| 2001-01-08 00:00:00 | ****************** UNSAT ************** |
| | |
| | 1)NOTE:PLEASE SUBMIT A CLEAR RISER DIA- |
| | -GRAM SHOWING WORK BEING DONE. |
| | |
| | 2)NOTE: YOU SHOW AN EXISTING 200A METER |
| | PACK AND YOU ARE INCREASING SERVICE BUT |
| | NOT METERBANK?? PLEASE SHOW EXISTING |
| | RISER CONDUCTORS FOR SERVICE INCREASE. |
| | |
| | 3)NOTE: PLEASE SEE WHERE IT IS PROPOSED |
| | TO INCREASE PANEL TO 200A WITH #1 WIRE. |
| | THIS IS NOT PERMITTED PER NEC. |
| | |
| | 4)NOTE: PLEASE DIVIDE LOAD CALCULATIONS |
| | FOR EACH PANEL AND ONE FOR TOTAL SERVICE |
| | PLEASE LAYOUT/SHOW PER NEC AND ART215-5. |
| | THE TOTAL SQ FT SHOWN IS 2000. IS THIS |
| | FOR MAIN HOUSE? GARAGE/APT? OR BOTH? |
| | |
| | 5)NOTE: PLEASE SHOW ELECTRICAL REWORK |
| | IN KITCHEN THAT IS PROPOSED ON APPLICAT- |
| | -ION.PLEASE SHOW LAYOUT OF FLOOR PLAN |
| | FOR CHANGES. |
| | |
| | 6)NOTE: PLEASE SEE NEC 310-15. #4 IS NOT |
| | RATED FOR 125A SERVICE OR PANEL. |
| | |
| | PLEASE SUBMIT PLANS WITH MORE DETAIL. |
| | PLEASE SEE CITY/COUNTY ADMINISTRATIVE |
| | CODE 104.2 AND 104.2.7. |
| | PLEASE SUBMIT ALL THE ABOVE INFORMATION |
| | FOR REVIEW. IF THERE ARE ANY QUESTIONS |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW. |
| | 659-8096 EXT 8372 |