Plan Review Details - Permit 00100581
Plan Review Stops For Permit 00100581
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2001-01-23 Cont ID  
Sent By jwitmer Date 2001-01-23 Time 08:29 Rev Time 2.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2001-01-02 Cont ID  
Sent By jwitmer Date 2001-01-02 Time 09:17 Rev Time 2.00
Received By jwitmer Date   Time   Sent To  
Notes
2001-01-08 00:00:00BUILDING PLAN REVIEW:
  
 1). SBC 1804.2 SOILS REPORT / MINIMUM
 SOIL BEARING CAPACITY
 2).SS 553.71 THRESHOLD BUILDING- A COPY
 OF THE REQUIRED THRESHOLD INSPECTION
 PLAN PREPARED BY THE ENGINEER OF RECORD.
 3). SBC. 104.2 ATTACHMENT OF ALL WINDOW
 AND DOOR BUCKS.NOTE: 609.2.1.1 EXCEPTION
 ALL BUCKS,HEADERS,BLOCKING ETC; IN PART-
 ITIONS TO BE APPROVED FIRE RETARDANT
 TREATED WOOD.
 4). SBC 1606.4/1707.4.1 GLAZED OPENINGS
 REQUIRE TESTING REPORTS FOR LARGE MISSLE
 IMPACT RESISTANT GLAZING FOR OPENINGS
 BELOW 30' AND SMALL MISSLE IMPACT TESTIN
 ABOVE 30'.
 5). SBC 1707.5 INFORMATION ON THE ROOF
 TILE TESTING, A SBCCI REPORT OR DADE
 COUNTY PRODUCT APPROVAL REPORT.
  
 BUILDING PLAN REVIEW:
 JIM WITMER
 (561) 659-8-96 EX 8412
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RE-SUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISIONS
 AND REMOVE AND OR REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING
 THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND, WIL
 HELP TO EXPEDITE TO YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2000-11-20 Cont ID  
Sent By hpiskura Date 2000-11-20 Time 14:27 Rev Time 0.00
Received By hpiskura Date 2000-11-13 Time 07:26 Sent To  
Notes
2001-01-08 00:00:00LETTER W/ APPLICATION

Review Stop E ELECTRICAL
Rev No 11 Status N Date 2002-10-17 Cont ID  
Sent By dpalmer Date 2002-10-17 Time 08:35 Rev Time 0.00
Received By dpalmer Date 2002-10-17 Time 08:35 Sent To  
Notes
2002-10-17 00:00:00STAMPED OFFICE FILE SET.

Review Stop E ELECTRICAL
Rev No 10 Status P Date 2002-10-09 Cont ID  
Sent By dpalmer Date 2002-10-09 Time 16:48 Rev Time 0.00
Received By dpalmer Date 2002-10-09 Time 16:48 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 9 Status F Date 2002-07-25 Cont ID  
Sent By dpalmer Date 2002-07-25 Time 11:54 Rev Time 0.00
Received By dpalmer Date 2002-07-25 Time 11:54 Sent To  
Notes
2002-07-25 00:00:00*************** UNSAT *************
  
 1)NOTE: PLEASE NOTE, SHEET E3-1 DOES
 NOT HAVE AN ORIGINAL SIGNATURE FROM
 ENGINEER OF RECORD. IT APPEARS THAT THIS
 SHEET IS ONE THAT DID NOT GET CAHNGED
 OUT?.
 FS/FAC 471.025.
 PLEASE NOTE IT STILL HAS DATE FROM 2/13/
 02.
 PLEASE ALSO NOTE THAT HAND DRAWN CHANGES
 NEED TO BE PRINTED.
  
 PLEASE SUBMIT THE ABOVE FOR REVIEW. IF
 THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 8 Status F Date 2002-04-03 Cont ID  
Sent By dpalmer Date 2002-04-03 Time 12:52 Rev Time 0.00
Received By dpalmer Date 2002-04-03 Time 12:51 Sent To  
Notes
2002-04-03 00:00:00**************** UNSAT *****************
  
 1)NOTE: PLEASE NOTE THAT ALL HANDWRITTEN
 CHANGES NEED TO RE-DONE ON THE PLANS
 AND REPRINTED. PLEASE NOTE THAT ALL OF
 THESE CHANGES ARE REQ`D TO BE DONE BY
 THE ENGINEER/ARCH`S OF RECORD.
 PLEASE ALSO NOTE THAT ALL MUST BE SIGNED
 ,DATED AND SEALED BY THE ENGINEER AND/OR
 ARCH OF RECORD.
 FS/FAC. 471.025,481.221
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 7 Status F Date 2002-02-21 Cont ID  
Sent By dpalmer Date 2002-02-21 Time 07:50 Rev Time 0.00
Received By dpalmer Date 2002-02-21 Time 07:50 Sent To  
Notes
2002-02-21 00:00:00NOTE
  
 ELECTRICAL REV DID NOT MATCH TO JOBSITE
 EQUIPMENT. CALLED CONTRACTOR AND NEW
 PLANS WILL BE SUBMITTED FOR REVIEW.

