Plan Review Details - Permit 00100495
Plan Review Stops For Permit 00100495
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2000-12-08 Cont ID  
Sent By dpalmer Date 2000-12-08 Time 14:16 Rev Time 0.00
Received By dpalmer Date 2000-12-08 Time 14:16 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2000-12-07 Cont ID  
Sent By dpalmer Date 2000-12-07 Time 16:37 Rev Time 0.00
Received By dpalmer Date 2000-12-07 Time 16:35 Sent To  
Notes
2001-01-08 00:00:00WAITING FOR INFORMATION FOR INTERIOR
 DESIGNER.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-10-31 Cont ID  
Sent By dpalmer Date 2000-10-31 Time 17:49 Rev Time 0.00
Received By dpalmer Date 2000-10-31 Time 17:49 Sent To  
Notes
2001-01-08 00:00:00**************** UNSAT *****************
  
 1)NOTE: PLEASE SEE TITLE BLOCK ON SIDE
 OF PLANS. PLANS NOTE THAT THEY ARE NOT
 VALID WITHOUT SEAL. IS THE PERSON IN
 TITLE BLK AN ARCH/ENGINEER UNDER FLORIDA
 ADMIN. 481.221 OR 481.321 IF SO PLEASE
 PROVIDE SEAL/SIG. PLEASE CLARIFY.
  
 2)NOTE: PLEASE NOTE THAT SMOKE DETECTORS
 ARE REQ`D INSIDE AND OUTSIDE ALL SLEEP-
 -ING ROOMS PER NFPA-72 2-2.1.1.1
  
 3)NOTE: PLEASE SHOW A/C COND UNIT AND
 DISCONNECT PER 440-11 AND SHOW GFI REC
 FOR A/C UNIT.
  
 4)NOTE: PLEASE NOTE MISSING OUTLET PER
 210-52 WALL BY KITCHEN.
  
 5)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL EQUIPMENT BEING INSTALLED. ALL
 MAINS AND PANELS MUST BE RATED FOR THE
 AVAILABLE FAULT CURRENT PER 110-9.
  
 6)NOTE: PLEASE NOTE THAT YOU SHOW ONLY
 PANEL SCHEDULES FOR PANEL"A". PLEASE
 SHOW OTHER PANELS SHOWN. PLEASE SHOW
 CONDUCTOR SIZES AND CONDUIT SIZES,
 PLEASE SHOW HOW THEY ARE BEING FED SINCE
 NOTHING IN PANEL "A" INDICATES FEEDING
 OTHER PANELS???
 ALSO PLEASE SEE LOAD CALCUALTIONS AT THE
 TOP OF PANEL"A".NO SQ FOOTAGE IS SHOWN
 FOR GENERAL LIGHTING CALCS.??
 PLEASE SEE PANEL SCHEDULE AT THE
 BOTTOM FOR LIGHTING LOAD ??? IT SHOWS
 LIGHTS AS 7431. PLEASE SHOW SQ FT.
  
 7)NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-52D AND 210-11-C-3
 MUST BE #12 AND 20A .
  
 8)NOTE: PLEASE SHOW DISC FOR AHU IN CLOS
 -ET.
  
 9)NOTE: PLEASE LABEL OUTLET IN GARAGE AS
 GFI/GFI PROTECTED PER 210-8.
  
 10)NOTE: PLEASE INDICATE WHICH PANELS
 ARE MCB AND MLO.
  
 11)NOTE: PLEASE SEE 250-50 FOR THE REQ`
 MENTS FOR GROUNDING ELECTRODE CONDUCTOR
 GOING TO BLDG STEEL ALSO. PLEASE SHOW
 BLDG STEEL ON RISER WITH CWP.
  
 12)NOTE: PLEASE SEE PLANS,, THERE ARE NO
 CATV AND TELEPHONE OUTLETS SHOWN??
 IS THERE GOING TO BE CATV OR PHONES
 INSTALLED? IF SO THEN ALL LOCATIONS NEED
 TO BE SHOWN ON PLANS.
  
 13)NOTE: PLEASE SHOW OCTAGONS IN BEDROOM
 -S AS FAN/LIGHTS OR DRAW IN. IF THIS IS
 WHATS BEING INSTALLED.
  
