Plan Review Details - Permit 00100965
Plan Review Stops For Permit 00100965
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-12-11 Cont ID  
Sent By dpalmer Date 2000-12-11 Time 17:06 Rev Time 0.00
Received By dpalmer Date 2000-12-11 Time 17:06 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-11-06 Cont ID  
Sent By dpalmer Date 2000-11-06 Time 18:59 Rev Time 0.00
Received By dpalmer Date 2000-11-21 Time 15:31 Sent To  
Notes
2001-01-08 00:00:00***************** UNSAT ***************
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL EQUIPMENT BEING INSTALLED. MAINS/AND
 PANELS MUST BE RATED FOR THE AVAILABLE
 FAULT CURRENT PER 110-9. PER 215-5
  
 2)NOTE: PLEASE SEE PANELS AND RISER
 DIAGRAM. PLEASE CORRELATE THE MLO AND
 MCB SHOWN??
  
 3)NOTE: PLEASE INCLUDE AND SHOW BLDG.
 STEEL AS PART OF THE GROUNDING ELECTRODE
 SYSTEM PER 250-50.
  
 4)NOTE: PLEASE LIST THE REQ`D DEDICATED
 BATH(S) CIRCUIT(S) ON PANEL SCHEDULE
 PER 210-11-C-3. AND 215-5
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-07-06 Cont ID  
Sent By pkrauss Date 2001-07-06 Time 09:26 Rev Time 0.25
Received By pkrauss Date 2001-07-06 Time 09:25 Sent To  
Notes
2001-07-06 00:00:00MECHANICAL PERMIT 01051555.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-10-28 Cont ID  
Sent By jleech Date 2000-10-28 Time 14:39 Rev Time 0.50
Received By jleech Date 2000-10-28 Time 14:39 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-10-29 Cont ID  
Sent By tlarge Date 2000-10-29 Time 12:52 Rev Time 0.33
Received By tlarge Date 2000-10-29 Time 12:52 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2000-12-07 Cont ID  
Sent By drunnels Date 2000-12-07 Time 09:14 Rev Time 1.00
Received By drunnels Date 2000-12-07 Time 09:13 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2000-11-22 Cont ID  
Sent By drunnels Date 2000-11-22 Time 09:44 Rev Time 2.00
Received By drunnels Date 2000-11-21 Time 15:32 Sent To  
Notes
2001-01-08 00:00:001] SUBMIT PRODUCT APPROVAL FOR ROOF
 COVERING.

Review Stop Z ZONING
Rev No 1 Status P Date 2000-10-27 Cont ID  
Sent By sgraham Date 2000-10-27 Time 10:47 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved