| Plan Review Stops For Permit 00100489 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2001-03-27 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-03-27 |
Time |
14:24 |
Rev Time |
0.50 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-03-27 00:00:00 | REVISIONS: STOREFRONT |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2001-01-25 |
|
|
Cont ID |
|
| Sent By |
drunnels |
Date |
2001-01-25 |
Time |
14:57 |
Rev Time |
0.25 |
| Received By |
drunnels |
Date |
2001-01-25 |
Time |
14:55 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2000-10-25 |
|
|
Cont ID |
|
| Sent By |
drunnels |
Date |
2000-10-25 |
Time |
11:03 |
Rev Time |
1.00 |
| Received By |
drunnels |
Date |
2000-10-25 |
Time |
11:01 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1.SUBMIT PRODUCT APPROVALS FOR IMPACT | | | RESISTANCE GLAZING FOR STOREFRONT WINDOW | | | AND DOORS/ METRO DADE COUNTY OR SBCCI | | | 2. SUBMIT FIRE SPRINKLER PLANS AND | | | PERMIT APPLICATION | | | 3.SUBMIT LETTER FROM SPECIAL INSPECTOR | | | FOR CITY PLACE | | | 4. SIGNS TO BE UNDER SEPERATE PERMIT |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2001-03-26 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-03-26 |
Time |
15:12 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-03-26 |
Time |
15:12 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2000-12-11 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-12-11 |
Time |
22:33 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-12-11 |
Time |
22:33 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2000-11-01 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-11-01 |
Time |
18:39 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-11-01 |
Time |
18:39 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | *****************UNSAT ***************** | | | | | | 1)NOTE: PLEASE SUBMIT AIC RATING FOR | | | MAIN AND PANEL. PLANS SHOW AIC FOR | | | BRANCH BRKRS ONLY. PER 110-9 AND 215-5 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2000-10-16 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-10-16 |
Time |
10:22 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2000-10-16 |
Time |
10:22 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1) NO HYDRAULIC CALCULATIONS PROVIDED | | | WITH FIRE SPRINKLER DRAWINGS. | | | 2) FIRE ALARM STROBE REQUIRED IN | | | BATHROOM. | | | 3) PROVIDE FIRE ALARM SYSTEM SHOP | | | DRAWINGS FOR FIRE ALARM EQUIPMENT SHOWN | | | ON PLANS. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2000-12-14 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-12-14 |
Time |
10:32 |
Rev Time |
0.25 |
| Received By |
ndenmark |
Date |
2000-12-14 |
Time |
10:32 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | SEE ATTACHED LETTER FROM ENGINEER ON | | | APPROVED PLANS |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2000-11-06 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-11-06 |
Time |
14:42 |
Rev Time |
0.33 |
| Received By |
ndenmark |
Date |
2000-11-06 |
Time |
14:42 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PROVISO: | | | 1.PLEASE PROVIDE LETTER DETAILING | | | ATTACHMENT OF AHU TO CEILING AND C/U TO | | | EQUIPMENT RACK ON ROOF | | | 2.1997 SMC 304.4.1 REQUIRES THE OPENING | | | AND PASSAGEWAY TO BE AT LEAST AS LARGE | | | AS THE LARGEST PIECE OF THE EQUIPMENT | | | AND IN NO CASE LESS THAN 22 X 36 INCHES. | | | 3.A MINIMUM OF 18" CLEARANCE IS REQUIRED | | | BETWEEN THE ROOF SURFACE AND THE BOTTOM | | | OF THE SUPPORT STRUCTURE OF THE EQUIPMEN |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2001-01-25 |
|
|
Cont ID |
|
| Sent By |
drunnels |
Date |
2001-01-25 |
Time |
15:32 |
Rev Time |
0.00 |
| Received By |
drunnels |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-25 00:00:00 | APPROVED PER PAUL SCHMITZ |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2000-10-18 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-10-18 |
Time |
07:45 |
Rev Time |
0.50 |
| Received By |
tlarge |
Date |
2000-10-18 |
Time |
07:45 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1)SINK SHALL COMPLY W/FACBC SECS.4.24.1- | | | 4.24.7. | | | | | | 2)DOOR OF TOILET ROOM SHALL NOT SWING | | | INTO THE CLEAR FLOOR REQD.FOR SINK. | | | FACBC SEC.4.22.2 | | | | | | 3)SHOW REQD.CLEAR FLOOR SPACE FOR SINK | | | ON PLAN. | | | | | | 4)SHOW WATER SUPPLY TO SINK ON WATER | | | RISER. | | | | | | 5)TOILET ROOM SHALL BE ACCESSIBLE TO | | | PATRONS.SEE ATTACHED. | | | | | | CALL IF YOU HAVE QUESTIONS. | | | TIMOTHY LARGE | | | PLUMBING PLANS EXAMINER. |
|
|