Plan Review Details - Permit 00100755
Plan Review Stops For Permit 00100755
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2000-12-20 Cont ID  
Sent By jwitmer Date 2000-12-20 Time 13:58 Rev Time 1.00
Received By jwitmer Date   Time   Sent To  
Notes
2001-01-08 00:00:00BUILDING:OK REVISIONS JW

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2000-12-06 Cont ID  
Sent By drunnels Date 2000-12-06 Time 14:29 Rev Time 1.00
Received By drunnels Date 2000-12-06 Time 14:29 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2000-12-05 Cont ID  
Sent By drunnels Date 2000-12-05 Time 08:05 Rev Time 1.00
Received By drunnels Date 2000-12-05 Time 08:05 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2000-11-06 Cont ID  
Sent By drunnels Date 2000-11-06 Time 09:50 Rev Time 1.00
Received By drunnels Date 2000-11-06 Time 09:50 Sent To  
Notes
2001-01-08 00:00:001. SHEET #1: HALL #3 IS 34 FEET IN
 LENGTH, MAXIMUM DEAD END CORRIDOR LENGTH
 IS 20 FEET. TABLE 1004 1997 SBC

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2000-12-29 Cont ID  
Sent By dpalmer Date 2000-12-29 Time 16:43 Rev Time 0.00
Received By dpalmer Date 2000-12-29 Time 16:43 Sent To  
Notes
2001-01-08 00:00:00**************** UNSAT *****************
  
 1)NOTE: PLEASE SEE NOTES,ON ALL PREVIOUS
 REVIEWS. PLEASE SHOW ALL BRANCH CIRCUIT-
 -S ON PLANS AND CORRLATE WITH PANEL
 SCHEDULES.!!!
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.
 659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2000-12-07 Cont ID  
Sent By dpalmer Date 2000-12-07 Time 17:21 Rev Time 0.00
Received By dpalmer Date 2000-12-07 Time 17:21 Sent To  
Notes
2001-01-08 00:00:00************** REVISION REQ`STED *******
  
  
 1)NOTE: NEED TO PROVIDE PLANS SHOWING
 ALL BRANCH CIRCUIT #`S AND CORRELATE
 WITH PANEL SCHEDULES BEFORE FINAL ELEC-
 -TRICAL INSPECTION IS CALLED IN.
  
  
 PLEASE SUBMIT FOR REVIEW BEFORE FINAL.
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2000-11-30 Cont ID  
Sent By dpalmer Date 2000-11-30 Time 17:15 Rev Time 0.00
Received By dpalmer Date 2000-11-30 Time 17:15 Sent To  
Notes
2001-01-08 00:00:00**************** UNSAT ****************
  
 1NOTE: PLEASE SUBMIT PLANS WITH RAISED
 SEAL CLEAR AND VISABLE PER F.A.C.481.221
  
 2)NOTE: PLEASE SUBMIT PLANS TO ADDRESS
 ORIG NOTES FROM PREVIOUS REVIEW. SHOW
 ALL BRANCH CIRCUIT #`S ON PLANS AND
 CORRELATE WITH PANEL SCHEDULES.
  
 3)NOTE: PLEASE SEE POWER PLAN ON FROUNT
 PAGE. THIS LOOKS AS THOUGH ALL OUTLETS
 ARE NEW???
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-11-07 Cont ID  
Sent By dpalmer Date 2000-11-07 Time 20:37 Rev Time 0.00
Received By dpalmer Date 2000-11-07 Time 20:37 Sent To  
Notes
2001-01-08 00:00:00**************** UNSAT ****************
  
 1)NOTE:NOT ENOUGH ELECTRICAL DETAIL FOR
 SUFF REVIEW. PLEASE SEE PANEL SCHEDULES
 PANELS SHOW ALL CIRCUITS AS EXISTING???
 WHERE ARE THE NEW CIRCUITS? IF USING
 EXISTING CIRCUIT #`S THEN PLEASE
 INDICATE. PLEASE SHOW BRANCH CIRUCITS
 ON PLANS THAT CORRELATE WITH PANEL SCHED
 -ULES. PLEASE CLOUD NEW WORK OR CLARIFY.
  
