Plan Review Details - Permit 00100865
Plan Review Stops For Permit 00100865
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2000-11-28 Cont ID  
Sent By mcarsill Date 2000-11-28 Time 16:04 Rev Time 0.00
Received By mcarsill Date 2000-11-28 Time 16:04 Sent To  
Notes
2001-01-08 00:00:00HOOD INSTALLATION ONLY. FIRE SUPPRESSION
 SYSTEM TO BE REVIEWED UNDER SEPARATE
 PLANS AND PERMIT.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2000-11-02 Cont ID  
Sent By mcarsill Date 2000-11-02 Time 18:49 Rev Time 0.00
Received By mcarsill Date 2000-11-02 Time 18:49 Sent To  
Notes
2001-01-08 00:00:001) NOT ENOUGH INSPECTION AND CLEAN-OUTS
 PORTALS PROVIDED FOR SYSTEM.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2000-12-01 Cont ID  
Sent By ndenmark Date 2000-12-01 Time 13:24 Rev Time 1.00
Received By ndenmark Date 2000-12-01 Time 13:23 Sent To  
Notes
2001-01-08 00:00:00PROVISO:
 1.SUBMIT 2 SETS OF DRAWINGS DETAILING
 CHANGES AS INDICATED ON OFFICE SET DO
 NOT CALL FOR INSPECTIONUNTIL PLANS
 ARE RESUBMITTED.
 PROVIDE INFO ON PLANS FOR THE 1" PER FT
 SLOPE ON THE DUCT.
 PROVIDE SBCCI APPROVAL FOR THE WRAP.
 PROVIDE REVISION ON DUCT SIZES WHERE
 APPLICABLE.
 PROVIDE INFO ON OTHER CHANGES AS INDICA-
 TED ON DRAWING AND SITE.
 PROVIDE CLEANOUT DETAIL FOR WRAP AND
 DUCT.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2000-10-21 Cont ID  
Sent By ndenmark Date 2000-10-21 Time 13:07 Rev Time 0.50
Received By ndenmark Date 2000-10-21 Time 13:07 Sent To  
Notes
2001-01-08 00:00:00************DENIED**********************
  
 1. 1997 SMC 505.4 REQUIRES MIN. 1" PER
 FOOT SLOPE BACK TOWARD HOOD OR APPROVED
 RESIDUE TRAP. TRAP APPEARS TO BE IN
 ANOTHER SPACE OR OTHERWIZE UNACCESSIBLE
 FOR CLEANING AND MONITORING. PROVIDE
 INFORMATION ON APPROVAL OF GREASE TRAP
 AS INDICATED AND LOCATION IN RELATION TO
 OTHER BUILDING COMPONENTS.
 2. PROVIDE REQUIRED SLOPE ON DUCT.
 3. PROVIDE MANUFACTURES INFORMATION
 SHOWING APPROVED TRANSITION METHOD FROM
 DUCT WRAP TO ENCLOSURE.
 4. NFPA 96 4-3.4.3 REQUIRES WHERE
 PERSONNELL ENTRY IS NOT POSSIBLE,
 ADEQUATE ACCESS FOR CLEANING SHALL BE
 PROVIDED AT EACH FLOOR.PROVIDE DETAIL.
 5.NFPA 96 4-7.2.2 REQUIRES ENCLOSURE TO
 BE NOT LESS THAN 2 HRS.