Plan Review Details - Permit 00100464
Plan Review Stops For Permit 00100464
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2000-12-12 Cont ID  
Sent By lmartine Date 2000-12-12 Time 16:00 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
2001-01-08 00:00:00BUILDING COMMENTS
 -------------------
  
 1]
 PROVIDE SIGNED AND SEALED SURVEYS.
 2]
 ALL NOTES SHALL REFER TO STANDARD BUILD-
 CODE 1997 EDITION,NOT SFBC OR UBC.
 3]
 ADDITIONAL FEES DUE ARE COUNTY IMPACT &
 CITY RADON.
 4]
 NORTH ELEVATION WALL,PROVIDE 2HR WALL
 ASSEMBLY,TABLE 600 REQUIREMENT.
 5]
 REMOVE ANY AND ALL DETAILS THAT DO NOT
 APPLY TO THIS SITE.
 6]
 SUBMIT PRODUCT TEST REPORTS FOR ALL
 EXTERIOR GLAZING ,DOORS AND ROOF COVER.
 7]
 ANY ARCHITECTURAL TRIM ON EXTERIOR IF OF
 WOOD SHALL BE FIRE RETARTANT TREATED,SEE
 F.102.2.7,SBC.
 8]
 PARAPETS SHALL BE CONSTRUCTED OF NON-
 COMBUSTIBLE MATERIAL.
  
  
 REVIEWED BY:
 LUIS MARTINEZ
 561-659-8096
 #8456

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-11-21 Cont ID  
Sent By dpalmer Date 2000-11-21 Time 11:08 Rev Time 0.00
Received By dpalmer Date 2000-11-21 Time 11:08 Sent To  
Notes
2001-01-08 00:00:00*************** UNSAT *****************
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL EQUIPMENT BEING INSTALLED. THIS
 IS REQ`D PER 215-5 AND MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
 MIN RATING MAY BE PUT ON PLANS TO COVER
 UNKNOWN OR CALLS MAY BE PLACED TO FPL
 FOR AVAILABLE FAULT CURRENT.
  
