Plan Review Details - Permit 00100785
Plan Review Stops For Permit 00100785
Review Stop P PLUMBING
Rev No 2 Status P Date 2000-11-06 Cont ID  
Sent By pschmitz Date 2000-11-06 Time 09:21 Rev Time 1.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-01-08 00:00:00RESUB FOR PLAN REVIEW OK PES.

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-10-20 Cont ID  
Sent By tlarge Date 2000-10-20 Time 04:36 Rev Time 0.65
Received By pschmitz Date 2000-10-20 Time 04:35 Sent To  
Notes
2001-01-08 00:00:00ALL SUBMITTED SHHETS SHALL BE SIGNED,
 DATED AND SEALED BY THE DESIGN
 PROFESSIONAL PER COUNTYWIDE AMENDMENTS
 TO SPC SEC.104.2.3.(RE:LEGAL SHEET)
  
 2)PLANS REFER TO SOUTH FLORIDA BUILDING
 CODE.THE APPLICABLE CODES IN THE CITY OF
 WEST PALM BEACH ARE THE STANDARD PLUMB-
 ING CODE,1994 ED.,STANDARD BUILDING,
 MECHANICAL,AND GAS CODES,1997 ED.
  
 3)SHOW MEANS OF DRAINING AND VENTING THE
 SYSTEM PER SMC SEC.1513.
  
 4)SHOW PRESSURE RELIEF DEVICE PER SMC
 SEC.1504.5.
  
 5)SUBMIT TWO COPIES OF LEGIBLE DATA
 SHEETS FROM THE FLA.ENERGY CENTER.
  
 6)THE DESIGN PROFESSIONAL'S NAME,ADDRESS
 AND PHONE NUMBER SHALL BE LEGIBLY
 INDICATED ON EACH SHEET PER FL.ADMIN.
 RULE 61G15-23.002.
  
 CALL IF YOU HAVE QUESTIONS.
 561-659-8096,EXT.8377
  
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.