| 2001-01-08 00:00:00 | CHECKLIST: |
| | 1-SCOPE OF WORK IS NOT CLEAR. |
| | -ARCHITECT'S PLANS INDICATE THAT THE |
| | PORCH IS EXISTING, BUT AFTER PHONE |
| | CONVERSATION WITH THE CONTRACTOR BOB |
| | COHEN (CELL PHONE 523-0304), HE SAID |
| | THAT PORCH IS NEW. |
| | 2-THERE IS AN OPEN APPLICATION FOR |
| | CONSTRUCTION OF COVERED PORCH. IS THIS |
| | THE SAME PORCH?. CLARIFY. |
| | APPLICATION NUMBER 00-08-1029. |
| | 3-PROVIDE PRODUCT APPROVAL FOR NEW "GAF" |
| | FLAT ROOF SYSTEM. |
| | 4-THERE IS A PRODUCT APPROVAL FOR NEW |
| | FRENCH DOORS. WHERE ARE THE NEW FRENCH |
| | DOORS GOING TO BE INSTALLED? |
| | 5-IF THERE IS ANY WORK TO BE DONE AT THE |
| | GARAGE, THEN PROVIDE COMPLETE PLANS |
| | UNDER A SEPARATE APPLICATION. PLEASE, |
| | COORDINATE WITH THE ZONING TECHNICIAN |
| | FOR USE PERMITTED BY THE ZONING CODE. |
| | 6-REVISE SLOPE OF ROOF. MIN. 1/4" PER FT |
| | AS PER SECTION 1503.1.2.3 SBC 1997. |
| | 7-GUARDRAIL SPACING SO THAT A 4" SPHERE |
| | CAN'T GO THRU. SECTION 1015.3 SBC 1997 |
| | |
| | |
| | |
| | |
| | |
| | NOTE: |
| | |
| | -IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| | JULIO GOMEZ, BUILDING PLAN REVIEWER, AT |
| | 659-8096 EXT. 8232. |