 PLEASE SUBMIT THE ABOVE INFOMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2000-11-27 Cont ID  
Sent By mgonzale Date 2000-11-27 Time 09:00 Rev Time 1.00
Received By mgonzale Date   Time   Sent To  
Notes
2001-01-08 00:00:00UNSAT, WITH COMMENTS:
 SHEET C2
 ANY WORK PERFORMED OUTSIDE OF SITE
 ALONG THE OKEECHOBEE ROW REQUIRES A DOT
 ROW PERMIT.
 SHEET C-3
 THE DUMPSTER ENCLOSURE MUST HAVE MINIMUM
 OPENINGS OF 12'-6" SO THAT TRASH IS
 ACCESSIBLE TO CITY SANITATION DEPT.
 THERE IS NOT SCALE LISTED ANY WHERE
 VISIBLE PLEASE CLARIFY TYP. ON ALL SHTS.
 SHEET C4
 PLEASE SHOW SILT FENCE AROUND THE
 ENTIRE SITE ASMARKED.
 ADD NOTE TO BALES DETAIL
 NOTE: BALES MUST BE PROVIDED AROUND
 CATCH BASINS AND MANHOLES TO CONTROL
 POLLUTION.
 TOTAL PERVIOUS AND IMPERVIOUS TALLY
 MUST BE LISTED ALONG WITH THE SITE
 TOTAL S.F. AND ACREAGE. AN ADDRESS OR
 PROPERTY CONTROL NUMBER MUST BE STATED.
 THE SITE STORM CHARGES WILL BE CALCULATE
 D FROM THESE NUMBERS.
 DRAINAGE CALCULATIONS MUST BE SUBMITTED
 TO STORM WATER ENGINEER FOR APPROVAL
 JOSE DEL RIOS, STORM WATER DIVISION
 (561) 659 8040.
 I HAVE ATTACHED A STORM REQUIREMENT SHT.
 SHEET C-6
 CITY OF WEST PALM BEACH STANDARD DETAILS
 MUST MUST BE SHOWN ON THIS PLAN. THEY
 MAY BE REQUESTED TO EMAIL
 [email protected]
 SHEET TP-1
 WHERE NEW AND EXISTING SERVICES EXIST.
 PROPOSED LARGE TREES MUST STAY 5'AWAY
 MIN.
 PLEASE IDENTIFY EXISTING METERS AT
 CORNER OF PROPERTY.TO REMAIN?TO BE REM
 OVED? TO BE RELOCATED? OWNER?
 SHOW EXISTING WM WHERE 1" IRRIGATION
 METER SERVICE WILL CONNECTTO AND
 SHOW SIXE AND MATERIAL.
 THE TWO INCH WATER SERVICE IS APPROX.
 320 L.F. TO THE BUILDING, PLEASE VERIFY
 IF THIS REQUIRES A HEALTH DEPARTMENT
 PERMIT.
 NO WATER SERVICE OR DRAINAGE ALLOWED
 IN UNCOVERED DUMPSTER AREAS.REASON:RAIN
 WATER WILL DRAIN INTO SANITARY SYSTEM.
 NEW SANITARY SEWER LINE MUST STAY OUT
 OF RETENTION AREA TO ALLOW MINIMUM
 COVER.
 NO SCALE SHOWN ON THIS SHEET.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2000-10-24 Cont ID  
Sent By mcarsill Date 2000-10-24 Time 11:26 Rev Time 0.00
Received By rturnque Date 2000-10-24 Time 11:26 Sent To  
Notes
2001-01-08 00:00:001) PLEASE CLEARLY INDICATE FIRE HYDRANT
 LOCATIONS ON OR NEAR THE SITE.
 2) PLEASE CLEARLY INDICATE EMERGENCY
 LIGHT FIXTURE LOCATIONS ON PLANS.
 3) BUILDING ADDRESS NOT SHOWN ON
 ELEVATION DRAWINGS. BUILDING ADDRESS TO
 COMPLY WITH CITY CODE REQUIREMENTS.
 4) SERVICE STATION TO COMPLY WITH NFPA
 30A, THE STANDARD FOR AUTOMOTIVE AND
 MARINE SERVICE STATION CODE, AND UNIFORM
 FIRE SAFETY RULES AND STANDARDS,
 CHAPTER 4A-49.
 5) THE UNDERGROUND FUEL TANKS TO COMPLY
 WITH NFPA 30, THE STANDARD FOR THE
 STORAGE AND HANDLING OF COMBUSTIBLE
 LIQUIDS.
 6) PLEASE INDICATE ON THE PLANS, THE
 LENGTHS OF FUEL HOSES PLANNED FOR USE.
 7) PLEASE IDENTIFY TYPE SIGNAGE FOR
 EMERGENCY SHUT-OFF FOR FUEL DISPENSING
 EQUIPMENT.
 8) PLEASE IDENTIFY THE LOCATIONS FOR
 WARNING SIGNS AT THE FUEL DISPENSING
 EQUIPMENT. WHAT WORDING IS PLANNED FOR
 THESE SIGNS.
 9) PLEASE PROVIDE LISTING INFORMATION
 ON DEVICES PLANNED FOR USE AT FUEL
 DISPENSING AREA.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2000-11-27 Cont ID  
Sent By ndenmark Date 2000-11-27 Time 15:08 Rev Time 0.50
Received By ndenmark Date 2000-11-27 Time 15:08 Sent To  
Notes
2001-01-08 00:00:00****************DENIED******************
 1. DUCTS PENETRATING RATED WALLS AT
 STORAGE ROOM TO HAVE FIRE DAMPERS PER
 1997 SMC 610.1.2. LOCATION AND INSTALLA-
 TION SHALL BE SHOWN ON THE DRAWINGS BY
 THE DESIGNER PER 1997 SMC 610.6.
 2. PROVIDE INFORMATION ON EQUIPMENT TO
 BE SERVED BY HOOD (FOOD TO BE COOKED,
 CORE TEMP. OF FOOD, VENT OR EXHAUST REQ-
 UIREMENTS OF EQUIPMENT, ETC.)
 3. NOTE: SEPARATE PERMITS REQUIRED FOR
 FUEL SYSTEM. SUBMIT 2 SETS OF PLANS
 ALREADY APPROVED BY DERM AT TIME OF
 PERMIT APPLICATION FOR THIS WORK.
 4. NOTE: SEPARATE PERMITS REQUIRED FOR
 WALKIN COOLERS/FREEZERS AND HOOD INSTALL
 ATION. SUBMIT PLANS AT TIME OF PERMIT
 APPLICATION FOR THESE SYSTEMS PRIOR TO
 ANY WORK BEING DONE.

