| Plan Review Stops For Permit 00100684 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
6 |
Status |
P |
Date |
2001-07-09 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-07-09 |
Time |
15:41 |
Rev Time |
0.55 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2001-05-09 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-05-09 |
Time |
17:25 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2001-05-09 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-05-09 |
Time |
07:16 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2001-05-09 |
Time |
07:21 |
Sent To |
|
|
| Notes |
| 2001-05-09 00:00:00 | 1) REQUIRE METAL STUD FRAMING DETAIL | | | WITH ATTACHMENT REQUIREMENTS, ARCHITECT | | | QUOTED TABLE 1705.1 & THERE IS NO SUCH | | | TABLE. | | | 2) ARCHITECT NOR THE CONTRACTOR HAS | | | ADDRESSED THE ISSUE OF STORM SHUTTERS, | | | THIS CAN BE "PROVISOED" PLANS ANDPRODUCT | | | APPROVAL CAN BE BY SEPERATE PERMIT WITH | | | ADDITIONAL FEES. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2001-04-26 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-04-26 |
Time |
07:19 |
Rev Time |
0.50 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-04-26 00:00:00 | SEE ORIGINAL COMMENTS |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2001-03-30 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-03-30 |
Time |
10:10 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2001-04-26 |
Time |
07:10 |
Sent To |
|
|
| Notes |
| 2001-03-30 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT# 00100684 | | | 460 S ROSEMARY AV # 184 | | | CONT: ? L. DAVIS OR SCHIAPPA | | | | | | 1)- DETERMINE WHO IS GOING TO BE THE | | | CONTRACTOR OF RECORD, IF SCHIAPPA CONST | | | IS TO BE THE CONTRACTOR OF RECORD, THEY | | | ARE REQUIRED TO RECEIVE A NOTIRIZED | | | LETTER FROM L. DAVIS CO. INC., THE | | | QUALIFIER OF THE COMPANY IS TRANSFERRING | | | PERMIT, PLANS & FEES. THERE IS A $100.00 | | | TRANSFER FEE. SCHIAPPA CONSTRUCTION IS | | | TO FINISH FILLING OUT THEIR APPLICATION. | | | | | | 2)- STOREFRONT ASSEMBLY: SBC 1606.4/ | | | 1707.4.1: REQUIRE TESTING FOR WIND AS | | | WELL AS LARGE MISSLE IMPACT RESISTANT | | | TESTING. | | | A)- SBC 1707.4 (WIND) A 10 SECOND TEST | | | WITH THE LOAD EQUAL TO 1.5 THE DESIGN | | | LOAD. | | | B)- SBC 1606.4.1 AMEND. IMPACT FROM | | | WINDBORN DEBRIS: GLAZED UNITS REQUIRE | | | APPROVED TESTING FOR LARGE MISSLE IMPACT | | | RESISTANCE OR STORM SHUTTERS WITH | | | APPROVAL FROM SBCCI OR DADE COUNTY PRO- | | | DUCT APPROVAL. | | | | | | 3)- SBC 104.2.2:ADDITIONAL INFORMATION | | | REQUIRED: SHEET A-4 DETAIL "A" NOTES | | | MMETAL STUD FRAMING SEE DETAIL 2, THIS | | | SHEET? NO DETAIL! REQUIREMENTS FOR FAST- | | | ENING THE TOP TRACK TO THE STRUCTURE | | | ABOVE, STUD SPACING, SPAN, ETC? | | | | | | 4)- SHEET A-5 CLARIFY THAT THE GLASS | | | SHELVING DETAIL SEC."C" WILL NOT BE LET | | | INTO THE TENANT SEPERATION WALL. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | (561) 659 -8096 EX 8412 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2000-10-25 |
|
|
Cont ID |
|
| Sent By |
drunnels |
Date |
2000-10-25 |
Time |
10:49 |
Rev Time |
1.00 |
| Received By |
drunnels |
Date |
2000-10-25 |
Time |
10:40 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1.SUBMIT PRODUCT APPROVAL FOR IMPACT | | | RESISTANCE GLAZING FOR STOREFTONT WINDOW | | | AND DOORS / METRO DADE COUNTY OR SBCCI | | | 2. SUBMIT FIRE SPRINKLER PLANS AND | | | PERMIT APPLICATION | | | 3. SUBMIT LETTER FROM SPECIAL INSPECTOR | | | FOR CITY PLACE | | | 4. PLANS MUCT BE APPROVED AND SPAMPED | | | BY CITY PLACE | | | 5. SUBMIT FLORIDA ENERGY CALCULATION | | | SHEETS | | | 6. SIGNS TO BE PERMITED SEPERATLY |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2001-10-22 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-10-22 |
Time |
19:12 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-10-22 |
