Plan Review Details - Permit 00100781
Plan Review Stops For Permit 00100781
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-05-29 Cont ID  
Sent By dpalmer Date 2001-05-25 Time 06:57 Rev Time 0.00
Received By nleiva Date 2001-05-25 Time 06:57 Sent To  
Notes
2001-05-25 00:00:00**************** UNSAT **************
  
 1)NOTE: PLEAS NOTE THAT PLANS ARE
 SHOWING THREE AHU`S AND ONLY TWO COND
 UNITS? PLEASE SHOW/CLARIFY
  
 2)NOTE: PLEASE NOTE THAT, NEED TO SHOW
 SEPARATE PANEL SCHEDULES FOR "A" AND "C"
 BOTH ARE SHOWN ON SAME SCHED. THIS IS
 FROM FIRST PROVISO.
  
 3)NOTE: PLEASE CLARIFY EQUIPMENT GROUND
 FROM FIRST MEANS OF DISCONNECT OF PANELS
 B AND C. CONDUIT ARE SHOWN WITH FEEDERS
 BUT NEED CLARIFICATION ON GROUND? IS
 THIS CONDUIT EMT, RIDGID?
  
 4)NOTE: PLEASE NOTE THAT LOAD SHOWN ON
 CIRCUITS FOR LIGHTINGWAY EXCEED THE
 80% LOAD PERMITTED BY THE NEC.
  
 5)NOTE: PLEASE CLARIFY OUTLET SHOWN
 IN/AT WATER CLOSET ON SECOND FLOOR.
  
 6)NOTE: PLEASE CLARIFY LOCATION OF
 SERVICE. ELECTRICAL INSPECTOR MENTIONED
 THE POSSIBILITY OF SERVICE BEING ON THE
 OTHER SIDE OF HOUSE.
 PLEASE SUBMIT THE PLAN/AS-BUILT FOR A-8
 FOR GARAGE.
  
  
 7) NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
  
 PLEASE NOTE THAT THE PROVISO ASKING FOR
 SOME OF THESE ITEMS WAS GIVEN LAST
 NOVEMBER. THE PLANS ARE JUST NOW BEING
 SUBMITTED ONE DAY BEFORE FINAL??
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT8372

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2000-11-15 Cont ID  
Sent By dpalmer Date 2000-11-15 Time 17:31 Rev Time 0.00
Received By dpalmer Date 2000-11-15 Time 12:58 Sent To  
Notes
2001-01-08 00:00:00****************** PROVISO *************
  
 1)NOTE: PLEASE SHOW MORE DETAIL FOR
 PANELS. MCB ECT.
  
 2)NOTE: PLEASE SEE RISER, PLEASE PROVIDE
 MORE DETAIL ON WIRE SHOWN FEEDING PANEL
 'B'.2" COND W/ 3-????`S. ALSO RISER SHOW
 -S PANEL 'B' FEEDING PANEL 'B'???
 PLEASE CLARIFY.
  
 3)NOTE: PLEASE COMPLETE TOTAL LOAD FOR
 SERVICE ON A-9.
  
 4)NOTE: PLEASE SHOW WHAT THE MEANS OF
 DISCONNECT IS ON CABANA??
  
 5)NOTE: PLEASE SHOW THIRD PANEL.
  
 6)NOTE:
  
  
 7)NOTE: PLEASE LABEL ALL PANELS ON PLANS
 AND FLOOR LAYOUT.
  
  
 8)NOTE: PLEASE SHOW ALL CATV AND TELE-ON
 -PHONE OUTLETS ON FLOOR PLANS.
  
 PLEASE SUBMIT ALL THE ABOVE INFORMAITON
 FOR REVIEW. IF THERE ARE ANY QUESTIONS'
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-11-20 Cont ID  
Sent By jleech Date 2000-11-20 Time 15:22 Rev Time 0.25
Received By jleech Date 2000-11-20 Time 15:22 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-11-20 Cont ID  
Sent By jleech Date 2000-11-20 Time 15:23 Rev Time 0.25
Received By jleech Date 2000-11-20 Time 15:23 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2000-11-20 Cont ID  
Sent By fknapp Date 2000-11-20 Time 15:17 Rev Time 4.00
Received By fknapp Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2000-11-20 Cont ID  
Sent By sgraham Date 2000-11-20 Time 16:07 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***