Plan Review Details - Permit 00100684
Plan Review Stops For Permit 00100684
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2001-07-09 Cont ID  
Sent By jwitmer Date 2001-07-09 Time 15:41 Rev Time 0.55
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2001-05-09 Cont ID  
Sent By jwitmer Date 2001-05-09 Time 17:25 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2001-05-09 Cont ID  
Sent By jwitmer Date 2001-05-09 Time 07:16 Rev Time 0.00
Received By jwitmer Date 2001-05-09 Time 07:21 Sent To  
Notes
2001-05-09 00:00:001) REQUIRE METAL STUD FRAMING DETAIL
 WITH ATTACHMENT REQUIREMENTS, ARCHITECT
 QUOTED TABLE 1705.1 & THERE IS NO SUCH
 TABLE.
 2) ARCHITECT NOR THE CONTRACTOR HAS
 ADDRESSED THE ISSUE OF STORM SHUTTERS,
 THIS CAN BE "PROVISOED" PLANS ANDPRODUCT
 APPROVAL CAN BE BY SEPERATE PERMIT WITH
 ADDITIONAL FEES.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2001-04-26 Cont ID  
Sent By jwitmer Date 2001-04-26 Time 07:19 Rev Time 0.50
Received By jwitmer Date   Time   Sent To  
Notes
2001-04-26 00:00:00SEE ORIGINAL COMMENTS

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2001-03-30 Cont ID  
Sent By jwitmer Date 2001-03-30 Time 10:10 Rev Time 0.00
Received By jwitmer Date 2001-04-26 Time 07:10 Sent To  
Notes
2001-03-30 00:00:00BUILDING PLAN REVIEW
 PERMIT# 00100684
 460 S ROSEMARY AV # 184
 CONT: ? L. DAVIS OR SCHIAPPA
  
 1)- DETERMINE WHO IS GOING TO BE THE
 CONTRACTOR OF RECORD, IF SCHIAPPA CONST
 IS TO BE THE CONTRACTOR OF RECORD, THEY
 ARE REQUIRED TO RECEIVE A NOTIRIZED
 LETTER FROM L. DAVIS CO. INC., THE
 QUALIFIER OF THE COMPANY IS TRANSFERRING
 PERMIT, PLANS & FEES. THERE IS A $100.00
 TRANSFER FEE. SCHIAPPA CONSTRUCTION IS
 TO FINISH FILLING OUT THEIR APPLICATION.
  
 2)- STOREFRONT ASSEMBLY: SBC 1606.4/
 1707.4.1: REQUIRE TESTING FOR WIND AS
 WELL AS LARGE MISSLE IMPACT RESISTANT
 TESTING.
 A)- SBC 1707.4 (WIND) A 10 SECOND TEST
 WITH THE LOAD EQUAL TO 1.5 THE DESIGN
 LOAD.
 B)- SBC 1606.4.1 AMEND. IMPACT FROM
 WINDBORN DEBRIS: GLAZED UNITS REQUIRE
 APPROVED TESTING FOR LARGE MISSLE IMPACT
 RESISTANCE OR STORM SHUTTERS WITH
 APPROVAL FROM SBCCI OR DADE COUNTY PRO-
 DUCT APPROVAL.
  
 3)- SBC 104.2.2:ADDITIONAL INFORMATION
 REQUIRED: SHEET A-4 DETAIL "A" NOTES
 MMETAL STUD FRAMING SEE DETAIL 2, THIS
 SHEET? NO DETAIL! REQUIREMENTS FOR FAST-
 ENING THE TOP TRACK TO THE STRUCTURE
 ABOVE, STUD SPACING, SPAN, ETC?
  
 4)- SHEET A-5 CLARIFY THAT THE GLASS
 SHELVING DETAIL SEC."C" WILL NOT BE LET
 INTO THE TENANT SEPERATION WALL.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659 -8096 EX 8412

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2000-10-25 Cont ID  
Sent By drunnels Date 2000-10-25 Time 10:49 Rev Time 1.00
Received By drunnels Date 2000-10-25 Time 10:40 Sent To  
Notes
2001-01-08 00:00:001.SUBMIT PRODUCT APPROVAL FOR IMPACT
 RESISTANCE GLAZING FOR STOREFTONT WINDOW
 AND DOORS / METRO DADE COUNTY OR SBCCI
 2. SUBMIT FIRE SPRINKLER PLANS AND
 PERMIT APPLICATION
 3. SUBMIT LETTER FROM SPECIAL INSPECTOR
 FOR CITY PLACE
 4. PLANS MUCT BE APPROVED AND SPAMPED
 BY CITY PLACE
 5. SUBMIT FLORIDA ENERGY CALCULATION
 SHEETS
 6. SIGNS TO BE PERMITED SEPERATLY

