwitmer Date 2001-07-20 Time 11:05 Rev Time 0.50
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2001-03-15 Cont ID  
Sent By fknapp Date 2001-03-15 Time 16:25 Rev Time 3.00
Received By jwitmer Date 2001-03-15 Time 16:25 Sent To  
Notes
2001-03-15 00:00:00*************BUILDING UNSAT*************
  
 SBC 104.2.2
  
 1) PROVIDE 2 CURRENT COMPLETE COPIES OF
 SBCCI OR METRO DADE PRODUCT APPROVALS
 FOR:
 ALL EXTERIOR DOORS AND WINDOWS
 MULLIONS
 ROOF COVER
  
 2) PROVIDE STORM PANEL INFORMATION WITH
 INSTALLATION SCHEDULE AND KEY PLAN WITH
 SPECIFIC ANCHORS AND MOUNTING TO BE USED
 FOR ALL NON-IMPACT GLAZING.
  
 3) PROVIDE ENERGY CALCULATIONS THAT HAVE
 SIGNATURE OF OWNER/AGENT COMPLETE WITH
 MANUAL J FORM.
  
 4) PROVIDE ROOF FRAMING PLAN.
  
 5) PROVIDE NOTES ON SHEET A-4 THAT
 REFERENCES 1997 SBC ANDHAS CORRECT
 MEAN ROOF HEIGHT.
  
 6) PROVIDE DESIGN COMPLIANCE FORM THAT
 MATCHES DESIGN OF PLANS.
  
 7) PROVIDE DETAILS WITH DIMENSIONS OF
 GUARDRAIL AND HANDRAILS PER 1997 SBC
 1007.5 AND 1015
  
 8) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 ANY QUESTIONS PLEASE CALL,
 FRANK KNAPP
 BUILDING PLAN REVIEW
 DEPARTMENT OF CONSTRUCTION SERVICES
 CITY OF WEST PALM BEACH
 (561) 659-8096 EXT. 8392

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date   Cont ID  
Sent By fknapp Date 2000-11-15 Time 14:27 Rev Time 4.00
Received By fknapp Date 2000-11-15 Time 13:23 Sent To  
Notes
2001-01-08 00:00:00 
  
 ************BUILDING UNSAT**************
  
 SBC 104.2.2
  
 1)PROVIDE 2 CURRENT COMPLETE COPIES OF
 SBCCI OR METRO DADE PRODUCT APPROVALS
 FOR:
 ALL EXTERIOR DOORS AND WINDOWS
 MULLIONS
 ROOF COVER
  
 2)PROVIDE INSTALLATION SCHEDULE AND KEY
 PLAN FOR STORM PANELS WITH SPECIFIC
 ANCHORS TO BE USED.
  
 3)PROVIDE ENERGY CALCULATIONS COMPLETE
 WITH MANUAL J.
  
 4)PROVIDE DESIGN CERTIFICATION FOR
 BUILDING CODE COMPLIANCE.
  
 5)PROVIDE DETAILS FROM REGISTERED
 ENGINEER FOR SUPPORTING FOUNDATION AND
 STRUCUAL REPAIRS.
  
 6)PROVIDE ROOF FRAMING PLAN.
  
 7)PROVIDE NOTES THAT REFERENCE 1997 SBC
 AND HAVE CORRECT MEAN ROOF HEIGHT.
  
 8)PROVIDE BR WINDOWS THAT COMPLY WITH
 EGRESS 1997 SBC 1005.4
  
 9)PROVIDE ROOF SHEATHING NAILING ZONES
 PER CITY AMENDMENTS 1997 SBC FIG.2306.1
  
 10)PROVIDE WINDOW AND DOOR BUCK
 CONNECTION DETAILS PER 1997 SBC 1606
  
 11)PROVIDE DETAILS WITH DIMENSIONS OF
 GUARDRAIL AND HANDRAILS PER 1997 SBC
 1007.5 AND 1015
  
 12)PROVIDE NEW VALUE OF WORK TO BE DONE
 TO INCLUDE LABOR AND MATERIAL.
  
 13)PROVIDE A COURT RECORDED NOC BEFORE A
 PERMIT CAN BE ISSUED.