| Plan Review Stops For Permit 00100755 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2000-12-20 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2000-12-20 |
Time |
13:58 |
Rev Time |
1.00 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | BUILDING:OK REVISIONS JW |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2000-12-06 |
|
|
Cont ID |
|
| Sent By |
drunnels |
Date |
2000-12-06 |
Time |
14:29 |
Rev Time |
1.00 |
| Received By |
drunnels |
Date |
2000-12-06 |
Time |
14:29 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2000-12-05 |
|
|
Cont ID |
|
| Sent By |
drunnels |
Date |
2000-12-05 |
Time |
08:05 |
Rev Time |
1.00 |
| Received By |
drunnels |
Date |
2000-12-05 |
Time |
08:05 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2000-11-06 |
|
|
Cont ID |
|
| Sent By |
drunnels |
Date |
2000-11-06 |
Time |
09:50 |
Rev Time |
1.00 |
| Received By |
drunnels |
Date |
2000-11-06 |
Time |
09:50 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1. SHEET #1: HALL #3 IS 34 FEET IN | | | LENGTH, MAXIMUM DEAD END CORRIDOR LENGTH | | | IS 20 FEET. TABLE 1004 1997 SBC |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
F |
Date |
2000-12-29 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-12-29 |
Time |
16:43 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-12-29 |
Time |
16:43 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | **************** UNSAT ***************** | | | | | | 1)NOTE: PLEASE SEE NOTES,ON ALL PREVIOUS | | | REVIEWS. PLEASE SHOW ALL BRANCH CIRCUIT- | | | -S ON PLANS AND CORRLATE WITH PANEL | | | SCHEDULES.!!! | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW. | | | 659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2000-12-07 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-12-07 |
Time |
17:21 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-12-07 |
Time |
17:21 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ************** REVISION REQ`STED ******* | | | | | | | | | 1)NOTE: NEED TO PROVIDE PLANS SHOWING | | | ALL BRANCH CIRCUIT #`S AND CORRELATE | | | WITH PANEL SCHEDULES BEFORE FINAL ELEC- | | | -TRICAL INSPECTION IS CALLED IN. | | | | | | | | | PLEASE SUBMIT FOR REVIEW BEFORE FINAL. | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2000-11-30 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-11-30 |
Time |
17:15 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-11-30 |
Time |
17:15 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | **************** UNSAT **************** | | | | | | 1NOTE: PLEASE SUBMIT PLANS WITH RAISED | | | SEAL CLEAR AND VISABLE PER F.A.C.481.221 | | | | | | 2)NOTE: PLEASE SUBMIT PLANS TO ADDRESS | | | ORIG NOTES FROM PREVIOUS REVIEW. SHOW | | | ALL BRANCH CIRCUIT #`S ON PLANS AND | | | CORRELATE WITH PANEL SCHEDULES. | | | | | | 3)NOTE: PLEASE SEE POWER PLAN ON FROUNT | | | PAGE. THIS LOOKS AS THOUGH ALL OUTLETS | | | ARE NEW??? | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2000-11-07 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-11-07 |
Time |
20:37 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-11-07 |
Time |
20:37 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | **************** UNSAT **************** | | | | | | 1)NOTE:NOT ENOUGH ELECTRICAL DETAIL FOR | | | SUFF REVIEW. PLEASE SEE PANEL SCHEDULES | | | PANELS SHOW ALL CIRCUITS AS EXISTING??? | | | WHERE ARE THE NEW CIRCUITS? IF USING | | | EXISTING CIRCUIT #`S THEN PLEASE | | | INDICATE. PLEASE SHOW BRANCH CIRUCITS | | | ON PLANS THAT CORRELATE WITH PANEL SCHED | | | -ULES. PLEASE CLOUD NEW WORK OR CLARIFY. | | | | | | PLEASE SUBMIT MORE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 659-8096 ETX 8372 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
P |
Date |
2000-12-21 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-12-21 |
Time |
14:42 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2000-12-21 |
Time |
14:42 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2000-12-06 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-12-06 |
Time |
08:56 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2000-12-06 |
Time |