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2001-10-30 Cont ID  
Sent By dpalmer Date 2001-10-30 Time 16:09 Rev Time 0.00
Received By dpalmer Date 2001-10-30 Time 16:09 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2001-04-27 Cont ID  
Sent By dpalmer Date 2001-04-27 Time 12:50 Rev Time 0.00
Received By dpalmer Date 2001-04-27 Time 12:50 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2001-03-07 Cont ID  
Sent By dpalmer Date 2001-03-07 Time 20:58 Rev Time 0.00
Received By dpalmer Date 2001-03-07 Time 20:58 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2001-01-22 Cont ID  
Sent By dpalmer Date 2001-01-22 Time 20:28 Rev Time 0.00
Received By dpalmer Date 2001-01-22 Time 20:28 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2001-01-03 Cont ID  
Sent By dpalmer Date 2001-01-03 Time 20:14 Rev Time 0.00
Received By dpalmer Date 2001-01-03 Time 20:13 Sent To  
Notes
2001-01-08 00:00:00**************** UNSAT ****************
  
 THESE ARE NOTES IN RESPONSE TO LETTER
 AND NOTES NOT FULLY ADDRESSED FROM FIRST
 REVIEW.PLEASE SEE THE FOLLOWING.
  
 1)NOTE:(NOTE 1)OK BUT NO MORE THAN 6 OCP
 DEVICES MAY BE INSTALLED. TEN (10 )
 SPACES ARE SHOWN.ALLOWING FUTURE
 INSTALLATION OF MORE THAN SIX MEANS OF
 DISCONNECT
  
  
 2NOTE: NOTE 2 OK
  
 3)NOTE: NOTE 3 OK
  
 4)NOTE: PLEASE SEE 230-6 FOR REQ`MENTS
 OF OUTSIDE THE BLDG. 2" ENCASEMENT OF
 CONCRETE. PLEASE CLARIFY THIS ON E3-1
 PLEASE NOTE THAT S-1 WAS NOT IN THE SET
 THAT I REVIEWED. MAYBE THIS IS WHERE
 THIS DETAIL IS LOCATED. PLEASE CLARIFY
 LOCATION OF DETAIL OF POURED CONCRETE
 ENCASEMENT.
  
 5)NOTE: NOTE 5 OK
  
 6)NOTE: NOTE 6 PLEASE CORRELATE E3-1 AND
 E3-2 EMDP ON E3-2 SHOWN AS MLO? YET ON
 E3-1 EMDP IS SHOWN AS 400A MCB.??
 PLEASE CLARIFY.HOW DOES FUTURE GENERATOR
 PROVIDE THE REQ`D EM POWER NOW.?LIGHTING
 FIRE PUMP, ECT
 NOTE: NOTE 7 OK
 8)NOTE: NOTE 8 YOUR REPSONSE IS THAT
 THERE ARE NO CIRCUITS ENTERING MORETHAN
 120 VOLTS. VOLTAGE AT 120V IS NOT PER-
 -MITTED. POWER FOR MAIN BLDG MAY BE
 SHUT DOWN INCASE OF FIRE AND THERE WILL
 STILL BE 120V COMING IN, ENOUGH TO CAUSE
 INJURY OR DEATH. POWER IN ONE BLDG FROM
 TWO SERVICES??? A MEANS OF DISCONNECT IS
 REQ`D IN ELEC ROOM.
 .
  
 9)NOTE: NOTE 9 OK.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. PLEASE CALL FOR APPOINTMENT
 WITH MYSELF AND THE CHIEF ELECTRICAL
 INSPECTOR FOR ANY QUESTIONS THAT MAY
 STILL NEED TO BE ADDRESSED.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372
  
  
 NOTE: PLEASE SEE 230-70A AND EXPLAIN HOW
 SERVICE READILY ACCESSIBLE. TO MEET NEC
 PLEASE NOTE THAT SERVICE IS SHOWN ON
 SECOND FLOOR UP STAIRS BEHIND TWO
 LOCKED DOORS.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-11-20 Cont ID  
Sent By dpalmer Date 2000-11-20 Time 21:41 Rev Time 0.00
Received By dpalmer Date 2000-11-20 Time 21:41 Sent To  
Notes
2001-01-08 00:00:00****************** UNSAT **************
  
 1)NOTE: PLEASE SEE 230-71A. THERE CAN BE
 NO MORE THAN SIX MEANS OF DISCONNECT IN
 A SINGLE ENCLOSURE. PLEASE SEE MSB
 ENCLOSURE SHOWN. THIS SHOWS 10?? PLEASE
 CORRECT.
  
