| 2001-01-08 00:00:00 | CHECKLIST: |
| | 1-NEED TO HAVE AN ACTUAL SURVEY WITH THE |
| | BUILDING LAYOUT IN ORDER TO ACCURATELY |
| | REVIEW PLANS FOR TABLE 600 OF SBC 1997 |
| | 2-EGRESS WINDOWS ON SECOND FLOOR DON'T |
| | COMPLY WITH THE MINIMUM REQUIREMENTS |
| | SECTION 1005.4.4 SBC 1997. MINIMUM |
| | CLEAR HEIGHT OPENING OF 24" AND MIN. |
| | TOTAL CLEAR OPENING OF 5.7 SQ. FT. |
| | 3-VERIFY SIZE OF FOOTING. SOIL TEST |
| | REPORT RECOMMENDS 18" EMBEDMENT OF |
| | FOOTING. SEE FINDINGS ON PAGE 3 OF 4 |
| | OF SOIL TEST REPORT. |
| | 4-OPTION OF 4080 SLIDING GLASS DOOR DO |
| | NOT ALLOW 32" MIN. CLEAR OPENING. SEE |
| | SECTION OF USABLE DOORS OF THE F.H.A. |
| | 5-SOIL TEST REPORT TO BE SIGNED, SEALED |
| | AND DATED WHEN SUBMITTED FOR PUBLIC |
| | RECORDS. CHAPTER 471 FLORIDA STATUTES. |
| | -BORING TESTS SHOW ORGANIC MATERIALS IN |
| | THE SOIL. REMOVE AS REQUIRED BY SECT'N |
| | 1804.1.8 SBC 1997. |
| | 6-SHOW LOCATION OF VENTS ON ROOF PLAN |
| | DRAWING BP-3. |
| | -CLARIFY SIZE OF VENT: 3"X24" OR 6"X24" |
| | 7-SPECIFY SAFETY GLASS AT REQUIRED AREAS |
| | SEC. 2405.2 SBC 1997. SEE PLANS. |
| | 8-PROVIDE PRODUCT APPROVAL FOR: |
| | -SLIDING GLASS DOORS, SINGLE HUNG WIND, |
| | HORIZONTAL SLIDERS. |
| | -FIREPLACE UL LISTING AND SPECS. |
| | -TWO HOUR CONCRETE BLOCK: PROVIDE |
| | CERTIFICATION FROM MANUFACTURER'S |
| | ENGINEER STATING THAT CONCRETE BLOCK |
| | EQUIVALENT THICKNESS COMPLIES WITH |
| | ASTM C140 FOR FIRE RESISTANCE. |
| | SECTION 709.3 SBC 1997. |
| | -GARAGE DOORS PRODUCT APPROVALS |
| | SUBMITTED DON'T MEET THE DESIGN |
| | PRESSURES CALCULATED BY THE ARCHITECT. |
| | ALSO, DRAWING SBC-580-015 DON'T MATCH |
| | THE REPORT. SEE THE DATE OF DRAWING. |
| | 9-REVISE THE DESIGN CERTIFICATION FOR |
| | BUILDING CODE COMPLIANCE FORM. SEE |
| | COMMENTS ON FORM SUBMITTED. |
| | 10:ENERGY CALCULATIONS: |
| | -COMPLETE TOP FORM. |
| | -SEE COMMENTS ON EACH FORM. |
| | -WILL NEED ORIGINAL ENERGY CALCULATIONS |
| | FOR EACH ADDRESS WITH ORIGINAL |
| | SIGNATURES. |
| | 11-PROVIDE CONSTRUCTION DRAWINGS AND |
| | SPECIFICATIONS FOR SCREEN ENCLOSURES |
| | OR CLARIFY IF IT'S GOING TO BE UNDER |
| | A SEPARATE CONTRACT. |
| | 12-SPECIFY FIREBLOCKING AS REQUIRED. |
| | SEE PLANS FOR COMMENTS.SEC 2305 SBC/97 |
| | 13-BATHROOM TYPE "B" WAS SELECTED TO |
| | COMPLY WITH THE FAIR HOUSING ACT, ALL |
| | OTHER BATHROOMS STILL NEED TO COMPLY |
| | WITH THE F.H.A. REQUIREMENTS EXCEPT |
| | FOR MANEUVERING AND CLEAR FLOOR SPACES |
| | 14-PROVIDE 1 1/2" WATER STOP AT MASONRY |
| | WALL. SEC 2111.6 CITY AMENDMENTS. |
| | 15-STORM PANELS: |
| | -PROVIDE COMPLETE INSTALLATION SCHEDULE |
| | AS PER SAMPLE ATTACHED AND KEY PLAN. |
| | -SPECIFY/HIGHLIGHT SPECIFIC MOUNTING |
| | CONDITIONS AND AND ANCHORS TO BE USED |
| | ACCORDING TO THE MEAN ROOF HEIGHT, |
| | DESIGN PRESSURES, EDGE DISTANCE, PANEL |
| | SPAN, CONNECTION TYPE AND STRUCTURE TO |
| | BE ATTACHED TO. |
| | 16-SEE COMMENTS ON PLANS FOR ADDITIONAL |
| | COMMENTS. |
| | |
| | |
| | |
| | NOTES: |
| | -IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| | JULIO GOMEZ AT 659-8096 EXT. 8232. |
| | -PLEASE RETURN REVIEWED SET AFTER THE |
| | CORRECTIONS ARE DONE TO THE ORIGINAL |
| | DRAWINGS IN ORDER TO EXPEDITE THE |
| | REVIEW PROCESS. |