Plan Review Details - Permit 00100638
Plan Review Stops For Permit 00100638
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-12-07 Cont ID  
Sent By dpalmer Date 2000-12-07 Time 20:30 Rev Time 0.00
Received By dpalmer Date 2000-12-07 Time 20:30 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-11-02 Cont ID  
Sent By dpalmer Date 2000-11-02 Time 20:45 Rev Time 0.00
Received By dpalmer Date 2000-11-02 Time 20:45 Sent To  
Notes
2001-01-08 00:00:00**************** UNSAT ****************
  
 1)NOTE: PLEASE SUBMIT AIC RATING FOR ALL
 EQUIPMENT BEING INSTALLED. MAINS/PANEL
 MUST BE RATED FOR THE AVAILABLE FAULT
 CURRENT PER 110-9 AND 215-5.
 PLEASE SHOW ELECTRICAL DETAIL FOR PANELS
 ON PANEL SCHEDULES. MLO? VOLTAGE? ETC
 PLANS SHOW ONE DISCONNECT AND ONE PANEL
 AND RISER SHOWS TWO OF EACH??? PLEASE
 SHOW ON PLANS AND/OR CORRELATE RISER W/
 PLANS.
  
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-10-30 Cont ID  
Sent By jleech Date 2000-10-30 Time 19:30 Rev Time 0.33
Received By jleech Date 2000-10-30 Time 19:30 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2001-05-31 Cont ID  
Sent By kstevens Date 2001-05-31 Time 14:19 Rev Time 0.33
Received By kstevens Date 2001-05-31 Time 14:18 Sent To  
Notes
2001-05-31 00:00:00REVIEW NOTES:
  
 REVISION OF SANITARY RISER DIAGRAM.

Review Stop P PLUMBING
Rev No 2 Status P Date 2000-11-30 Cont ID  
Sent By jleech Date 2000-11-30 Time 19:22 Rev Time 0.25
Received By jleech Date 2000-11-30 Time 19:22 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-11-01 Cont ID  
Sent By tlarge Date 2000-11-01 Time 18:23 Rev Time 0.33
Received By tlarge Date 2000-11-01 Time 18:23 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2000-12-13 Cont ID  
Sent By lsmith Date 2000-11-16 Time 14:10 Rev Time 4.50
Received By lsmith Date   Time   Sent To  
Notes
2001-01-08 00:00:00ALL NOTES FRO PREVIOUS REVIEW HAVE BEEN
 APPROVED LS12/13/00
  
  
 SITE SPECIFIC SIGNED BY ENGINEER/
 ARCH. & HAVE ADDRESS SHOWN ON 9.0
 C.PROVIDE SECTION AT EXTERIOR PORCH
 CEILINGS.
 D.PROVIDE DETAILS FOR SOFFIT ON
 ZERO LOT LINE.OPENINGS PROHIBITED
 E. DOOR TO GARAGE TO BE SOLID OR
 INSULATED PER FLA ENERGY CODE.
 F.LEFT ELEVATION DOES NOT COMPLY WITH
 TABLE 600 FOR 20% OPENINGS. SBC '97
 G.A/C AIR HANDLERS IN ATTIC MUST HAVE
 PLATFORMS, WALKWAYS & LIGHTS FOR
 SERVICE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL:
 LEA SMITH
 BUILDING PLAN REVIEW
 659-8096 EXT 8394

Review Stop Z ZONING
Rev No 1 Status P Date 2000-10-17 Cont ID  
Sent By gjoyce Date 2000-10-17 Time 09:23 Rev Time 0.15
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***