Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2000-10-20 Cont ID  
Sent By lmartine Date 2000-10-20 Time 07:47 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-10-26 Cont ID  
Sent By jleahy Date 2000-10-26 Time 07:52 Rev Time 0.30
Received By jleahy Date 2000-10-26 Time 07:51 Sent To  
Notes
2001-01-08 00:00:00SEE CHECK LIST FROM DEWEY 10/19/00 JL

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-10-19 Cont ID  
Sent By dpalmer Date 2000-10-19 Time 20:51 Rev Time 0.00
Received By dpalmer Date 2000-10-19 Time 20:51 Sent To  
Notes
2001-01-08 00:00:00************** UNSAT *******************
  
 1)NOTE: PLEASE NOTE THAT ALL CONTINUOUS
 LOADS ARE TO BE CALCULATED AT 125%.
 LIGHTING ETC.
  
 2)NOTE: LOAD THAT IS SHOWN, ALREADY
 EXCEEDS THE 80% PERMITTED OF BRKR RATING
  
 3)NOTE: PLEASE SHOW TRACK LIGHTING PER
 220-12B
  
 PLEASE SUBMIT THE ABOVE INFORMATION AND
 MAKE CORRECTIONS FOR REVIEW.
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372