 PLEASE SUBMIT MORE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 659-8096 ETX 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2000-12-21 Cont ID  
Sent By mcarsill Date 2000-12-21 Time 14:42 Rev Time 0.00
Received By mcarsill Date 2000-12-21 Time 14:42 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2000-12-06 Cont ID  
Sent By mcarsill Date 2000-12-06 Time 08:56 Rev Time 0.00
Received By mcarsill Date 2000-12-06 Time 08:56 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2000-11-28 Cont ID  
Sent By mcarsill Date 2000-11-28 Time 14:00 Rev Time 0.00
Received By mcarsill Date 2000-11-28 Time 14:00 Sent To  
Notes
2001-01-08 00:00:001) PLAN REVIEW COMMENTS INDICATE THAT
 NO FIRE SPRINKLERS ARE PRESENT. SINCE
 THERE ARE NO FIRE SPRINKLERS, DEAD-END
 CORRIDORS CANNOT EXCEED 20 FEET. HALL
 # 3 EXCEEDS DEAD-END CORRIDOR ALLOWANCE
 FOR BUSINESS OCCUPANCIES WITHOUT
 FIRE SPRINKLERS.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2000-11-03 Cont ID  
Sent By mcarsill Date 2000-11-03 Time 10:31 Rev Time 0.00
Received By mcarsill Date 2000-11-03 Time 10:31 Sent To  
Notes
2001-01-08 00:00:001) PLEASE PROVIDE A FURNITURE PLAN FOR
 THE DILATING AREA. THIS INFORMATION IS
 REQUIRED TO DETERMINE IF THIS IS AN
 ACCEPTABLE MEANS OF EGRESS.
 2) PLEASE PROVIDE INTERIOR FINISH
 CLASSIFICATIONS FOR TENANT SPACE.
 3) PLANS DO NOT INDICATE IF THE TENANT
 SPACE IS SPRINKLER PROTECTED.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status N Date 2001-01-09 Cont ID  
Sent By ndenmark Date 2001-01-09 Time 13:50 Rev Time 0.25
Received By ndenmark Date 2001-01-09 Time 13:50 Sent To  
Notes
2001-01-09 00:00:00NO MECHANICQL INCLUDED W/ THIS REVISION

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2000-12-04 Cont ID  
Sent By ndenmark Date 2000-12-04 Time 15:08 Rev Time 0.33
Received By ndenmark Date 2000-12-04 Time 15:08 Sent To  
Notes
2001-01-08 00:00:00OK WITH INFORMATION PROVIDED UNDER
 APPLICATION # 00110963
 APPLICATION AND MECH PLANS ATTACHED TO
 BLDG PERMIT APPLICATION. NEEDS BLDG TO
 BE ISSUED PRIOR TO MECH BEING ISSUED

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2000-11-08 Cont ID  
Sent By ndenmark Date 2000-11-08 Time 11:25 Rev Time 0.33
Received By ndenmark Date 2000-11-08 Time 11:25 Sent To  
Notes
2001-01-08 00:00:00**************DENIED********************
 1. INSUFFICIENT INFORMATION PROVIDED FOR
 REVIEW OF NEW AIR CONDITIONING FOR THIS
 SPACE
 PROVIDE PLAN OF NEW DUCT INSTALLATION
 INCLUDING CFM AT DROPS, OUTSIDE AIR
 CALCULATIONS PER ASHRAE 62-89, FOR
 REVIEW

Review Stop P PLUMBING
Rev No 3 Status P Date 2000-12-05 Cont ID  
Sent By jleech Date 2000-12-05 Time 10:11 Rev Time 0.33
Received By jleech Date 2000-12-05 Time 10:10 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2000-11-29 Cont ID  
Sent By jleech Date 2000-11-29 Time 16:04 Rev Time 0.00
Received By jleech Date 2000-11-29 Time 16:18 Sent To  
Notes
2001-01-08 00:00:001.BOTTLED WATER IS NOT A MATERIAL OR
 METHOD. A DRINKING FAUNTAIN IS A
 PLUMBING FIXTURE THAT IS REQUIRED
 BY S.P.C. 407. MINIMUM FACILITIES.
 CUP DISPENSER IS IN COMPLIANCE.
 2.SINK IN LOUNGE SHALL COMPLY WITH
 4.4.2 THRU .7 OF THE 97 FACBC.
 3.WASTE RISER DIAGRAM [REMODEL]. DEAD
 ENDS SHALL BE TERMINATED AT A
 DEVELOPED DISTANCE OF TWO FEET OR LESS
  
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT.8377

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-10-22 Cont ID  
Sent By pschmitz Date 2000-10-22 Time 11:41 Rev Time 2.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-01-08 00:00:00PLUMBING PLAN REVIEW SPC 94
 (1)SHT 1 COMPLY WITH TAB 407 MIN.
 FACILITIES FOR MEN, WOMEN,SEC 407.1.3
 FOR ALLOWABLE AREA DEDUCTION.
 (2) 1 DRINKING FOUNTAIN REQUIRED,
 TAB 407.
 (3) SEC 104.2 DRAWINGS SPECIFICATIONS
 ISOMETRIC OF DWV,WATER PIPING.WITH PIPE
 SIZES,ALSO TYPE OF MATERIAL USED.
 )4) COMPLY WITH FACBC 4.1.3 DETAILS &
 ELEVATIONS OF ALL ADA REQUIRED PLUMBING
 FIXTURES.WITH CLEAR FLOOR SPACE.
 END OF COMMENTS PAUL SCHMITZ
 561-659-8096 X 8233