Plan Review Details - Permit 00100526
Plan Review Stops For Permit 00100526
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2000-12-05 Cont ID  
Sent By drunnels Date 2000-12-05 Time 13:43 Rev Time 0.50
Received By drunnels Date 2000-12-05 Time 13:43 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2000-11-20 Cont ID  
Sent By drunnels Date 2000-11-20 Time 14:41 Rev Time 1.00
Received By aneil Date 2000-11-20 Time 14:41 Sent To  
Notes
2001-01-08 00:00:001] SUBMIT FIRESPRINKLER PLANS AND PERMIT
 APPLICATION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2000-10-19 Cont ID  
Sent By drunnels Date 2000-10-19 Time 09:03 Rev Time 1.00
Received By drunnels Date 2000-10-19 Time 08:41 Sent To  
Notes
2001-01-08 00:00:001.SHEET A4 DETAILS 1&3 PARTITION TYPE
 NOTE 3 CALLS FOR 1/2 INCH GWB DRAWINGS
 CALL FOR 5/8 INCH GWB WHICH IS TO BE
 USED?
 2. SUBMIT FIRE SPRINKLER PLANS AND
 PERMIT APPLICATION.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2000-10-23 Cont ID  
Sent By dpalmer Date 2000-10-23 Time 11:11 Rev Time 0.00
Received By dpalmer Date 2000-10-23 Time 11:11 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2000-11-07 Cont ID  
Sent By mcarsill Date 2000-11-07 Time 14:33 Rev Time 0.00
Received By mcarsill Date 2000-11-07 Time 14:33 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2000-10-13 Cont ID  
Sent By mcarsill Date 2000-10-13 Time 16:15 Rev Time 0.00
Received By mcarsill Date 2000-10-13 Time 16:14 Sent To  
Notes
2001-01-08 00:00:001) NO FIRE SPRINKLER DRAWINGS OR
 HYDRAULIC CALCULATIONS PROVIDED WITH
 PLANS.
 2) FIRE ALARM EQUIPMENT SHOWN ON PLANS
 REQUIRES SEPARATE PLAN AND PERMIT.
 CUT SHEETS AND WIRING DIAGRAM REQUIRED.
  
 PLANS REVIEWED BY CAPTAIN MIKE CARSILLO
 659-8096, EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-10-21 Cont ID  
Sent By ndenmark Date 2000-10-21 Time 09:22 Rev Time 0.33
Received By ndenmark Date 2000-10-21 Time 09:22 Sent To  
Notes
2001-01-08 00:00:00PROVISO:
 NOTE, ACCESS TO AHU TO FOR SERVICE AND
 REMOVAL OF EQUIPMENT TO BE AS PER 1997
 SMC 304.2 AND 304.4.1

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-10-21 Cont ID  
Sent By tlarge Date 2000-10-21 Time 11:01 Rev Time 1.00
Received By tlarge Date 2000-10-21 Time 10:39 Sent To  
Notes
2001-01-08 00:00:00***************PROVISO******************
 1)DRY VENTS NOT PERMITTED PER SPC SEC.
 906.2.1.(SEE W.C.)
  
 2)WATER HEATERS SHALL NOT INFRINGE ON
 THE CLEARANCES REQD.FOR THE LAV.AND
 WATER CLOSET.FACBC SECS.4.16.,4.19.
  
 CALL IF YOU HAVE QUESTIONS.
 561-659-8096,EXT.8377.
  
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER