| 2001-02-12 00:00:00 | ******************* UNSAT ************** |
| | |
| | |
| | 1)NOTE: PLEASE NOTE PLANS FIRST CAME IN |
| | WITH MINOR ELECTRICAL WORK BEING DONE |
| | INONLY LIMITED AREAS. NOW PLANS SHOW |
| | COMPLETE RE-WIRING OF HOUSE. THE PLANS |
| | WERE |
| | ORIGINALLY PASSED WITH A "PROVISO" |
| | MEANING NOTES WERE ATTACHED AND PLANS |
| | NEEDED MORE INFORMATION ON THEM BEFORE |
| | ROUGH INSPECTION. THERE IS NOW ALOT |
| | MORE WORK SHOWN AND PLANS NEED THE |
| | FIRST SET OF NOTES ADDRESSED AND NEW |
| | NOTES FOR OTHER WORKSHOWN. |
| | |
| | 2)NOTE AS ASKED FOR ON PREVIOUS REVIEW, |
| | NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW EQUIPMENT BEING INSTALLED. |
| | MAINS/PANELS/BREAKERS MUST BE RATED FOR |
| | THE AVAILABLE FAULT CURRNET PER 110-9. |
| | |
| | 3)NOTE: PLEASE NOTE THAT PLANS SHOW 2" |
| | UG CONDUIT GOING TO COTTAGE? OR IS THE |
| | SERVICE AT THE COTTAGE/GARAGE/APT AND |
| | GOING TO HOUSE? PLEASE CLARIFY. |
| | |
| | |
| | |
| | |
| | |
| | 5) NOTE: SMOKE DETECTORS ARE REQUIRED |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| | ALSO ON EACH LEVEL OF A MULTI-LEVEL |
| | DWELLING UNIT. ROOMS WITH BATHS AND OR |
| | CLOSETS ARE CONSIDERED SLEEPING ROOMS. |
| | PER NFPA-72 2-2.1.1.1. |
| | |
| | 6)NOTE: PLEASE SUBMIT PANEL SCHEDULE/S |
| | FOR NEW CIRCUITS BEING INSTALLED. 215-5 |
| | PLEASE SHOW PANEL SCHEDULE AT HOUSE/ |
| | MAIN BRKR IS REQ`D IF AT SEPARATE |
| | STRUCTURE. PER 225-31. |
| | PLANS SHOW 2POLE 100A GOING TO HOUSE.? |
| | |
| | |
| | |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS PLEAS |
| | E CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW. |
| | 561-659-8096 EXT8372 |