Plan Review Details - Permit 00100022
Plan Review Stops For Permit 00100022
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2001-02-22 Cont ID  
Sent By fknapp Date 2001-02-22 Time 14:13 Rev Time 2.00
Received By fknapp Date 2001-02-22 Time 14:13 Sent To  
Notes
2001-02-22 00:00:00 
  
 ************BUILDING PROVISO************
  
 SBC 104.2.2
  
 1) PROVIDE STORM PANEL INFORMATION WITH
 INSTALLATION SCHEDULE AND KEY PLAN WITH
 SPECIFIC ANCHORS AND MOUNTING TO BE USED
 FOR ALL NON-IMPACT GLAZING UNDER
 SEPARATE PERMIT.
  
 ANY QUESTIONS PLEASE CALL,
 FRANK KNAPP
 BUILDING PLAN REVIEW
 DEPARTMENT OF CONSTRUCTION SERVICES
 CITY OF WEST PALM BEACH
 (561) 659-8096 EXT. 8392

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2001-02-08 Cont ID  
Sent By fknapp Date 2001-02-08 Time 11:53 Rev Time 2.00
Received By fknapp Date 2001-02-08 Time 11:53 Sent To  
Notes
2001-02-08 00:00:00 
  
 *************BUILDING UNSAT*************
  
 SBC 104.2.2
  
 1) PROVIDE PLANS THAT SHOW COMPLETE
 DETAILS OF WORK TO BE DONE WITH MATERIAL
 TO BE USED.
  
 2) PROVIDE 2 CURRENT COMPLETE COPIES OF
 SBCCI OR METRO DADE PRODUCT APPROVALS
 FOR ALL NEW WINDOWS AND EXTERIOR DOORS.
  
 3) PROVIDE STORM PANEL INFORMATION WITH
 INSTALLATION SCHEDULE AND KEY PLAN WITH
 SPECIFIC ANCHORS AND MOUNTING TO BE USED
 FOR ALL NON-IMPACT GLAZING.
  
 4) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 5) PROVIDE HISTORIC APPROVAL BEFORE
 PERMIT CAN BE ISSUED.
  
 ANY QUESTIONS PLEASE CALL,
 FRANK KNAPP
 BUILDING PLAN REVIEW
 DEPARTMENT OF CONSTRUCTION SERVICES
 CITY OF WEST PALM BEACH
 (561) 659-8096 EXT. 8392

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2000-10-25 Cont ID  
Sent By fknapp Date 2000-10-25 Time 11:15 Rev Time 2.00
Received By fknapp Date 2000-10-25 Time 11:15 Sent To  
Notes
2001-01-08 00:00:00 
  
  
 ************BUILDING UNSAT**************
  
 SBC 104.2.2
  
 1)PROVIDE PLANS THAT SHOW COMPLETE
 DETAILS OF WORK TO BE DONE WITH MATERIAL
 TO BE USED.
  
 2)PROVIDE 2 CURRENT COMPLETE COPIES OF
 SBCCI OR METRO DADE PRODUCT APPROVALS
 FOR ALL NEW EXTERIOR DOORS AND WINDOWS.
  
 3)PROVIDE STORM PANEL INFORMATION WITH
 KEY PLAN AND INSTALLATION SCHEDULE WITH
 SPECIFIC ANCHORS AND MOUNTING TO BE USED

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2001-02-22 Cont ID  
Sent By dpalmer Date 2001-02-22 Time 07:31 Rev Time 0.00
Received By dpalmer Date 2001-02-22 Time 07:31 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2001-02-12 Cont ID  
Sent By dpalmer Date 2001-02-12 Time 07:55 Rev Time 0.00
Received By dpalmer Date 2001-02-12 Time 07:55 Sent To  
Notes
2001-02-12 00:00:00******************* UNSAT **************
  
  
 1)NOTE: PLEASE NOTE PLANS FIRST CAME IN
 WITH MINOR ELECTRICAL WORK BEING DONE
 INONLY LIMITED AREAS. NOW PLANS SHOW
 COMPLETE RE-WIRING OF HOUSE. THE PLANS
 WERE
 ORIGINALLY PASSED WITH A "PROVISO"
 MEANING NOTES WERE ATTACHED AND PLANS
 NEEDED MORE INFORMATION ON THEM BEFORE
 ROUGH INSPECTION. THERE IS NOW ALOT
 MORE WORK SHOWN AND PLANS NEED THE
 FIRST SET OF NOTES ADDRESSED AND NEW
 NOTES FOR OTHER WORKSHOWN.
  