Time |
19:12 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2001-04-19 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-04-19 |
Time |
21:32 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-04-19 |
Time |
21:32 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2001-03-29 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-03-29 |
Time |
21:18 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-03-29 |
Time |
21:18 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2000-11-01 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-11-01 |
Time |
17:10 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-11-01 |
Time |
17:10 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ******************* UNSAT ************** | | | | | | 1)NOTE: PLEASE SEE 220-12B FOR LOAD | | | CALCULATIONS FOR TRACK LIGHTING. PLEASE | | | SHOW LENGTHS ETC. | | | | | | 2)NOTE: PLEASE SHOW ALL CONTINUOUS LOADS | | | AT 125% (LIGHTING) | | | | | | 3)NOTE: AIC RATINGS FOR MAIN AND PANEL | | | IS BEING SHOWN, BUT PLEASE SUBMIT AIC | | | RATINGS FOR ALL EQUIPMENT INCLUDING | | | 3P60A AND 3P100A DISCONNECTS ON THE | | | LINE AND LOAD SIDE OF TRANSFORMERS. | | | 110-9 AND 215-5 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION | | | FOR REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 659-8096 EXT 8372 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
5 |
Status |
P |
Date |
2001-05-09 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-05-09 |
Time |
17:24 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-05-09 00:00:00 | PASSED PER MIKE CARSELLO 5/9/01 SEE APP. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
F |
Date |
2001-05-04 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-05-04 |
Time |
11:33 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2001-05-04 |
Time |
11:33 |
Sent To |
|
|
| Notes |
| 2001-05-04 00:00:00 | 1) STILL NO FIRE SPRINKLER DRAWINGS | | | PROVIDED WITH PLANS. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
F |
Date |
2001-04-18 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-04-18 |
Time |
13:14 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-04-18 |
Time |
13:14 |
Sent To |
|
|
| Notes |
| 2001-04-18 00:00:00 | 1) STILL NO FIRE SPRINKLER DRAWINGS | | | INCLUDED WITH PLANS. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2001-03-27 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-03-27 |
Time |
11:08 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-03-27 |
Time |
11:08 |
Sent To |
|
|
| Notes |
| 2001-03-27 00:00:00 | 1) NO FIRE SPRINKLER DRAWINGS PROVIDED | | | WITH PLANS. | | | 2) NO INTERIOR FINISH CLASSIFICATIONS | | | NOTED ON PLANS. | | | 3) PULL STATIONS ARE NOT REQUIRED IN | | | TENANT SPACE. SEPARATE PLANS AND PERMITS | | | REQUIRED FOR FIRE ALARM EQUIPMENT. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2000-10-18 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-10-18 |
Time |
15:20 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2000-10-18 |
Time |
15:20 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1) NO FIRE SPRINKLER DRAWINGS OR | | | HYDRAULIC CALCULATIONS PROVIDED WITH | | | PLANS. | | | 2) NO INTERIOR FINISH CLASSIFICATIONS | | | PROVIDED WITH PLANS. | | | 3) NO FIRE ALARM EQUIPMENT SHOWN ON | | | PLANS WITHIN TENANT SPACE. | | | 4) EMERGENCY LIGHT FIXTURES IN THE | | | MEANS OF EGRESS NOT CLEARLY SHOWN. | | | 5) NO CITY PLACE STAMP PRESENT ON PLANS. | | | | | | PLANS REVIEWED BY CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2001-06-21 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-06-21 |
Time |
15:06 |
Rev Time |
0.35 |
| Received By |
pkrauss |
Date |
2001-06-21 |
Time |
15:06 |
Sent To |
|
|
| Notes |
| 2001-06-21 00:00:00 | REVISION MECH PERMIT 01060020. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2001-04-26 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-04-26 |