 2)NOTE: ALSO PLEASE SEE 230-95 FOR THE
 REQ`D GFI PROTECTION OF SERVICE.
  
 3)NOTE: PLEASE SEE 230-76 AND 230-79 FOR
 MEANS OF DISCONNECT REQ`D. SHUNT TRIPS
 ARE NOT A SERVICE RATED MEANS OF DISC-
 -CONNECT.
  
 4)NOTE: PLEASE ALSO SEE 230-70 FOR THE
 LOCATION OF THE MEANS OF DISCONNECTS.
 PLEASE ALSO NOTE PER LOCAL AMENDMENTS
 NO UNPROTECTED MORE THAN 8`INSIDE A
 BLDG.
  
 5)NOTE: PLEASE SHOW NOTE PER LOCAL
 AMENDMENTS FOR COLOR CODING OF 277/480V
 SYSTEMS.
  
 6)NOTE: PLEASE SUBMIT CLARIFICATION FOR
 SERVICE. YOU SHOW EMERGENCY POWER
 FOR EMDP? PLEASE SHOW WHERE THIS POWER
 IS COMING FROM?????GENERATOR? NOTE:
 MEANS OF DISCONNECT ON BLDG. FOR THIS.
  
 7)NOTE: ALSO PLEASE SHOW ALL CONTINUOUS
 LOADS AT 125% AND INCLUDE LARGEST MOTOR.
 LIGHTING LOADS AT 125%.!!
  
 8)NOTE: PLEASE NOTE GROUPING OF MAINS
 FOR SERVICE AT BLDG AND SERVICE FOR
 CHILLERS. POWERED CONTROL CIRCUITS
 ENTERING BLDG FROM THE SERVICE FOR THE
 CHILLER NEEDS TO HAVE MEANS OF DISC
 GROUPED PER 230-72 AND LABELED FOR
 LOCATIONS OF EACH MEANS.
  
 9)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL EQUIPMENT BEING INSTALLED. PER 110-9
 AND 215-5.SEE MAIN FOR FIRE PUMP CONTR.
  
  
 PLEASE SUBMIT ALL OF THE ABOVE INFORMAT-
 -ION FOR REVIEW. IF THERE ARE ANY QUES-
 -TIONS PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2001-01-16 Cont ID  
Sent By mgonzale Date 2001-01-16 Time 12:59 Rev Time 1.00
Received By mgonzale Date   Time   Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2001-01-05 Cont ID  
Sent By mgonzale Date 2001-01-05 Time 09:34 Rev Time 1.00
Received By mgonzale Date   Time   Sent To  
Notes
2001-01-08 00:00:00APPROVED WITH PROVISOS FOR BUILDING ONLY
 2 SETS OF PLANS HAVE BEEN MARKED UP
 THROUGH PUBLIC UTILITIES
 AS FAR AS THE BUILDING WE HAVE NO OBJECT
 IONS AS TO ITS COMMENCEMENT.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2000-11-27 Cont ID  
Sent By mgonzale Date 2000-11-27 Time 11:37 Rev Time 1.00
Received By mgonzale Date   Time   Sent To  
Notes
2001-01-08 00:00:00FAILED
 COMMENTS
 C-2
 NO LARGE TREES ARE TO BE PLANTED ON TOP
 OF EXIST. 4" WM ALONG ACACIA ROAD
 A 5' MINIMUM DISTANCE FROM A LARGE
 TREE TO EXISTING PUBLIC UTILITIES
 MUST BE MAINTAINED.
 CUT ON PUBLIC WM NOT ALLOWED
 C.O. MUST BE INSTALLED AT ROW LINE
 WHERE SANITARY SEWER WILL BE MADE UNTO
 DIXIE.A FDOT ROW PERMIT MAY APPLY.
 EXISTING CURB AND SIDEWALK THAT MAY BE D
 DAMAGED BY CONSTRUCTION MUST RE REPLACED
 WHERE EXIST DRIVEWAY APPROCHES ARE
 ELIMINATED THE SIDEWALK MUST BE REDONE
 AND RECURBED.
 SPECIFY WITH A NOTE THAT WM IN ROW
 MUST BE CLASS 52 CEMENT LINED DIP
  
