| Plan Review Stops For Permit 00101075 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2001-01-09 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-01-09 |
Time |
11:40 |
Rev Time |
3.00 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-09 00:00:00 | PROVISO: SEE PLANS FOR LIST. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2000-11-08 |
|
|
Cont ID |
|
| Sent By |
drunnels |
Date |
2000-11-08 |
Time |
12:32 |
Rev Time |
2.00 |
| Received By |
drunnels |
Date |
2000-11-08 |
Time |
12:32 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1.THE FLORIDA ENERGY SHEETS MUST BE | | | SIGNED BY THE OWNER/AGENT. | | | 2.SUBMIT DETAIL SHOWING TENANT | | | SEPERATION WALL COMPLYING WITH SECTION | | | 704.3 1997 SBC | | | 3.SECTION 704 REQUIRES A MINIMUM OF 2-HR | | | SEPERATION BETWEEN STORAGE AND | | | MERCANTILE OCCUPANCIES. | | | 4.ALL OPENINGS IN RATED WALLS MUST | | | COMPLY WITH SECTION 705 1997 SBC | | | 5.NEW EXTERIOR DOOR SHALL COMPLY WITH | | | SECTION 705 1997 SBC. | | | 6.SUBMIT PRODUCT APPROVAL FOR NEW | | | EXTERIOR DOOR, METRO DADE COUNTY/SBCCI |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
N |
Date |
2001-01-04 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-01-04 |
Time |
11:07 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-01-04 |
Time |
11:07 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ELECTRICAL BEING PULLED FROM PLANS. | | | TO BE SUBMITTED SEPARTELY UNDER NEW | | | PERMIT. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2001-01-03 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-01-03 |
Time |
21:14 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-01-03 |
Time |
21:14 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ************** UNSAT ****************** | | | | | | | | | ELECTRICAL PLANS WERE ALREADY SUBMITTED | | | AND PASSED WITH A PROVISO!! NOW NEW | | | ELECTRICAL PLANS ARE SUBMITTED.!! | | | WHERE ARE THE PLANS THAT SHOWED EGRESS | | | LIGHTING, EXIT LIGHTING AND EMERGENCY | | | LIGHTING??????? WHERE ARE THE PLANS.?? | | | WE NEEDED LOAD CALCUALTIONS SUBMITTED | | | FOR THE TRACK LIGHTING THAT WAS SUBMITT- | | | -ED ON PERVIOUS PLANS. PLANS N WENT BACK | | | AND THESE COMMENTS WERE NOT ADDRESSED??? | | | | | | STOARGE AREA OUTLETS STILL ARE NOT | | | CIRCUITED?? | | | | | | PANEL SCHEDULE IS NOT SHOWN TO CORRELATE | | | WITHTHE NEW CIRCUITS SHOWN EITHER?? | | | | | | | | | PLEASE CALL FOR CLARIFICATION ON THE | | | ABOVE. I PLACED MY PHONE # AND EXT ON | | | THE PREVIOUS NOTES, AND TO THIS DAY NO - | | | ONE HAS CALLED WITH ANY QUESTIONS. | | | | | | | | | PLEASE CALL | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2000-10-31 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-10-31 |
Time |
20:01 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-10-31 |
Time |
20:01 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ************** PROVISO ***************** | | | | | | 1)NOTE: PLEASE SEE ART; 220-12B FOR | | | TRACK LIGHTING CALCULATIONS. PLEASE | | | SUBMIT LOAD CALCS REFLECTING NEC REQ` | | | MENTS. | | | | | | 2)NOTE: PLEASE NOTE AS PER PALM BEACH | | | COUNTY LOCAL AMENDMENTS. STORAGE AREA | | | NEED TO PROVIDE OUTLETS PER 20` OF WALL | | | SPACE. | | | | | | PLEASE REVISE PLAN TO REFLECT THE ABOVE | | | AND SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW BEFORE ROUGH ELECTRICAL INSPECT- | | | -ION IS CALLED IN. IF THERE ARE ANY | | | QUESTIONS PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2000-12-28 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-12-28 |
