| 2001-01-08 00:00:00 | DENIED |
| | |
| | 1)IMPACT FEES MUST BE PAID TO PALM BEACH |
| | COUNTY,PLANS STAMPED BY THEM AND COPY OF |
| | RECEIPT SUBMITTED TO CITY OF W.P.B. |
| | BUILDING DEPT.BEFORE A PERMIT TO |
| | CONSTRUCT WILL BE ISSUED. |
| | |
| | 2)NOTICE OF COMMENCEMENT MUST BE |
| | RECORDED AND FILED WITH CITY BUILDING |
| | DEPT. PRIOR TO PERMIT BEING ISSUED. |
| | |
| | 3)PLEASE PROVIDE 2 COPIES OF ALL ITEMS |
| | SUBMITTED. |
| | |
| | 4)PROVIDE (1) COPY OF SOIL REPORT WITH |
| | WET SIGNATURE, DATE AND IMPRESSION SEAL |
| | OF ENGINEER FOR BUILDING DEPT. FILE. |
| | |
| | 5)PROVIDE 2 CURRENT COPIES OF METRO-DADE |
| | OR SBCCI PRODUCT APPROVALS FOR STEEL |
| | DOOR,SINGLE HUNG WINDOWS AND FIXED GLASS |
| | WINDOWS. PRODUCT APPROVAL SUBMITTED FOR |
| | DOOR HAD EXPIRED AND PROPOSAL FOR |
| | WINDOWS IS NOT ACCEPTABLE. |
| | |
| | 6)PROVIDE INSTALLATION SCHEDULE AND KEY |
| | PLAN WITH SPECIFIC ANCHORS TO BE USED |
| | FOR STORM PANELS PRIOR TO INSTALLATION. |
| | |
| | 7)INDICATE LOCATION OF ATTIC ACCESS AS |
| | REQUIRED BY 97 SBC 2309.6. |
| | |
| | 8)INDICATE ROOF PITCH ON PLANS. |
| | |
| | 9)INDICATE TYPE OF MATERIAL TO BE |
| | INSTALLED ON PORCH AND ENTRY CEILINGS. |
| | |
| | 10)PLEASE CLARIFY STEEL REFRENCE TO |
| | STEEL COLUMN WITH 4500# UPLIFT SHOWN ON |
| | SHEET 6. NOTHING IS INDICATED ON |
| | FOUNDATION PLAN AT THIS LOCATION. |
| | |
| | 11)PROVIDE ADDITIONAL DETAIL FOR |
| | STRUCTURAL STEEL POST FOR PORCH WHICH |
| | SHOWS CONFIGURATION OF CONNECTIONS AT |
| | TOP AND BOTTOM OF POST.INCLUDE TYPE |
| | SIZE AND NUMBER OF FASTENERS. |
| | |
| | 12)PROVIDE 2 COMPLETE SETS OF TRUSS |
| | DRAWINGS AND LAYOUTS. TRUSS LAYOUT IS |
| | REQUIRED TO HAVE WET SIGNATURE,DATE AND |
| | IMPRESSION SEAL OF TRUSS ENGINEER AND BE |
| | REVIEWED AND APPROVED BY DESIGNER OF |
| | STRUCTURE AND SO NOTED ON LAYOUT. |
| | |
| | 13)PLEASE HAVE DESIGNER OF RECORD REVIEW |
| | TRUSS COMPANY LAYOUT AND MAKE REVISIONS |
| | TO SHEET 6 OF PLANS TO ADDRESS ANY |
| | DISCREPANCIES. |
| | |
| | 14)PLEASE REVIEW CONNECTORS ON SHEET 6 |
| | SEVERAL DO NOT MEET THE UPLIFTS REQUIRED |
| | BY TRUSS ENGINEERING.PLEASE USE CURRENT |
| | PRODUCT CATALOGS WHEN SPECIFYING |
| | CONNECTORS. |
| | |
| | 15)HIGHEST MEAN ROOF HEIGHT OF 14'-0" |
| | THE MEAN ROOF HEIGHT OF STRUCTURE IS |
| | 15'-0". HAVE TRUSS ENGINEER CHECK LOAD |
| | CALCULATIONS FOR ADDITIONAL HEIGHT. |