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2001-10-22 Cont ID  
Sent By dpalmer Date 2001-10-22 Time 19:12 Rev Time 0.00
Received By dpalmer Date 2001-10-22 Time 19:12 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2001-04-19 Cont ID  
Sent By dpalmer Date 2001-04-19 Time 21:32 Rev Time 0.00
Received By dpalmer Date 2001-04-19 Time 21:32 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-03-29 Cont ID  
Sent By dpalmer Date 2001-03-29 Time 21:18 Rev Time 0.00
Received By dpalmer Date 2001-03-29 Time 21:18 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-11-01 Cont ID  
Sent By dpalmer Date 2000-11-01 Time 17:10 Rev Time 0.00
Received By dpalmer Date 2000-11-01 Time 17:10 Sent To  
Notes
2001-01-08 00:00:00******************* UNSAT **************
  
 1)NOTE: PLEASE SEE 220-12B FOR LOAD
 CALCULATIONS FOR TRACK LIGHTING. PLEASE
 SHOW LENGTHS ETC.
  
 2)NOTE: PLEASE SHOW ALL CONTINUOUS LOADS
 AT 125% (LIGHTING)
  
 3)NOTE: AIC RATINGS FOR MAIN AND PANEL
 IS BEING SHOWN, BUT PLEASE SUBMIT AIC
 RATINGS FOR ALL EQUIPMENT INCLUDING
 3P60A AND 3P100A DISCONNECTS ON THE
 LINE AND LOAD SIDE OF TRANSFORMERS.
 110-9 AND 215-5
  
 PLEASE SUBMIT THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2001-05-09 Cont ID  
Sent By jwitmer Date 2001-05-09 Time 17:24 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2001-05-09 00:00:00PASSED PER MIKE CARSELLO 5/9/01 SEE APP.

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status F Date 2001-05-04 Cont ID  
Sent By mcarsill Date 2001-05-04 Time 11:33 Rev Time 0.00
Received By jwitmer Date 2001-05-04 Time 11:33 Sent To  
Notes
2001-05-04 00:00:001) STILL NO FIRE SPRINKLER DRAWINGS
 PROVIDED WITH PLANS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2001-04-18 Cont ID  
Sent By mcarsill Date 2001-04-18 Time 13:14 Rev Time 0.00
Received By mcarsill Date 2001-04-18 Time 13:14 Sent To  
Notes
2001-04-18 00:00:001) STILL NO FIRE SPRINKLER DRAWINGS
 INCLUDED WITH PLANS.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2001-03-27 Cont ID  
Sent By mcarsill Date 2001-03-27 Time 11:08 Rev Time 0.00
Received By mcarsill Date 2001-03-27 Time 11:08 Sent To  
Notes
2001-03-27 00:00:001) NO FIRE SPRINKLER DRAWINGS PROVIDED
 WITH PLANS.
 2) NO INTERIOR FINISH CLASSIFICATIONS
 NOTED ON PLANS.
 3) PULL STATIONS ARE NOT REQUIRED IN
 TENANT SPACE. SEPARATE PLANS AND PERMITS
 REQUIRED FOR FIRE ALARM EQUIPMENT.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2000-10-18 Cont ID  
Sent By mcarsill Date 2000-10-18 Time 15:20 Rev Time 0.00
Received By mcarsill Date 2000-10-18 Time 15:20 Sent To  
Notes
2001-01-08 00:00:001) NO FIRE SPRINKLER DRAWINGS OR
 HYDRAULIC CALCULATIONS PROVIDED WITH
 PLANS.
 2) NO INTERIOR FINISH CLASSIFICATIONS
 PROVIDED WITH PLANS.
 3) NO FIRE ALARM EQUIPMENT SHOWN ON
 PLANS WITHIN TENANT SPACE.
 4) EMERGENCY LIGHT FIXTURES IN THE
 MEANS OF EGRESS NOT CLEARLY SHOWN.
 5) NO CITY PLACE STAMP PRESENT ON PLANS.
  
 PLANS REVIEWED BY CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2001-06-21 Cont ID  
Sent By pkrauss Date 2001-06-21 Time 15:06 Rev Time 0.35
Received By pkrauss Date 2001-06-21 Time 15:06 Sent To  
Notes
2001-06-21 00:00:00REVISION MECH PERMIT 01060020.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2001-04-26 Cont ID  
Sent By pkrauss Date 2001-04-26 Time 09:27 Rev Time 0.35
Received By pkrauss Date 2001-04-26 Time 09:20 Sent To  
Notes
2001-04-26 00:00:00MECHANICAL PERMIT REQUIRED.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-03-27 Cont ID  
Sent By pkrauss Date 2001-03-27 Time 13:35 Rev Time 0.40
Received By pkrauss Date 2001-03-27 Time 13:22 Sent To  
Notes
2001-03-27 00:00:00RESUBMITTAL - SUBMITTED O.A.
 CALCULATION AND ACCESS FOR AHU. ALSO
 CONDENSATE TO BE RUN BY LANDLORD.
  
