Plan Review Details - Permit 00100489
Plan Review Stops For Permit 00100489
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2001-03-27 Cont ID  
Sent By jwitmer Date 2001-03-27 Time 14:24 Rev Time 0.50
Received By jwitmer Date   Time   Sent To  
Notes
2001-03-27 00:00:00REVISIONS: STOREFRONT

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2001-01-25 Cont ID  
Sent By drunnels Date 2001-01-25 Time 14:57 Rev Time 0.25
Received By drunnels Date 2001-01-25 Time 14:55 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2000-10-25 Cont ID  
Sent By drunnels Date 2000-10-25 Time 11:03 Rev Time 1.00
Received By drunnels Date 2000-10-25 Time 11:01 Sent To  
Notes
2001-01-08 00:00:001.SUBMIT PRODUCT APPROVALS FOR IMPACT
 RESISTANCE GLAZING FOR STOREFRONT WINDOW
 AND DOORS/ METRO DADE COUNTY OR SBCCI
 2. SUBMIT FIRE SPRINKLER PLANS AND
 PERMIT APPLICATION
 3.SUBMIT LETTER FROM SPECIAL INSPECTOR
 FOR CITY PLACE
 4. SIGNS TO BE UNDER SEPERATE PERMIT

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2001-03-26 Cont ID  
Sent By dpalmer Date 2001-03-26 Time 15:12 Rev Time 0.00
Received By dpalmer Date 2001-03-26 Time 15:12 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-12-11 Cont ID  
Sent By dpalmer Date 2000-12-11 Time 22:33 Rev Time 0.00
Received By dpalmer Date 2000-12-11 Time 22:33 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-11-01 Cont ID  
Sent By dpalmer Date 2000-11-01 Time 18:39 Rev Time 0.00
Received By dpalmer Date 2000-11-01 Time 18:39 Sent To  
Notes
2001-01-08 00:00:00*****************UNSAT *****************
  
 1)NOTE: PLEASE SUBMIT AIC RATING FOR
 MAIN AND PANEL. PLANS SHOW AIC FOR
 BRANCH BRKRS ONLY. PER 110-9 AND 215-5
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2000-10-16 Cont ID  
Sent By mcarsill Date 2000-10-16 Time 10:22 Rev Time 0.00
Received By mcarsill Date 2000-10-16 Time 10:22 Sent To  
Notes
2001-01-08 00:00:001) NO HYDRAULIC CALCULATIONS PROVIDED
 WITH FIRE SPRINKLER DRAWINGS.
 2) FIRE ALARM STROBE REQUIRED IN
 BATHROOM.
 3) PROVIDE FIRE ALARM SYSTEM SHOP
 DRAWINGS FOR FIRE ALARM EQUIPMENT SHOWN
 ON PLANS.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2000-12-14 Cont ID  
Sent By ndenmark Date 2000-12-14 Time 10:32 Rev Time 0.25
Received By ndenmark Date 2000-12-14 Time 10:32 Sent To  
Notes
2001-01-08 00:00:00SEE ATTACHED LETTER FROM ENGINEER ON
 APPROVED PLANS

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-11-06 Cont ID  
Sent By ndenmark Date 2000-11-06 Time 14:42 Rev Time 0.33
Received By ndenmark Date 2000-11-06 Time 14:42 Sent To  
Notes
2001-01-08 00:00:00PROVISO:
 1.PLEASE PROVIDE LETTER DETAILING
 ATTACHMENT OF AHU TO CEILING AND C/U TO
 EQUIPMENT RACK ON ROOF
 2.1997 SMC 304.4.1 REQUIRES THE OPENING
 AND PASSAGEWAY TO BE AT LEAST AS LARGE
 AS THE LARGEST PIECE OF THE EQUIPMENT
 AND IN NO CASE LESS THAN 22 X 36 INCHES.
 3.A MINIMUM OF 18" CLEARANCE IS REQUIRED
 BETWEEN THE ROOF SURFACE AND THE BOTTOM
 OF THE SUPPORT STRUCTURE OF THE EQUIPMEN

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-01-25 Cont ID  
Sent By drunnels Date 2001-01-25 Time 15:32 Rev Time 0.00
Received By drunnels Date   Time   Sent To  
Notes
2001-01-25 00:00:00APPROVED PER PAUL SCHMITZ

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-10-18 Cont ID  
Sent By tlarge Date 2000-10-18 Time 07:45 Rev Time 0.50
Received By tlarge Date 2000-10-18 Time 07:45 Sent To  
Notes
2001-01-08 00:00:001)SINK SHALL COMPLY W/FACBC SECS.4.24.1-
 4.24.7.
  
 2)DOOR OF TOILET ROOM SHALL NOT SWING
 INTO THE CLEAR FLOOR REQD.FOR SINK.
 FACBC SEC.4.22.2
  
 3)SHOW REQD.CLEAR FLOOR SPACE FOR SINK
 ON PLAN.
  
 4)SHOW WATER SUPPLY TO SINK ON WATER
 RISER.
  
 5)TOILET ROOM SHALL BE ACCESSIBLE TO
 PATRONS.SEE ATTACHED.
  
 CALL IF YOU HAVE QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.