 METER MUST BE INSTALLED JUST OUTSIDE OF
 PROPERTY. AND A VALVE SHOULD BE
 ADDED AFTER METER TO SHUT SEPERATE
 FIRE AND DOMESTIC SERVICES INCASE ONE
 GOES DOWN.
 NO POLLUTION CONTROL PLAN
 IT MUST SHOWN SILT FENCE AROUND
 CONSTRCUTION AREAS ALONG WITH BALES
 OF HAY AND IT MUST LIST PERVIOIUS AND
 IMPERVIOUS CALCULATIONS WITH 100% TOTAL
 SITE LISTED IN S.F. AND ACRES.
 NEW STORM CHRGES WILL BE CLACUALTED FROM
 THIS TALLY.
 (SEE STORM REQUIREMENTS)
 AFTER REVISIONS ARE MADE PLEASE
 SUBMITT 2 SETS FOR REVIEW TO PUBLIC
 UTILITIES ENGINEERING SERVICES DIV
 1000 45TH ST. ATTENTION DEAN LAUDERMILK
 561 659 8040
 (MAKE SURE YOU USE LATEST STD DETAILS
 FOR UTILITY THEY MAY BE REQUESTED AT
 [email protected]
 HAVE A GREAT DAY.

Review Stop FIRE FIRE DEPARTMENT
Rev No 8 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 7 Status P Date 2002-03-15 Cont ID  
Sent By mcarsill Date 2002-03-15 Time 10:11 Rev Time 0.00
Received By mcarsill Date 2002-03-15 Time 10:11 Sent To  
Notes
2002-03-15 00:00:00FLAME SPREAD INFORMATION.