 NOTE ON PRINT AS TO LOCATION OF C.U.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2000-11-07 Cont ID  
Sent By ndenmark Date 2000-11-07 Time 13:08 Rev Time 0.33
Received By ndenmark Date 2000-11-07 Time 13:08 Sent To  
Notes
2001-01-08 00:00:00*************DENIED*********************
 1. PROVIDE OUTSIDE AIR CALCULATIONS
 SHOWING COMPLIANCE W/ ASHRAE 62-89
 2. ACCESS TO AIR HANDLER SHALL COMPLY
 WITH 1997 SMC 304.4ACCESS TO BE AT
 LEAST AS LARGE AS THE LARGEST PIECE OF
 EQUIPMENT AND IN NO CASE LESS THAN 22X36
 INCHES. A LEVEL WORKING PLATFORM SHALL
 BE PROVIDED ON THE CONTROL SIDE AND ANY
 OTHER SIDE REQUIRED FOR SERVICE.
 3. PLUMBING PLAN DOES NOT INDICATE THE
 LOCATION OF THE CONDENSATE DRAIN TERMIN-
 ATION OR THE LOCATION OF THE OVERFLOW
 DRAIN LINE TERMINATION POINT. PLEASE
 SPECIFY FOR CLARITY. NOTE: LOCAL WATER
 AUTHORITY DOES NOT PERMIT CONDENSATE TO
 GO TO SANITARY SEWER. CHECK WITH LAND-
 LORD FOR LOCATION OF BUILDING CONDENSATE
 RISER AND PROVIDE CONSPICUOUS LOCATION
 FOR OVERFLOW DRAIN LINE TO TERMINATE.

Review Stop P PLUMBING
Rev No 3 Status P Date 2001-04-26 Cont ID  
Sent By kstevens Date 2001-04-26 Time 12:40 Rev Time 0.33
Received By kstevens Date 2001-04-26 Time 12:40 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2001-03-31 Cont ID  
Sent By pschmitz Date 2001-03-31 Time 11:25 Rev Time 2.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-03-31 00:00:00PLUMBING PLAN REVIEW DENIED 2ND TIME
 (1) SHT A-1 REST/RM FACILITIES TO BE
 DIRECTLY ACCESSIBLE TO PUBLIC FROM AREAS
 THEY ARE INTENDED TO SERVE SPC 94
 SEC 407.2.2
 (2) 1 DRINKING FOUNTAIN REQ. TAB 407, TO
 COMPLY W/FACBC-97,4.1.3(10)(A) CLEAR FLR
 SPACE, CUP DISPENSER.
 (3) SHT M-1 WATER RISER,SHOW PIPE SIZES,
 AIR CHAMBERS TO COMPLY W/ SEC 607.8.3
 ACCESSIBLE AND RECHARGEABLE.
 END OF COMMENTS PAUL SCHMITZ
 QUESTIONS561-659-8096X8233

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-10-21 Cont ID  
Sent By tlarge Date 2000-10-21 Time 13:09 Rev Time 0.65
Received By pschmitz Date 2000-10-21 Time 13:09 Sent To  
Notes
2001-01-08 00:00:001)TWO TOILET ROOMS ARE REQD.PER SPC
 TABLE 407.SEE SPC SEC.407.1.3. FOR
 ALLOWED DEDUCTIBLE AREAS.BOTH TOILET
 ROOMS SHALL BE FULLY HANDICAP ACCESSIBLE
  
 2)A DRINKING FOUNTAIN IS REQD.PER TABLE
 407 OF SPC.PROVISIONS SHALL BE MADE FOR
 PEOPLE WHO HAVE TROUBLE BENDING OR
 STOOPING.
  
 3)FLOORS AND WALLS IN TOILET ROOMS SHALL
 BE NONABSORBENT TO A HEIGHT OF 4'PER
 SBC SEC.1204.2.
  
 4)A FLOOR DRAIN IS REQD.IN THE ADD'L.
 TOILET ROOM PER SPC SEC.409.4.1.1.
  
 5)PLANS REQUIRE CITY PLACE APPROVAL
 STAMO.
  
 6)SHT.A-5-GRAB BAR ALONGSIDE WATER
 CLOSET SHALL BE A MIN.OF 42"PER FACBC
 SEC.4.26 AND FIG.29.
  
 7)SIZE THE WATER RISER AND THE VENT.
  
 CALL IF YOU HAVE QUESTIONS.
 561-659-8096,EXT.8377.
  
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.