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-10-29 Cont ID  
Sent By tlarge Date 2000-10-29 Time 11:20 Rev Time 1.75
Received By tlarge Date 2000-10-29 Time 10:06 Sent To  
Notes
2001-01-08 00:00:001)SUBMIT DETAIL OF GREASE TRAP.SHT.C-2
 REFERS TO C-5 FOR DETAIL AND NO DETAIL
 IS SHOWN.SEE ATTACHED FOR CITY OF WPB
 REQS.COUNTYWIDE AMENDMENTS TO SPC.
 104.2.1.
  
 2)CLARIFY WATER SOURCE FOR IRRIGATION
 SYSTEM.PLANS SHOW WATER METER AND ALSO
 A WELL.A WATER USE PERMIT FROM SFWMD IS
 REQD.AND A WELL PERMIT FROM PB COUNTY
 HEALTH DEPT.IF SUPPLIED BY A WELL.
 F.S.373.219.
  
 3)VENT FOR DUMPSTER DRAINS SHALL BE A
 MIN.OF 2",NOT 1 1/2" PER SPC SEC.920.2.
 (SEE SHT.TP-1)
  
 4)SHTS.SP-1,SP-2-DELETE REFERENCES TO
 UNIFORM PLUMBING CODE AND INSERT
 STANDARD PLUMBING CODE.COUNTYWIDE AMEND-
 MENTS TO SPC SEC.101.1
  
 5)SUBMIT RISER DIAGRAM FOR ROOF DRAINAGE
 AND OVERFLOW.COMPLY W/SPC TABLES 1108.1,
 1108.2 FOR PRIMARY SYSTEM AND SPC SEC.
 1109.2,1109.3.SUBMIT CALCULATIONS FOR
 REVIEW.
  
 6)FLEXIBLE PIPING IS NOT PERMITTED FOR
 TYPE OF INSTALLATION SHOWN.COMPLY W/SPC
 SEC.1104 AND TABLE 703.(SEE SHT.A2.1,
 DETAIL #1.
  
 7)SHT.P1.0-PLBG.SPECS.-NOTE #2-DELETE
 REFERENCE TO SFBC AND ALSO IN PLUMBING
 NOTES #1,4,7.
  
 8)SHT.P1.0-MIN.SIZE PAN DRAIN SHALL BE
 1" PER SPC SEC.507.8.2.
  
 9)HEAT TRAPS ARE REQD.ON THE WATER
 HEATER PER FL.ENERGY CODE SEC.
 412.1 ABCD.2.2.
  
 10)WATER HEATER SHALL BE READILY ACCESS-
 IBLE PER SPC SEC.501.7.
  
 11)WATER FILTRATION SYSTEM SHALL BE NSF
 APPROVED PER SPC SEC.615.1.
  
 12)SUBMIT A CLEAR AND LEGIBLE SANITARY
 AND WATER RISER DIAGRAM FOR REVIEW.SIZE
 ALL SECTIONS OF THE RISERS.COUNTYWIDE
 AMENDMENTS TO SPC SEC.104.2.1.INCLUDE
 THE WATER AND SANITARY LINES FOR THE
 DUMPSTER.SHOW SANITARY AND GREASE LINES
 0N THE PLAN VIEW.ONLY 1 IS SHOWN.DESIGN
 SHALL COMPLY W/SPC.
  
 13)SHOW WATER LINE TO DUMPSTER AREA ON
 WATER RISER.
  
 CALL IF YOU HAVE QUESTIONS.
 561-659-8096,EXT.8377.
  
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.

Review Stop Z ZONING
Rev No 1 Status P Date 2000-12-08 Cont ID  
Sent By lmartine Date 2000-12-08 Time 14:59 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
2001-01-08 00:00:00APPROVED BY ANGELA JONES 12/8/00