08:56 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2000-11-28 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-11-28 |
Time |
14:00 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2000-11-28 |
Time |
14:00 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1) PLAN REVIEW COMMENTS INDICATE THAT | | | NO FIRE SPRINKLERS ARE PRESENT. SINCE | | | THERE ARE NO FIRE SPRINKLERS, DEAD-END | | | CORRIDORS CANNOT EXCEED 20 FEET. HALL | | | # 3 EXCEEDS DEAD-END CORRIDOR ALLOWANCE | | | FOR BUSINESS OCCUPANCIES WITHOUT | | | FIRE SPRINKLERS. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2000-11-03 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-11-03 |
Time |
10:31 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2000-11-03 |
Time |
10:31 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1) PLEASE PROVIDE A FURNITURE PLAN FOR | | | THE DILATING AREA. THIS INFORMATION IS | | | REQUIRED TO DETERMINE IF THIS IS AN | | | ACCEPTABLE MEANS OF EGRESS. | | | 2) PLEASE PROVIDE INTERIOR FINISH | | | CLASSIFICATIONS FOR TENANT SPACE. | | | 3) PLANS DO NOT INDICATE IF THE TENANT | | | SPACE IS SPRINKLER PROTECTED. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
N |
Date |
2001-01-09 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2001-01-09 |
Time |
13:50 |
Rev Time |
0.25 |
| Received By |
ndenmark |
Date |
2001-01-09 |
Time |
13:50 |
Sent To |
|
|
| Notes |
| 2001-01-09 00:00:00 | NO MECHANICQL INCLUDED W/ THIS REVISION |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2000-12-04 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-12-04 |
Time |
15:08 |
Rev Time |
0.33 |
| Received By |
ndenmark |
Date |
2000-12-04 |
Time |
15:08 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | OK WITH INFORMATION PROVIDED UNDER | | | APPLICATION # 00110963 | | | APPLICATION AND MECH PLANS ATTACHED TO | | | BLDG PERMIT APPLICATION. NEEDS BLDG TO | | | BE ISSUED PRIOR TO MECH BEING ISSUED |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2000-11-08 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-11-08 |
Time |
11:25 |
Rev Time |
0.33 |
| Received By |
ndenmark |
Date |
2000-11-08 |
Time |
11:25 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | **************DENIED******************** | | | 1. INSUFFICIENT INFORMATION PROVIDED FOR | | | REVIEW OF NEW AIR CONDITIONING FOR THIS | | | SPACE | | | PROVIDE PLAN OF NEW DUCT INSTALLATION | | | INCLUDING CFM AT DROPS, OUTSIDE AIR | | | CALCULATIONS PER ASHRAE 62-89, FOR | | | REVIEW |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2000-12-05 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2000-12-05 |
Time |
10:11 |
Rev Time |
0.33 |
| Received By |
jleech |
Date |
2000-12-05 |
Time |
10:10 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2000-11-29 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2000-11-29 |
Time |
16:04 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2000-11-29 |
Time |
16:18 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1.BOTTLED WATER IS NOT A MATERIAL OR | | | METHOD. A DRINKING FAUNTAIN IS A | | | PLUMBING FIXTURE THAT IS REQUIRED | | | BY S.P.C. 407. MINIMUM FACILITIES. | | | CUP DISPENSER IS IN COMPLIANCE. | | | 2.SINK IN LOUNGE SHALL COMPLY WITH | | | 4.4.2 THRU .7 OF THE 97 FACBC. | | | 3.WASTE RISER DIAGRAM [REMODEL]. DEAD | | | ENDS SHALL BE TERMINATED AT A | | | DEVELOPED DISTANCE OF TWO FEET OR LESS | | | | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 659-8096 EXT.8377 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2000-10-22 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2000-10-22 |
Time |
11:41 |
Rev Time |
2.00 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PLUMBING PLAN REVIEW SPC 94 | | | (1)SHT 1 COMPLY WITH TAB 407 MIN. | | | FACILITIES FOR MEN, WOMEN,SEC 407.1.3 | | | FOR ALLOWABLE AREA DEDUCTION. | | | (2) 1 DRINKING FOUNTAIN REQUIRED, | | | TAB 407. | | | (3) SEC 104.2 DRAWINGS SPECIFICATIONS | | | ISOMETRIC OF DWV,WATER PIPING.WITH PIPE | | | SIZES,ALSO TYPE OF MATERIAL USED. | | | )4) COMPLY WITH FACBC 4.1.3 DETAILS & | | | ELEVATIONS OF ALL ADA REQUIRED PLUMBING | | | FIXTURES.WITH CLEAR FLOOR SPACE. | | | END OF COMMENTS PAUL SCHMITZ | | | 561-659-8096 X 8233 |
|
|