| Plan Review Stops For Permit 00100685 |
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2000-10-20 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-10-20 |
Time |
16:06 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2000-10-20 |
Time |
16:03 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1) SEPARATE PLANS AND PERMITS REQUIRED | | | FOR HOOD SUPPRESSION SYSTEM. | | | 2) PLEASE PROVIDE DATA FOR 3M FIREMASTER | | | BLANKET PLANNED FOR USE. | | | APPROVED PROVISO: | | | | | | PLANS REVIEWED BY CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2000-10-21 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-10-21 |
Time |
13:24 |
Rev Time |
0.33 |
| Received By |
ndenmark |
Date |
2000-10-21 |
Time |
13:24 |
Sent To |
|
|
| Notes |