Plan Review Details - Permit 00100039
Plan Review Stops For Permit 00100039
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2000-10-25 Cont ID  
Sent By drunnels Date 2000-10-25 Time 08:34 Rev Time 1.00
Received By drunnels Date 2000-10-25 Time 08:34 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2000-11-02 Cont ID  
Sent By dpalmer Date 2000-11-02 Time 08:34 Rev Time 0.00
Received By dpalmer Date 2000-11-02 Time 08:34 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-10-16 Cont ID  
Sent By dpalmer Date 2000-10-16 Time 20:52 Rev Time 0.00
Received By dpalmer Date 2000-10-16 Time 20:51 Sent To  
Notes
2001-01-08 00:00:00**************** UNSAT ***************
  
 1)NOTE: NOT ENOUGH ELECTRICAL DETAIL FOR
 REVIEW. NO BRANCH CIRCUIT SIZES?
 WHERE ARE CIRCUIT(S) COMING FROM??
 WHAT SIZE TRANSFORMER IS BEING INSTALLED
 ???? LOAD??
 IS THERE ONLY LIMITED CIRCUIT(S) COMING
 IN TO KIOSK? WHERE IS POWER COMING??
 KIOSK MUST HAVE CIRCUIT(S) LABELED
 SHOWING WHERE POWER IS COMING FROM.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 561-659-8096 EXT 8372
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2000-10-06 Cont ID  
Sent By mcarsill Date 2000-10-06 Time 10:23 Rev Time 0.00
Received By mcarsill Date 2000-10-06 Time 10:23 Sent To  
Notes
***NONE***