| Plan Review Stops For Permit 00100881 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2000-10-20 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2000-10-20 |
Time |
07:47 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2000-10-26 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2000-10-26 |
Time |
07:52 |
Rev Time |
0.30 |
| Received By |
jleahy |
Date |
2000-10-26 |
Time |
07:51 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | SEE CHECK LIST FROM DEWEY 10/19/00 JL |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2000-10-19 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-10-19 |
Time |
20:51 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-10-19 |
Time |
20:51 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ************** UNSAT ******************* | | | | | | 1)NOTE: PLEASE NOTE THAT ALL CONTINUOUS | | | LOADS ARE TO BE CALCULATED AT 125%. | | | LIGHTING ETC. | | | | | | 2)NOTE: LOAD THAT IS SHOWN, ALREADY | | | EXCEEDS THE 80% PERMITTED OF BRKR RATING | | | | | | 3)NOTE: PLEASE SHOW TRACK LIGHTING PER | | | 220-12B | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION AND | | | MAKE CORRECTIONS FOR REVIEW. | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
|