Plan Review Details - Permit 00100742
Plan Review Stops For Permit 00100742
Review Stop P PLUMBING
Rev No 2 Status P Date 2000-10-25 Cont ID  
Sent By tlarge Date 2000-10-25 Time 09:21 Rev Time 0.65
Received By tlarge Date 2000-10-25 Time 09:21 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-10-20 Cont ID  
Sent By tlarge Date 2000-10-20 Time 05:13 Rev Time 0.33
Received By tlarge Date 2000-10-20 Time 05:13 Sent To  
Notes
2001-01-08 00:00:001)SIZE SUPPLY LINE AT METER.COMPLY W/
 SGC TABLE 305.4(A).
  
 2)RECALCULATE YOUR BTU LOAD.PLANS NOTE
 389,000 BTU'S.I CALCULATE 455.SGC SEC.
 302.
  
 3)SUBMIT LEGIBLE COPIES OF THE
 APPROPRIATE SIZING TABLES.SGC SEC.302.
  
 CALL IF YOU HAVE QUESTIONS.
 561-659-8096,EXT.8377.
  
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.