Time |
09:27 |
Rev Time |
0.35 |
| Received By |
pkrauss |
Date |
2001-04-26 |
Time |
09:20 |
Sent To |
|
|
| Notes |
| 2001-04-26 00:00:00 | MECHANICAL PERMIT REQUIRED. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2001-03-27 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-03-27 |
Time |
13:35 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2001-03-27 |
Time |
13:22 |
Sent To |
|
|
| Notes |
| 2001-03-27 00:00:00 | RESUBMITTAL - SUBMITTED O.A. | | | CALCULATION AND ACCESS FOR AHU. ALSO | | | CONDENSATE TO BE RUN BY LANDLORD. | | | | | | NOTE ON PRINT AS TO LOCATION OF C.U. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2000-11-07 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-11-07 |
Time |
13:08 |
Rev Time |
0.33 |
| Received By |
ndenmark |
Date |
2000-11-07 |
Time |
13:08 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | *************DENIED********************* | | | 1. PROVIDE OUTSIDE AIR CALCULATIONS | | | SHOWING COMPLIANCE W/ ASHRAE 62-89 | | | 2. ACCESS TO AIR HANDLER SHALL COMPLY | | | WITH 1997 SMC 304.4ACCESS TO BE AT | | | LEAST AS LARGE AS THE LARGEST PIECE OF | | | EQUIPMENT AND IN NO CASE LESS THAN 22X36 | | | INCHES. A LEVEL WORKING PLATFORM SHALL | | | BE PROVIDED ON THE CONTROL SIDE AND ANY | | | OTHER SIDE REQUIRED FOR SERVICE. | | | 3. PLUMBING PLAN DOES NOT INDICATE THE | | | LOCATION OF THE CONDENSATE DRAIN TERMIN- | | | ATION OR THE LOCATION OF THE OVERFLOW | | | DRAIN LINE TERMINATION POINT. PLEASE | | | SPECIFY FOR CLARITY. NOTE: LOCAL WATER | | | AUTHORITY DOES NOT PERMIT CONDENSATE TO | | | GO TO SANITARY SEWER. CHECK WITH LAND- | | | LORD FOR LOCATION OF BUILDING CONDENSATE | | | RISER AND PROVIDE CONSPICUOUS LOCATION | | | FOR OVERFLOW DRAIN LINE TO TERMINATE. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2001-04-26 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-04-26 |
Time |
12:40 |
Rev Time |
0.33 |
| Received By |
kstevens |
Date |
2001-04-26 |
Time |
12:40 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2001-03-31 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2001-03-31 |
Time |
11:25 |
Rev Time |
2.00 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-03-31 00:00:00 | PLUMBING PLAN REVIEW DENIED 2ND TIME | | | (1) SHT A-1 REST/RM FACILITIES TO BE | | | DIRECTLY ACCESSIBLE TO PUBLIC FROM AREAS | | | THEY ARE INTENDED TO SERVE SPC 94 | | | SEC 407.2.2 | | | (2) 1 DRINKING FOUNTAIN REQ. TAB 407, TO | | | COMPLY W/FACBC-97,4.1.3(10)(A) CLEAR FLR | | | SPACE, CUP DISPENSER. | | | (3) SHT M-1 WATER RISER,SHOW PIPE SIZES, | | | AIR CHAMBERS TO COMPLY W/ SEC 607.8.3 | | | ACCESSIBLE AND RECHARGEABLE. | | | END OF COMMENTS PAUL SCHMITZ | | | QUESTIONS561-659-8096X8233 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2000-10-21 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-10-21 |
Time |
13:09 |
Rev Time |
0.65 |
| Received By |
pschmitz |
Date |
2000-10-21 |
Time |
13:09 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1)TWO TOILET ROOMS ARE REQD.PER SPC | | | TABLE 407.SEE SPC SEC.407.1.3. FOR | | | ALLOWED DEDUCTIBLE AREAS.BOTH TOILET | | | ROOMS SHALL BE FULLY HANDICAP ACCESSIBLE | | | | | | 2)A DRINKING FOUNTAIN IS REQD.PER TABLE | | | 407 OF SPC.PROVISIONS SHALL BE MADE FOR | | | PEOPLE WHO HAVE TROUBLE BENDING OR | | | STOOPING. | | | | | | 3)FLOORS AND WALLS IN TOILET ROOMS SHALL | | | BE NONABSORBENT TO A HEIGHT OF 4'PER | | | SBC SEC.1204.2. | | | | | | 4)A FLOOR DRAIN IS REQD.IN THE ADD'L. | | | TOILET ROOM PER SPC SEC.409.4.1.1. | | | | | | 5)PLANS REQUIRE CITY PLACE APPROVAL | | | STAMO. | | | | | | 6)SHT.A-5-GRAB BAR ALONGSIDE WATER | | | CLOSET SHALL BE A MIN.OF 42"PER FACBC | | | SEC.4.26 AND FIG.29. | | | | | | 7)SIZE THE WATER RISER AND THE VENT. | | | | | | CALL IF YOU HAVE QUESTIONS. | | | 561-659-8096,EXT.8377. | | | | | | TIMOTHY LARGE | | | PLUMBING PLANS EXAMINER. |
|
|