Plan Review Details - Permit 00101068
| Plan Review Stops For Permit 00101068 |
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2000-12-19 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-12-19 |
Time |
08:42 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2000-12-19 |
Time |
08:42 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1) EXHAUST SYSTEM OUTLET BEHIND | | | SCRUBBER TO MEET THE REQUIREMENTS OF | | | NFPA 96. "DOWNGRADING OTHER PARTS OF | | | THE EXHAUST SYSTEM DUE TO THE | | | INSTALLATION OF THESE APPROVED DEVICES, | | | WHETHER LISTED OR NOT, SHALL NOT BE | | | ALLOWED". RE: NFPA 96, SECTION 6-3 | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2000-11-28 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-11-28 |
Time |
08:45 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2000-11-28 |
Time |
08:45 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2000-10-30 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-10-30 |
Time |
09:06 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2000-10-30 |
Time |
09:05 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1) NO PLANS SUBMITTED WITH PERMIT | | | APPLICATION. WRITER NOTED THAT FAXED | | | INFORMATION WAS INCLUDED WITH | | | PERMIT APPLICATION. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2000-12-19 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-12-19 |
Time |
09:17 |
Rev Time |
5.00 |
| Received By |
ndenmark |
Date |
2000-12-19 |
Time |
09:17 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PROVISO: | | | DON NOT DOWNGRADE DUCT SYSTEM DOWNSTREAM | | | OF SCRUBBER UNIT PER NFPA 96 6-3 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2000-11-28 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-11-28 |
Time |
11:20 |
Rev Time |
2.00 |
| Received By |
ndenmark |
Date |
2000-11-28 |
Time |
11:20 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | *************DENIED********************* | | | PROVIDE INFORMATION ON FILTERS ASSEMBLY | | | SPECIFIC STANDARD ASHRAE 52-76 SPECS | | | | | | PROVIDE INFORMATION SHOWING COMPLIANCE | | | WITH NFPA 96 6-3 AND 6-3.1 | | | | | | DUCT CONTSTRUCTION TO BE SAME ON BOTH | | | SIDES OF THE FILTER AND FAN SECTIONS | | | | | | EXHAUST OUTLET TO COMPLY WITH NFPA 96 | | | 4-8.3 SEE FIGURE 4-8.3.1(A). |
|
|
|