| Plan Review Stops For Permit 00100247 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2001-03-05 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2001-03-05 |
Time |
14:01 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2000-11-06 |
|
|
Cont ID |
|
| Sent By |
drunnels |
Date |
2000-11-06 |
Time |
11:11 |
Rev Time |
2.00 |
| Received By |
drunnels |
Date |
2000-11-06 |
Time |
11:11 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1.PROVIDE PRODUCT APPROVALS FOR WINDOWS, | | | DOORS AND ROOF COVERINGS ON ALL | | | STRUCTURES | | | 2.PROVIDE DETAILS SHOWING CONCESSION | | | BUILDING COMPLYING WITH THE FLORIDA | | | ACCESSIBILITY CONE FOR BUILDING CONSTRU- | | | CTION 1997 EDITION | | | 3. PROVIDE ENGINEERING SHOWING DUG OUT, | | | AND SCOREBOARD COMPLYING WITH CHAPTER 16 | | | 1997 EDITION SBC | | | 4.PROVIDE FOOTING DETAILS FOR THE | | | CONCESSION BUILDING | | | 5.IF THE FOOTING AND FOUNDATION FOR | | | PAVILION IS IN THIS CONTRACT PLEASE | | | PROVIDE PLANS AND DETAILS. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2001-04-02 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-04-02 |
Time |
08:57 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-04-02 |
Time |
08:57 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2001-02-28 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-02-28 |
Time |
10:12 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-02-28 |
Time |
10:12 |
Sent To |
|
|
| Notes |
| 2001-02-28 00:00:00 | ************* UNSAT ************ | | | | | | 1)NOTE: PLEASE SEE SHEET 2 OF 4 THIS IS | | | SHOWING A NEW ELECTRICAL SERVICE AND | | | 3 OF 4 SAYS EXISTING? | | | | | | 2)NOTE: PLEASE NOTE LOAD CALCULATIONS | | | FOR MAIN SERVICE WAS NOT SUBMITTED SHOW- | | | ING ALL CONTINUOUS LOADS AT 125%. | | | | | | 3)NOTE: PLEASE SEE 3 OF 4 "PLAN NOTES" | | | #3 SHOWS 4-1/0`S AND #6G. THIS IS SHOWN | | | AS A 1PHASE SERVICE. PLEASE CLARIFY. | | | | | | 4)NOTE:PLEASE NOTE THAT ALL ELECTRICAL | | | POWER FEEDING PAVILLIONS REQ MEANS OF | | | DISCONNECT PER 225-31. | | | | | | PLEASE SUBMIT THE ABOVE CLARIFICATION | | | AND INFORMATION FOR REVIEW. IF THERE ARE | | | ANY QUESTIONS OR IF CORRECTIONS CAN BE | | | TAKEN CARE OF IN PERSON, PLEASE CALL | | | TO SSET UP A TIME FOR A MEETING. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2000-10-31 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-10-31 |
Time |
19:15 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-10-31 |
Time |
19:15 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | **************** UNSAT ***************** | | | | | | 1)NOTE: PLEASE SUBMIT LOAD CALCULATIONS | | | SHOWING ALL CONTINUOUS LOADS AT 125% | | | LIGHTING ETC.SHEET E-3 OF 4 SHOWS CON- | | | -CESSION PANEL AS BEING BY OTHERS?? | | | PLEASE SUBMIT CLARIFICATION? | | | PANEL FOR CONCESSION BLDG IS ON 4 OF 4? | | | CONTINUOUS LOADS FOR PANEL "L" ALSO. | | | | | | 2)NOTE: PLEASE SEE NOTE #3 NOTE DESCRIBE | | | -S 4-1/0`S FOR FEED TO PANEL"L". SHOWS | | | MAIN BREAKER AT 60AMPS. PLEASE CALRIFY | | | 1/0 WIRE SIZE INTO 60A BRKR. | | | | | | 3)NOTE: PLEASE SEE 110-26 AND 384-7 FOR | | | PANEL REQ`MENTS IN A "STORAGE ROOM". | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 659-8096 EXT 8372 |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
P |
Date |
2000-11-08 |
|
|
Cont ID |
|
| Sent By |
mgonzale |
Date |
2000-11-08 |
Time |
14:38 |
Rev Time |
1.00 |
| Received By |
mgonzale |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | APPROVED |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2000-10-25 |
|
|
Cont ID |
|
| Sent By |
rturnque |
Date |
2000-10-25 |
Time |
10:23 |
Rev Time |
0.30 |
| Received By |
rturnque |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2000-10-30 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-10-30 |
Time |
17:07 |
Rev Time |
0.25 |
| Received By |
ndenmark |
Date |
2000-10-30 |
Time |
17:07 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | MECHANICAL PERMIT REQUIRED FOR MECHANICA | | | WORK |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2000-11-08 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2000-11-08 |
Time |
10:58 |
Rev Time |
1.00 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PROVISO FOR PLUMBING | | | (1) FLR DRAINS ARE REQUIRED IN PUBLIC | | | REST RM'S SEC 409.4.1.1 | | | (2) AIR CHAMBERS TO COMPLY WITH | | | SEC 607.8.2 TO BE ACCESIBLE, RECHARGEABL | | | END OF COMMENTS QUESTIONS CALL | | | PAUL SCHMITZ 561-659-8096 X 8233 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2000-10-21 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-10-21 |
Time |
10:21 |
Rev Time |
2.25 |
| Received By |
tlarge |
Date |
2000-10-21 |
Time |
10:21 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1)A WATER USE PERMIT IS REQD.FROM SO.FLA | | | WATER MNGMT.DIV.FOR THE IRRIGATION | | | SYSTEM PER F.S.373.219.SUBMIT COPY OF | | | PERMIT. | | | | | | 2)A WELL DRILLING PERMIT WILL ALSO BE | | | REQD.FROM SFWMD AND P.B.COUNTY HEALTH | | | DEPT.COUNTYWIDE AMENDMENTS TO SPC SEC. | | | 101.4.7. | | | | | | 3)FLOOR DRAINS ARE REQD.IN THE TOILET | | | ROOMS PER SPC SEC.409.4.1.1. | | | | | | 4)DOOR SHALL NOT SWING INTO THE CLEAR | | | FLOOR SPACE REQD.FOR THE DRINKING | | | FOUNTAINS.(A MIN.30"X48"CLEAR SPACE IS | | | REQD.FACBC SEC.4.15.5. | | | | | | 5)SHT.P-1-NOTE #5-CALCULATED AIR CHAMBER | | | SHALL COMPLY W/STANDARD PDI-WH201.SPC | | | SEC.607.8.2. | | | | | | 6)SHOW SINK AND DRINKING FOUNTAIN ON | | | WATER RISER ON SHT.P-1.COUNTYWIDE AMEND- | | | MENT TO SPC SEC.104.2.1. | | | | | | CALL IF YOU HAVE QUESTIONS. | | | TIMOTHY LARGE | | | PLUMBING PLANS EXAMINER. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2000-10-19 |
|
|
Cont ID |
|
| Sent By |
gjoyce |
Date |
2000-10-19 |
Time |
13:28 |
Rev Time |
0.15 |
| Received By |
gjoyce |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|