Plan Review Details - Permit 00100791
Plan Review Stops For Permit 00100791
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2000-10-18 Cont ID  
Sent By mcarsill Date 2000-10-18 Time 13:59 Rev Time 0.00
Received By mcarsill Date 2000-10-18 Time 13:59 Sent To  
Notes
2001-01-08 00:00:001) MANAUL PULL STATIONS ARE NOT
 REQUIRED.
 2) FIRE ALARM EQUIPMENT INSTALLED IN
 ANTHROPOLOGIE SHALL BE INTERFACED WITH
 THE BASE BUILDING FIRE ALARM SYSTEM.
 3) FIRE ALARM SYSTEM WHEN ACTIVATED
 IS TO BE AUDIBLE THROUGHOUT.
 4) FIRE ALARM SYSTEM IS TO BE CLASS A,
 STYLE D OR ADDRESSABLE.
 5) PLEASE PROVIDE A HORN STROBE NEAR
 THE MAIN ENTRY DOOR LOCATION.
 6) DUCT DETECTOR REQUIRED IN AIR
 HANDLING SYSTEMS OVER 2000 CFM.
 7) SMOKE DETECTORS ARE TO BE LOCATED
 NO CLOSER THAN THREE FEET FROM AIR
 CONDITIONER DIFFUSERS.
 APPROVED PROVISO:
  
 PLANS REVIEWED BY CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910