| Plan Review Stops For Permit 00101083 |
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2001-05-17 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-05-17 |
Time |
15:59 |
Rev Time |
0.35 |
| Received By |
pkrauss |
Date |
2001-05-17 |
Time |
15:59 |
Sent To |
|
|
| Notes |
| 2001-05-17 00:00:00 | AS BUILT DRAWINGS. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2000-10-28 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2000-10-28 |
Time |
07:36 |
Rev Time |
0.50 |
| Received By |
jleech |
Date |
2000-10-28 |
Time |
07:36 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PROVISO; | | | 1.R/A REQUIRED FROM UPSTAIRS MASTER | | | SUITE ALSO. | | | 2.REVISE AIR FLOW CALKULATIONS FIRST | | | FLOOR 1 1/2 TON UNIT IS NOT CAPABLE | | | OF PUSHING 840 CFM'S OR INSTALL A | | | 2 TON UNIT. | | | 3.REVISED DRAWINGS REQUIRED BEFORE FINAL | | | A/C INSPECTION. |
|
|
|