Review Stop FIRE FIRE DEPARTMENT
Rev No 6 Status P Date 2001-10-30 Cont ID  
Sent By mcarsill Date 2001-10-30 Time 16:35 Rev Time 0.00
Received By mcarsill Date 2001-10-30 Time 16:34 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2001-04-24 Cont ID  
Sent By mcarsill Date 2001-04-24 Time 15:18 Rev Time 0.00
Received By mcarsill Date 2001-04-24 Time 15:18 Sent To  
Notes
2001-04-24 00:00:001) ADDITIONAL ILLUMINATED EXIT SIGNS
 APPEAR TO BE REQUIRED IN INSTRUMENT
 REHEARSAL ROOM 119.
 2) IT IS IMPERATIVE THAT A TWO HOUR
 FIRE SEPARATION BE PRESENT BETWEEN
 THE FIRE PUMP ROOM AND FIRE EXIT STAIR
 # 2. NO EQUIPMENT IN FIRE PUMP ROOM
 IS TO INTERFERE WITH EXITING FROM THE
 FIRE EXIT STAIR.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2001-03-06 Cont ID  
Sent By mcarsill Date 2001-03-06 Time 10:28 Rev Time 0.00
Received By mcarsill Date 2001-03-06 Time 10:27 Sent To  
Notes
2001-03-06 00:00:001) PLEASE PROVIDE ILLUMINATED EXIT
 SIGNS IN INSTRUMENT REHEARSAL ROOM, 119.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2001-01-19 Cont ID  
Sent By mcarsill Date 2001-01-19 Time 13:53 Rev Time 0.00
Received By mcarsill Date 2001-01-19 Time 13:53 Sent To  
Notes
2001-01-19 00:00:00ON JANUARY 19,2001, THIS WRITER MET WITH
 MR. THOMAS OF SCHWAB, TWITTY AND HANSEN.
 HE PROVIDED WRITER WITH SOME SPRINKLER
 PLANS THAT DISPLAYED ALL VERTICAL SHAFTS
 WILL BE FIRE SPRINKLER PROTECTED. A
 REVIEW OF THESE DRAWINGS INDICATE THAT
 STAIR NUMBER 2 NEEDS FIRE SPRINKLER
 PROTECTION AT THE TOP OF IT.
 1) SEPARATE PLANS AND PERMITS REQUIRED
 FOR FIRE SPRINKLER AND FIRE
 ALARM SYSTEM INSTALLATIONS.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2000-12-11 Cont ID  
Sent By mcarsill Date 2000-12-11 Time 10:49 Rev Time 0.00
Received By mcarsill Date 2000-12-11 Time 10:49 Sent To  
Notes
2001-01-08 00:00:001) PLAN REVIEW COMMENTS, ITEM 4 RESPONSE
 INDICATES THAT VERTICAL SHAFTS ARE
 NON ACCESSIBLE. NFPA 13, INDICATES "ONE
 SPRINKLER SHALL BE INSTALLED AT THE TOP
 OF ALL SHAFTS".
 2) COULD NOT LOCATE FPO-1 OR FP3-1.
 AS INDICATED ON THE PLAN REVIEW COMMENTS
 REGARDING THE FIRE PUMP AND STANDPIPE
 SYSTEM.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2000-11-03 Cont ID  
Sent By mcarsill Date 2000-11-01 Time 12:56 Rev Time 0.00
Received By mcarsill Date 2000-11-01 Time 12:56 Sent To  
Notes
2001-01-08 00:00:001) BUILDING WILL BE REQUIRED TO HAVE
 A KNOX-BOX FOR EMERGENCY PURPOSES. AN
 APPLICATION FOR THIS BOX CAN BE OBTAINED
 FROM WEST PALM BEACH FIRE RESCUE,
 STATION #1.
 2) BUILDING ADDRESS NOT SHOWN ON
 ELEVATION DRAWINGS. BUILDING ADDRESS TO
 COMPLY WITH CITY CODE REQUIREMENTS.
 3) PROVISIONS ARE TO BE MADE FOR AT
 LEAST TWO HANDICAPPED PERSONS.
 4) ENTIRE BUILDING IS TO BE COMPLETELY
 FIRE SPRINKLER PROTECTED. THIS INCLUDES
 ALL MECHANICAL, ELECTRICAL, AND SERVICE
 ROOMS. ALSO ALL VERTICAL SHAFTS ARE
 TO BE PROTECTED BY FIRE SPRINKLERS.
 NO HYDRAULIC CALCULATIONS WERE PROVIDED
 WITH FIRE SPRINKLER DRAWINGS. A SEPARATE
 PLAN AND PERMIT IS REQUIRED FOR THE
 INSTALLATION OF FIRE SPRINKLER SYSTEM.
 5) CLEARLY INDICATE FIRE HYDRANT
 LOCATIONS IN RELATIONSHIP TO NEW
 BUILDING.
 6) PLEASE PROVIDE INTERIOR FLAME SPREAD
 INFORMATION ON ALL INTERIOR FINISHES.
 THIS INCLUDES DRAPERIES, SEATS, ETC.
 7) ANY DOOR IN A REQUIRED MEANS OF
 EGRESS SUBJECT TO AN OCCUPANCY OF 100
 OR MORE PERSONS SHALL BE EQUIPPED WITH
 APPROVED PANIC HARDWARE. IF THEY ARE
 FIRE DOORS, THEN THEY ARE TO BE EQUIPPED
 WITH APPROVED PANIC FIRE EXIT HARDWARE.
 8)PLEASE PROVIDE TOTAL OCCUPANT LOADS
 FOR ALL FLOORS.
 9) AT LEAST ONE USEABLE STAIR IS TO BE
 PROVIDED DURING CONSTRUCTION ACTIVITIES.
 10) FIRE HYDRANTS ARE TO BE PROVIDED
 PRIOR TO BEGINNING CONSTRUCTION.
 11) A TEMPORARY STANDPIPE IS TO BE
 PROVIDED FOR THE BUILDING WHEN IT
 REACHES THREE STORIES AND 50 FEET IN
 HEIGHT.
 12) PLEASE INDICATE THE TYPE OF STAGES
 OR PLATFORMS PLANNED FOR THE AUDITORIUM
 AREAS.
 13) PLEASE PROVIDE COMPLETE FIRE ALARM
 SYSTEM SHOP DRAWINGS FOR THE FIRE
 ALARM SYSTEM. CUT SHEETS, WIRING DIAGRAM
 AND FLOOR PLANS ARE TO BE SUBMITTED.
 FIRE ALARM SYSTEM AND SPRINKLER SYSTEM
 ARE TO BE MONITORED BY A UL LISTED
 CENTRAL STATION APPROVED BY THE FIRE
 RESCUE DEPARTMENT.
 14) PLEASE PROVIDE MORE DETAILS ON OWNER
 SUPPLIED CHORAL SEATED RISERS PLANNED
 FOR CHORAL REHEARSAL, 335.
 15) ELEVATORS TO COMPLY WITH ANSI A17.1
 AND 4A-47,UNIFORM RULES AND STANDARDS
 FOR ELEVATORS.
 16) DOUBLE DOORS LEADING FROM SOUND LOCK
 INTO GALLERY, FIRST FLOOR TO BE 20
 MINUTE FIRE DOORS WITH CLOSERS.
 17) PROVIDE COMPLETE PLANS AND PERMITS
 FOR THE INSTALLATION OF THE REQUIRED
 STANDPIPE SYSTEM AND FIRE PUMP.
 18) PLATFORM CONSTRUCTION TO COMPLY WITH
 NFPA 101, THE LIFE SAFETY CODE, 1985
 EDITION, SECTION 8-3.2.1.3. IS STORAGE
 GOING TO BE PERMITTED UNDERNEATH THE
 PLATFORM.
 19) PROVIDE FLAMESPREAD DETAILS FOR
 PROJECTION SCREEN.
 20) PLEASE PROVIDE CODE SECTIONS FOR
 SEATING LAYOUTS SHOWN ON PLANS.
  