Time |
15:13 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2000-12-28 |
Time |
15:13 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2000-12-14 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-12-14 |
Time |
08:40 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2000-12-14 |
Time |
08:40 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1) THE PLAN DOES NOT INDICATE IF THE | | | ENTIRE WEST WALL IS ONE HOUR FIRE | | | SEPARATED. | | | 2) THE PLAN DOES NOT INDICATE IF THE | | | ENTIRE EAST WALL IS ONE HOUR FIRE | | | SEPARATED. | | | 3) WHAT TYPE OF OCCUPANCY IS LOCATED | | | NEXT TO THE WEST WALL OF THE TENANT | | | SPACE. | | | 4) NO UL NUMBER PROVIDED FOR THE FIRE | | | RATING. | | | 5) NO DOOR SCHEDULE PROVIDED WITH PLANS. | | | | | | PLANS REVIEWED BY CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2000-11-07 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-11-07 |
Time |
12:50 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2000-11-07 |
Time |
12:50 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1) EXITING INTO THE STOCKROOM IS ALLOWED | | | ONLY IF THE FOLLOWING CONDITIONS EXIST: | | | AN AISLE OF AT LEAST 44 INCHES IS | | | PROVIDED AND MAINTAINED, THE DOOR | | | LEADING TO THE STOCKROOM IS NOT SUBJECT | | | TO LOCKING, AND NOT MORE THAN 50 | | | PERCENT OF EXIT ACCESS IS PROVIDED | | | THROUGH STOCKROOM. | | | 2) INTERIOR FINISH TO BE CLASS A OR B. | | | 3) PLEASE CORRECT DEAD-END OF MORE THAN | | | 20 FEET. | | | 4) STORAGE AREA TO BE AT LEAST ONE HOUR | | | FIRE RATED WITH A RATED FIRE DOOR AND | | | CLOSER SEPARATING IT FROM THE DISPLAY | | | AREA SINCE NO FIRE SPRINKLERS ARE | | | PRESUMED TO BE PRESENT. | | | 5) PLEASE INDICATE THE TYPE OF STORAGE | | | PLANNED FOR THE STORAGE AREA. | | | | | | PLANS REVEIWED BY CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
N |
Date |
2001-01-09 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2001-01-09 |
Time |
13:16 |
Rev Time |
0.25 |
| Received By |
ndenmark |
Date |
2001-01-09 |
Time |
13:15 |
Sent To |
|
|
| Notes |
| 2001-01-09 00:00:00 | MECHANICAL REMOVED FROM DRAWINGS FOR | | | REVIEW. SUBMIT MECHANICAL PLANS AT TIME | | | OF PERMIT APPLICATION PRIOR TO ANY | | | MECHANICAL WORK BEING DONE. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2000-11-08 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-11-08 |
Time |
09:08 |
Rev Time |
0.25 |
| Received By |
ndenmark |
Date |
2000-11-08 |
Time |
09:08 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ***********DENIED*********************** | | | 1. PROVIDE OUTSIDE AIR CALCULATIONS PER | | | ASHRAE 62-89 | | | 2. PROVIDE CFM VALUES FOR EACH DROP FOR | | | BALANCE OF SYSTEM |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2000-12-10 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2000-12-10 |
Time |
09:05 |
Rev Time |
1.00 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PLUMBING PLAN REVIEW | | | (1) FACILITIES SHOWN AS EXISTING. | | | (2) BACK FLOW PREVENTER ON WATER SERVICE | | | IS REQUIRED,IF NOT ON THERE, ORD#285395 | | | END OF COMMENTSPAUL SCHMITZ | | | 561-659-8096 X 8233 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2000-10-28 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-10-28 |
Time |
07:24 |
Rev Time |
0.30 |
| Received By |
tlarge |
Date |
2000-10-28 |
Time |
07:24 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PLUMBING SHOWN AS EXISTING. |
|
|