 PLEASE SUBMIT ALL THE ABOVE INFORMAITON
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-10-28 Cont ID  
Sent By jleech Date 2000-10-28 Time 13:56 Rev Time 0.33
Received By jleech Date 2000-10-28 Time 13:56 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-06-08 Cont ID  
Sent By kstevens Date 2001-06-08 Time 14:04 Rev Time 0.25
Received By kstevens Date 2001-06-08 Time 14:03 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-10-29 Cont ID  
Sent By tlarge Date 2000-10-29 Time 12:30 Rev Time 0.50
Received By tlarge Date 2000-10-29 Time 12:06 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2000-12-07 Cont ID  
Sent By rmcdouga Date 2000-12-07 Time 14:54 Rev Time 4.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-01-08 00:00:00***************PROVISO******************
  
 1)PROVIDE 2 CURRENT COPIES OF METRO-DADE
 OR SBCCI PRODUCT APPROVALS FOR THE
 FOLLOWING ITEMS:
 -SINGLE HUNG WINDOWS
 -FIXED GLASS WINDOWS
  
 2)PROVIDE INSTALLATION SCHEDULE AND KEY
 PLAN FOR STORM PANELS PRIOR TO INSTALL-
 ATION.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2000-11-16 Cont ID  
Sent By rmcdouga Date 2000-11-16 Time 11:53 Rev Time 4.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-01-08 00:00:00DENIED
  
 1)IMPACT FEES MUST BE PAID TO PALM BEACH
 COUNTY,PLANS STAMPED BY THEM AND COPY OF
 RECEIPT SUBMITTED TO CITY OF W.P.B.
 BUILDING DEPT.BEFORE A PERMIT TO
 CONSTRUCT WILL BE ISSUED.
  
 2)NOTICE OF COMMENCEMENT MUST BE
 RECORDED AND FILED WITH CITY BUILDING
 DEPT. PRIOR TO PERMIT BEING ISSUED.
  
 3)PLEASE PROVIDE 2 COPIES OF ALL ITEMS
 SUBMITTED.
  
 4)PROVIDE (1) COPY OF SOIL REPORT WITH
 WET SIGNATURE, DATE AND IMPRESSION SEAL
 OF ENGINEER FOR BUILDING DEPT. FILE.
  
 5)PROVIDE 2 CURRENT COPIES OF METRO-DADE
 OR SBCCI PRODUCT APPROVALS FOR STEEL
 DOOR,SINGLE HUNG WINDOWS AND FIXED GLASS
 WINDOWS. PRODUCT APPROVAL SUBMITTED FOR
 DOOR HAD EXPIRED AND PROPOSAL FOR
 WINDOWS IS NOT ACCEPTABLE.
  
 6)PROVIDE INSTALLATION SCHEDULE AND KEY
 PLAN WITH SPECIFIC ANCHORS TO BE USED
 FOR STORM PANELS PRIOR TO INSTALLATION.
  
 7)INDICATE LOCATION OF ATTIC ACCESS AS
 REQUIRED BY 97 SBC 2309.6.
  
 8)INDICATE ROOF PITCH ON PLANS.
  
 9)INDICATE TYPE OF MATERIAL TO BE
 INSTALLED ON PORCH AND ENTRY CEILINGS.
  
 10)PLEASE CLARIFY STEEL REFRENCE TO
 STEEL COLUMN WITH 4500# UPLIFT SHOWN ON
 SHEET 6. NOTHING IS INDICATED ON
 FOUNDATION PLAN AT THIS LOCATION.
  
 11)PROVIDE ADDITIONAL DETAIL FOR
 STRUCTURAL STEEL POST FOR PORCH WHICH
 SHOWS CONFIGURATION OF CONNECTIONS AT
 TOP AND BOTTOM OF POST.INCLUDE TYPE
 SIZE AND NUMBER OF FASTENERS.
  
 12)PROVIDE 2 COMPLETE SETS OF TRUSS
 DRAWINGS AND LAYOUTS. TRUSS LAYOUT IS
 REQUIRED TO HAVE WET SIGNATURE,DATE AND
 IMPRESSION SEAL OF TRUSS ENGINEER AND BE
 REVIEWED AND APPROVED BY DESIGNER OF
 STRUCTURE AND SO NOTED ON LAYOUT.
  
 13)PLEASE HAVE DESIGNER OF RECORD REVIEW
 TRUSS COMPANY LAYOUT AND MAKE REVISIONS
 TO SHEET 6 OF PLANS TO ADDRESS ANY
 DISCREPANCIES.
  
 14)PLEASE REVIEW CONNECTORS ON SHEET 6
 SEVERAL DO NOT MEET THE UPLIFTS REQUIRED
 BY TRUSS ENGINEERING.PLEASE USE CURRENT
 PRODUCT CATALOGS WHEN SPECIFYING
 CONNECTORS.
  
 15)HIGHEST MEAN ROOF HEIGHT OF 14'-0"
 THE MEAN ROOF HEIGHT OF STRUCTURE IS
 15'-0". HAVE TRUSS ENGINEER CHECK LOAD
 CALCULATIONS FOR ADDITIONAL HEIGHT.

Review Stop Z ZONING
Rev No 1 Status P Date 2000-10-23 Cont ID  
Sent By sgraham Date 2000-10-23 Time 15:50 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***