 PLANS REVIEWED BY CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2002-07-31 Cont ID  
Sent By pkrauss Date 2002-07-31 Time 08:28 Rev Time 0.55
Received By pkrauss Date 2002-07-31 Time 07:35 Sent To  
Notes
2002-07-31 00:00:00AS BUILT DRAWINGS

Review Stop M MECHANICAL (A/C)
Rev No 5 Status F Date 2002-02-11 Cont ID  
Sent By pkrauss Date 2002-02-11 Time 16:32 Rev Time 0.45
Received By pkrauss Date 2002-02-11 Time 16:32 Sent To  
Notes
2002-02-11 00:00:00 
 *******************DENIED***************
  
 PLAN SHEET M2.2 - MECHANICAL ROOM #205
 & 203 FIRE DAMPERS ARE REQUIRED FOR THE
 O.A. AND EXHAUST LOUVER.1997 SMC
 610.1.2.PROVIDE LOCATION & DETAILS ON
 PLAN AS PER 1997 SMC 610.6.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2001-10-23 Cont ID  
Sent By ndenmark Date 2001-10-23 Time 11:19 Rev Time 1.00
Received By ndenmark Date 2001-10-23 Time 11:19 Sent To  
Notes
2001-10-23 00:00:00REVISION 4 ADDITION OF FIRE DAMPERS ON
 FIRST FLOOR AND REMOVAL OF DAMPERS ON
 FOURTH FLOOR.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2001-03-19 Cont ID  
Sent By pkrauss Date 2001-03-19 Time 14:23 Rev Time 0.35
Received By pkrauss Date 2001-03-19 Time 14:11 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-01-04 Cont ID  
Sent By ndenmark Date 2001-01-04 Time 09:13 Rev Time 0.50
Received By ndenmark Date 2001-01-04 Time 09:13 Sent To  
Notes
2001-01-08 00:00:00PRIOR COMMENTS ADDRESSED AND CORRECTED
 ON REVISION DATED 12/1/00

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2000-11-27 Cont ID  
Sent By ndenmark Date 2000-11-27 Time 12:38 Rev Time 3.00
Received By ndenmark Date 2000-11-27 Time 12:37 Sent To  
Notes
2001-01-08 00:00:00**************DENIED********************
  
 1. NO FIRE DAMPERS SHOWN AT RATED CORR-
 IDOR WALLS AT DUCT PENETRATIONS. 1997
 SMC 610.6.1 REQUIRES LOCATION AND INSTA-
 LLATION DETAILS TO BE INDICATED ON PLAN
 BY DESIGNER.(PER 610.1)
 2. MENS RM ON M-2.1 HAS A E1(150 CFM)
 W/ 75CFM DIFFUSER AFTER HEATER AND 75CFM
 PRIOR TO HEATER. IS THIS CORRECT?
 3. CLARIFY AIR DIRECTION ON M-2.1 @ (17)
 EXHAUST AIR LOUVER.
 4. PROVIDE ENLARGED DETAIL OF MECHANICAL
 ROOMS SHOWING COMPLIANCE WITH 1997 SMC
 304.2.1 AND MANUFACTURES COIL PULL
 CLEARANCE REQUIREMENTS
 5. SPECIFY CHILLED WATER PIPING MATERIAL
 6. NOTE: NO COMBUSTIBLE MATERIALS ARE
 TO BE USED IN ANY AREA USED AS A RETURN
 AIR PLENUM. (RE: NOTE ON MECHANICAL
 FLOOR PLANS)

Review Stop P PLUMBING
Rev No 6 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 5 Status P Date 2002-07-19 Cont ID  
Sent By kstevens Date 2002-07-19 Time 19:54 Rev Time 0.00
Received By kstevens Date 2002-07-19 Time 19:54 Sent To  
Notes
2002-07-19 00:00:00REVISIONS/AS BUILTS OK

Review Stop P PLUMBING
Rev No 4 Status P Date 2001-01-19 Cont ID  
Sent By jleech Date 2001-01-19 Time 10:05 Rev Time 2.00
Received By jleech Date 2001-01-19 Time 10:05 Sent To  
Notes
2001-01-19 00:00:00PROVISO;
 UL #C-AJ-5021 IS NOT THE CORRECT
 ASSEMBLY FOR PVC PIPE. PLEASE SUBMIT
 PROPER ASSEMBLY FOR APPROVAL BEFORE ANY
 FIRE SAFING IS STARTED.

