Plan Review Details - Permit 00100865
| Plan Review Stops For Permit 00100865 |
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2000-11-28 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-11-28 |
Time |
16:04 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2000-11-28 |
Time |
16:04 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | HOOD INSTALLATION ONLY. FIRE SUPPRESSION | | | SYSTEM TO BE REVIEWED UNDER SEPARATE | | | PLANS AND PERMIT. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2000-11-02 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-11-02 |
Time |
18:49 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2000-11-02 |
Time |
18:49 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1) NOT ENOUGH INSPECTION AND CLEAN-OUTS | | | PORTALS PROVIDED FOR SYSTEM. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2000-12-01 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-12-01 |
Time |
13:24 |
Rev Time |
1.00 |
| Received By |
ndenmark |
Date |
2000-12-01 |
Time |
13:23 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PROVISO: | | | 1.SUBMIT 2 SETS OF DRAWINGS DETAILING | | | CHANGES AS INDICATED ON OFFICE SET DO | | | NOT CALL FOR INSPECTIONUNTIL PLANS | | | ARE RESUBMITTED. | | | PROVIDE INFO ON PLANS FOR THE 1" PER FT | | | SLOPE ON THE DUCT. | | | PROVIDE SBCCI APPROVAL FOR THE WRAP. | | | PROVIDE REVISION ON DUCT SIZES WHERE | | | APPLICABLE. | | | PROVIDE INFO ON OTHER CHANGES AS INDICA- | | | TED ON DRAWING AND SITE. | | | PROVIDE CLEANOUT DETAIL FOR WRAP AND | | | DUCT. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2000-10-21 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-10-21 |
Time |
13:07 |
Rev Time |
0.50 |
| Received By |
ndenmark |
Date |
2000-10-21 |
Time |
13:07 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ************DENIED********************** | | | | | | 1. 1997 SMC 505.4 REQUIRES MIN. 1" PER | | | FOOT SLOPE BACK TOWARD HOOD OR APPROVED | | | RESIDUE TRAP. TRAP APPEARS TO BE IN | | | ANOTHER SPACE OR OTHERWIZE UNACCESSIBLE | | | FOR CLEANING AND MONITORING. PROVIDE | | | INFORMATION ON APPROVAL OF GREASE TRAP | | | AS INDICATED AND LOCATION IN RELATION TO | | | OTHER BUILDING COMPONENTS. | | | 2. PROVIDE REQUIRED SLOPE ON DUCT. | | | 3. PROVIDE MANUFACTURES INFORMATION | | | SHOWING APPROVED TRANSITION METHOD FROM | | | DUCT WRAP TO ENCLOSURE. | | | 4. NFPA 96 4-3.4.3 REQUIRES WHERE | | | PERSONNELL ENTRY IS NOT POSSIBLE, | | | ADEQUATE ACCESS FOR CLEANING SHALL BE | | | PROVIDED AT EACH FLOOR.PROVIDE DETAIL. | | | 5.NFPA 96 4-7.2.2 REQUIRES ENCLOSURE TO | | | BE NOT LESS THAN 2 HRS. |
|
|
|