Plan Review Details - Permit 00100488
Plan Review Stops For Permit 00100488
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2001-03-27 Cont ID  
Sent By jwitmer Date 2001-03-27 Time 14:24 Rev Time 0.50
Received By jwitmer Date   Time   Sent To  
Notes
2001-03-27 00:00:00REVISIONS: STOREFRONT

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2001-01-25 Cont ID  
Sent By drunnels Date 2001-01-25 Time 15:00 Rev Time 0.25
Received By drunnels Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2000-10-25 Cont ID  
Sent By drunnels Date 2000-10-25 Time 10:33 Rev Time 1.00
Received By drunnels Date 2000-10-25 Time 10:33 Sent To  
Notes
2001-01-08 00:00:001. SUBMIT PRODUCT APPROVAL FOR IMPACT
 RESISTENT GLAZING ON STOREFRONT WINDOWS
 AND DOORS/METRO DADE COUNTY OR SBCCI
 2.SUBMIT FIRESPRINKLER PLANS AND PERMIT
 APPLICATION
 3.SUBMIT LETTER FROM SPECIAL INSPECTOR
 FOR CITY PLACE

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2001-03-26 Cont ID  
Sent By dpalmer Date 2001-03-26 Time 14:55 Rev Time 0.00
Received By dpalmer Date 2001-03-26 Time 14:55 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-12-11 Cont ID  
Sent By dpalmer Date 2000-12-11 Time 22:29 Rev Time 0.00
Received By dpalmer Date 2000-12-11 Time 22:29 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-11-01 Cont ID  
Sent By dpalmer Date 2000-11-01 Time 17:37 Rev Time 0.00
Received By dpalmer Date 2000-11-01 Time 17:37 Sent To  
Notes
2001-01-08 00:00:00************** UNSAT *******************
  
 1)NOTE:PLEASE NOTE THAT THE AIC RATING
 FOR BRKRS INSATLLED IN PANEL SHOWS
 THEM AT 10,000A. THIS IS FINE BUT NO
 AIC RATINGS WERE SUBMITTED FOR MAIN
 DISCONNECT. PLEASE SUBMIT AIC RATING FOR
 MAIN DISC. PLANS WOULD HAVE PASSED WITH
 PROVISO BUT WERE COMING BACK FOR OTHER
 COMMENTS.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2000-11-28 Cont ID  
Sent By mcarsill Date 2000-11-28 Time 15:07 Rev Time 0.00
Received By mcarsill Date 2000-11-28 Time 15:06 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2000-10-16 Cont ID  
Sent By mcarsill Date 2000-10-16 Time 15:12 Rev Time 0.00
Received By mcarsill Date 2000-10-16 Time 15:12 Sent To  
Notes
2001-01-08 00:00:001) NO HYDRAULIC CALCULATIONS PROVIDED
 WITH FIRE SPRINKLER DRAWINGS.
 2) A FIRE ALARM STROBE IS NEEDED IN
 THE TOILET ROOM.
 3) AN EXIT SIGN IS NEEDED ABOVE THE
 REAR EXIT DOOR.
 4) WHAT TYPE OF MATERIAL IS THE CURTAIN
 AND IS IT FLAMMABLE.
 5) EXITING THROUGH THE STOCKROOM IS
 PERMITTED IF THE FOLLOWING CONDITIONS
 ARE MET, AN AISLE OF AT LEAST 44" IS
 TO BE PROVIDED AND MAINTAINED

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2000-12-14 Cont ID  
Sent By ndenmark Date 2000-12-14 Time 10:29 Rev Time 0.25
Received By ndenmark Date 2000-12-14 Time 10:29 Sent To  
Notes
2001-01-08 00:00:00SEE ATTACHED LETTER FROM ENGINEER

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-11-06 Cont ID  
Sent By ndenmark Date 2000-11-06 Time 14:27 Rev Time 0.33
Received By ndenmark Date 2000-11-06 Time 14:27 Sent To  
Notes
2001-01-08 00:00:00PROVISO:
 1. LETTER FROM ENGINEER DETAILING
 ATTACHEMENT OF C/U TO STAND AND AHU TO
 CEILING TO FOLLOW PRIOR TO INSPECTION
 ON EQUIPMENT
 2. MINIMUM CLEARANCE BETWEEN ROOF SURFAC
 AND BOTTOM OF SUPPORT STRUCTURE OF EQUIP
 STAND IN 18".
 3. 250 CFM SUPPLY AIR SHOWN ON RETURN
 SIDE OF AHU IS RETURN AIR NOT SUPPLY
 PER D. ROMCKE

Review Stop P PLUMBING
Rev No 2 Status P Date 2000-12-10 Cont ID  
Sent By pschmitz Date 2000-12-10 Time 08:00 Rev Time 1.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-01-08 00:00:00PLUMBING PLAN REVIEWPROVISO
 PREVIOUS COMMENTS NOT ADDRESSED.
 (1) SHT A2-SINK TO COMPLY W/ FACBC
 SEC 4.24.1 NO HIGHER 34" ABOVE FF.
 SEC 4.24.1 KNEE CLEARANCE 27" HIGH.
 30" WIDE, 19" DEEP,SHALL BE PROVIDED.
 SEC. 4.24.5 CLEAR FLR SPACE 30" X 48".
 (2) SEC 4.1.3 (16) (A) SIGNAGE H/C.
 (3) SHT MP-1 AIR CHAMBERS SEC 607.8.3
 TO BE ACCESSIBLE, RECHARGEABLE.
 END OF COMMENTS PAUL SCHMITZ
 561-659-8096 X 8233

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-10-21 Cont ID  
Sent By tlarge Date 2000-10-21 Time 11:20 Rev Time 0.33
Received By tlarge Date 2000-10-21 Time 11:20 Sent To  
Notes
***NONE***