Review Stop P PLUMBING
Rev No 3 Status F Date 2000-12-18 Cont ID  
Sent By jleech Date 2000-12-18 Time 14:53 Rev Time 3.00
Received By jleech Date 2000-12-18 Time 14:53 Sent To  
Notes
2001-01-08 00:00:00PLUMBING REVIEW NOTES;
  
 1.A MIN. OF ONE DRINKING FOUNTAIN PER
 FLOOR SHALL BE SUPPLIED PER SPC TABLE
 407. PROVISIONS SHALL BE MADE FOR
 PEOPLE WHO HAVE TROUBLE BENDING OR
 STOOPING PER FACBC SEC 4.1.3.(10).
  
 2.SHT. C-2 SHOW SIZE OF SEWER TAP AND
 SANITARY SEWER LINE.
  
 3.SUBMIT CALCULATIONS FOR SECONDARY
 EMERGENCY DRAINAGE. COMPLY WITH SEC.
 SPC. 1109.1 - 1109.3 AND APPENDIX "A".
  
 4.SUBMIT UL ASSEMBLY NUMBER OF FIRE
 SAFING DETAILS FOR PIPE PENETRATIONS
 COUNTYWIDE AMENDMENTS TO SPC. SEC.
 104.2.4.
  
 5.SHT. M2.2 BACKFLOW PREVENTER DEVICE
 ON MAKE UP WATER SHALL BE FOR HIGH
 HAZARD. COMPLY WITH SPC TABLE 606
  
 6.I COULD NOT CHECK T. LARGE'S NOTE 17
 [THE LAYOUT OF THE RESTROOM ON SHT.
 A-5.2.1 BY FIRE STAIR 300 DOESN'T
 CORRELATE W/A 2.3.1 CLARIFY. SHTS.
 WERE NOT SUBMITED.
  
 7.DRY VENTS ON WATER CLOSETS NOT
 PERMITED PER SPC 906.2.1.
  
 8.SANITARY ISOMETRIC RISER DIAGRAM PAGE
 P3-1 WASTE STACK (92 F.U.) MUST RUN
 UNDIMINISHED IN SIZE TO CONNECTION
 OF STACK VENT SPC 714.2
  
 9.WOMENS HANDICAP STALL DOOR SHOWN
 (A1.3.1) SWINGING OUT (A4.1.5)SWINGING
 IN SWING SHOULDBE OUT OF H/C TURNING
 CIRCLE.
  
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT.8377

Review Stop P PLUMBING
Rev No 2 Status F Date 2000-10-26 Cont ID  
Sent By tlarge Date 2000-10-26 Time 17:01 Rev Time 0.00
Received By tlarge Date 2000-10-26 Time 17:01 Sent To  
Notes
2001-01-08 00:00:00*****CONTINUATION OF PLUMBING PLAN
 REVIEW COMMENTS.
  
 26)TWO WATER CLOSETS ON A HORIZ.SECTION
 MAY BE VENTED PER COUNTYWIDE AMENDMENTS
 TO SPC SEC.911.1.3.
  
 27)DRY VENTS ON WATER CLOSETS NOT
 PERMITTED PER SPC SEC.906.2.1.
  
 28)CLEARLY DESIGNATE THE FLOOR LEVELS ON
 THE PLUMBING DRAWINGS.COUNTYWIDE AMEND-
 MENTS TO SPC SEC.104.2.1.
  
 29)VACUUM RELIEF VALVE SHALL BE
 INSTALLED PER SPC SEC.507.1.2.
  
 CALL IF YOU HAVE QUESTIONS.
 561-659-8096,EXT.8377.
  
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-10-26 Cont ID  
Sent By tlarge Date 2000-10-26 Time 15:14 Rev Time 30.00
Received By tlarge Date 2000-10-26 Time 15:14 Sent To  
Notes
2001-01-08 00:00:001)SUBMIT OCCUPANT LOAD PER TABLE 407 OF
 THE SPC.SEE SPC SEC.407.1.3.FOR ALLOWED
 DEDUCTIBLE AREAS.
  
 2)A MIN.OF 1 DRINKING FOUNTAIN PER FLOOR
 SHALL BE SUPPLIED PER SPC TABLE 407.
 PROVISIONS SHALL BE MADE FOR PEOPLE WHO
 HAVE TROUBLEBENDING OR STOOPING PER
 FACBC SEC.4.1.3.(10)(A).
  
 3)THE MIN.NUMBER OF REQD.SANITARY
 FACILITIES SHALL BE DETERMINED BY THE
 OCCUPANT LOAD.SEE COMMENT #1.COMPLY W/
 SPC TABLE 407.ADD'L.FIXTURES ARE REQD.
  