 2)NOTE AS ASKED FOR ON PREVIOUS REVIEW,
 NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRNET PER 110-9.
  
 3)NOTE: PLEASE NOTE THAT PLANS SHOW 2"
 UG CONDUIT GOING TO COTTAGE? OR IS THE
 SERVICE AT THE COTTAGE/GARAGE/APT AND
 GOING TO HOUSE? PLEASE CLARIFY.
  
  
  
  
  
 5) NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ALSO ON EACH LEVEL OF A MULTI-LEVEL
 DWELLING UNIT. ROOMS WITH BATHS AND OR
 CLOSETS ARE CONSIDERED SLEEPING ROOMS.
 PER NFPA-72 2-2.1.1.1.
  
 6)NOTE: PLEASE SUBMIT PANEL SCHEDULE/S
 FOR NEW CIRCUITS BEING INSTALLED. 215-5
 PLEASE SHOW PANEL SCHEDULE AT HOUSE/
 MAIN BRKR IS REQ`D IF AT SEPARATE
 STRUCTURE. PER 225-31.
 PLANS SHOW 2POLE 100A GOING TO HOUSE.?
  
  
  
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS PLEAS
 E CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.
 561-659-8096 EXT8372

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2000-10-12 Cont ID  
Sent By dpalmer Date 2000-10-12 Time 20:17 Rev Time 0.00
Received By dpalmer Date 2000-10-12 Time 20:17 Sent To  
Notes
2001-01-08 00:00:00 
 ************** PROVISO *****************
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 EQUIPMENT MAINS/PANELS. MUST BE RATED
 FOR THE AVAILABLE FAULT CURRENT.110-9
  
 2)NOTE: PLEASE SHOW SERVICE ON COTTAGE
 215-5
  
 3)NOTE: PLEASE NOTE THE REQ`MENT FOR
 BATH(S) RECPETS PER 210-11-C-3
  
 4)NOTE: PLEASE SEE 210-8-A-6 ALL OUTLETS
 SERVING KITCHEN COUNTERSPACE ARE TO BE
 GFI/GFI PROTECTED.
  
 5)NOTE: PLEASE SEE 210-52-C FOR ISLAND
 REC REQ`MENTS.
  
 6)NOTE: MISSING OUTLETS FOR KITCHEN WALL
 SPACE. 210-52
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW BEFORE ANY ROUGH ELECTRICAL
 INSPECTION IS CALLED IN.IF THERE ARE ANY
 QUESTIONS PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 659-8096 EXT 8372

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-02-08 Cont ID  
Sent By jleech Date 2001-02-08 Time 07:42 Rev Time 0.25
Received By jleech Date 2001-02-08 Time 07:42 Sent To  
Notes
2001-02-08 00:00:00FIXTURE CHANGE ONLY.

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-10-11 Cont ID  
Sent By tlarge Date 2000-10-11 Time 21:04 Rev Time 0.25
Received By tlarge Date 2000-10-11 Time 21:03 Sent To  
Notes
2001-01-08 00:00:00SUBMIT PLANS SHOWING ALL PLUMBING WORK
 TO BE DONE.COUNTYWIDE AMENDMENTS TO SPC
 SEC.104.2.1.
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER..

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 2001-02-08 Cont ID  
Sent By fknapp Date 2001-02-08 Time 11:52 Rev Time 0.00
Received By fknapp Date 2001-02-08 Time 11:52 Sent To  
Notes
***NONE***