Plan Review Stops For Permit 00101025
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-11-20 Cont ID  
Sent By dpalmer Date 2000-11-20 Time 17:51 Rev Time 0.00
Received By dpalmer Date 2000-11-20 Time 17:50 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-11-06 Cont ID  
Sent By dpalmer Date 2000-11-06 Time 19:12 Rev Time 0.00
Received By dpalmer Date 2000-11-06 Time 19:12 Sent To  
Notes
2001-01-08 00:00:00************** UNSAT ******************
  
 1)NOTE: PLEASE NOTE THAT PER FS AND FL.
 ADMINISTRATIVE CODE. PLANS ARE TO BE
 SIGNED AND SEALED BY ENGINEER OF RECORD
 61G15-25.002 AND 471.025
  
 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 MAIN DISCONNECT AND PANEL. ALL MUST BE
 RATED FOR THE AVAILABLE FAULT CURRENT
 PER 110-9. SHOW PER 215-5
  
 3)NOTE: PLEASE SEE THAT NO LOAD CALCULAT
 -IONS WERE SUBMITTED/SHOWN?? 215-5
  
 4)NOTE: PLEASE SHOW PANEL SCHEDULE PER
 215-5 AND PLEASE MAKE SURE TO LIST THE
 REQ`D DEDICATED BATH(S) CIRCUIT(S) PER
 210-11-C-3 AND 210-52D.
  
 5)NOTE; PLEASE SHOW RECEPT FOR JACUZZI
 W/ GFI PROTECTION NOTED.
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-10-28 Cont ID  
Sent By jleech Date 2000-10-28 Time 13:32 Rev Time 0.33
Received By jleech Date 2000-10-28 Time 13:31 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-10-27 Cont ID  
Sent By tlarge Date 2000-10-27 Time 09:50 Rev Time 0.33
Received By tlarge Date 2000-10-27 Time 09:50 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2001-01-23 Cont ID  
Sent By lmartine Date 2001-01-23 Time 16:51 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2000-11-22 Cont ID  
Sent By drunnels Date 2000-11-22 Time 10:46 Rev Time 1.00
Received By drunnels Date 2000-11-22 Time 09:53 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2000-10-25 Cont ID  
Sent By sgraham Date 2000-10-25 Time 15:19 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***