 4)SHT.C-2-CLEARLY SHOW SIZE OF SANITARY
 SEWER LINE.
  
 5)TOILET ROOM #130(CHANGING ROOM)SHALL
 BE FULLY H.C.ACCESSIBLE PER FACBC SEC.
 4.1.3.(11).
  
 6)AN ADDITIONAL H.C.STALL IS REQD.IN THE
 WOMEN'S R.R.PER FACBC SEC.4.22.4.
  
 7)PANTRY SINK AND COUNTER(RM.117)SHALL
 COMPLY W/FACBC SEC.4.24.1-4.24.7.
  
 8)BREAK ROOM SINK AND CABINET SHALL
 COMPLY W/4.24.1.-4.24.7.
  
 9)SUBMIT CALCULATIONS FOR SECONDARY
 (EMERGENCY)DRAINAGE.COMPLY W/SPC SEC.
 1109.1-1109.3 AND APPENDIX "A."
  
 10)SHT.4.1.5-DETAIL #1-DOOR ON H.C.STALL
 CANNOT SWING INTO CLEAR FLOOR SPACE
 REQD.FOR URINAL PER FACBC SEC.4.17.5.
  
 11)SHOW THE REQD.WHEELCHAIR TURNING
 SPACE IN ROOM#130(CHANGING ROOM TOILET
 ROOM)FACBC SEC.4.2.3.
  
 12)SHT.4.1.5.-DETAIL #3-WATER CLOSET
 SHALL BE 18"FROM WALL PER FACBC SEC.
 4.16.2.(SEE NOTE #2 ALSO).
  
 13)HEIGHT OF PAPER TOWEL DISPENSER SHALL
 COMPLY W/FACBC SEC.4.2.5,4.2.6.,4.27.2,
 4.27.3.(SEE SHT.4.1.5.)
  
 14)SHOW CLEAR FLOOR SPACE FOR URINAL.
 COMPLY W/FACBC SEC.4.18.3.
  
 15)SHT.4.1.5.-SHOW THE REQD.WHEELCHAIR
 TURNING SPACE IN RESTROOMS #305,306,403,
 407.COMPLY W/FACBC SEC.4.2.3.
  
 16)A FLOOR DRAIN IS REQD.IN THE CHANGING
 ROOM TOILET PER SPC 409.4.1.1.
  
 17)THE LAYOUT OF THE RESTROOM ON SHT.
 A-5.2.1.BY FIRE STAIR 300 DOESN'T
 CORRELATE W/A-2.3.1.CLARIFY.
  
 18)SUBMIT UL ASSEMBLY NUMBER OFFIRE
 SAFING DETAILS FOR PIPE PENETRATIONS.
 COUNTYWIDE AMENDMENTS TO SPC SEC.104.2.4
  
 19)SHT.M2.2.-BFP DEVICE ON M/U WATER
 SHALL BE FOR HIGH HAZARD.COMPLY W/SPC
 TABLE 606.
  
 20)SHT.C-2-CLEARLY SHOW LOCATION OF CD
 LINES ON CIVIL DRAWINGS.COUNTYWIDE
 AMENDMENTS TO SPC SEC.104.2.1.
  
 21)SHOW POINT OF COMPASS ON PLBG.PLANS.
 COUNTYWIDE AMENDMENTS TO SPC SEC.104.2.1
  
 22)INDICATE SLOPE OF STORM DRAIN
 BRANCHES,LEADERS DRAIN AND SEWER.COMPLY
 W/SPC TABLES 1108.1,1108.2.
  
 23)WATER HEATER ABOVE THE FIRST FLOOR
 SHALL BE INSTALLED IN A PAN W/A DRAIN
 AND COMPLY W/SPC SEC.507.8.1.-507.8.4.
  
 24)SHT.P3.1-SANITARY SYSTEM SHALL COMPLY
 W/SPC SEC.914.1 FOR A CIRCUIT AND LOOP
 SYSTEM.VENTS SHALL COMPLY W/SPC SEC.
 920.3.
  
 25)WET VENTS SHALL RECEIVE THE DISCHARGE
 FROM FIXTURE DRAINS ONLY.FIXTURE
 BRANCHES AND WATER CLOSETS ARE NOT
 PERMITTED ON WET VENTS.COUNTYWIDE AMEND-
 MENTS TO SPC SEC.911.1.1.
  
 SEE REVIEW STEP#2 FOR CONTINUATION.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2001-03-02 Cont ID  
Sent By hpiskura Date 2001-03-02 Time 13:38 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy