Plan Review Details - Permit 00091508
| Plan Review Stops For Permit 00091508 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2000-10-24 |
|
|
Cont ID |
|
| Sent By |
drunnels |
Date |
2000-10-24 |
Time |
16:38 |
Rev Time |
2.00 |
| Received By |
drunnels |
Date |
2000-10-24 |
Time |
16:38 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PROVISO | | | DOOR IN LOUNGE / FLORIDA ACCESSIBILITY | | | CODE FOR BUILDING CONSTRUCTION SECTION | | | 4.13.6 & FIGURE 25A REQUIRES 60 INCHES | | | CLEAR MANEUVERING AREA AT DOORS/ | | | DOOR SHALL COMPLY |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2000-10-13 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-10-13 |
Time |
08:28 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-10-13 |
Time |
08:28 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2000-09-29 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-09-29 |
Time |
11:26 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2000-09-29 |
Time |
11:26 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1) INTERIOR FINISH ON WALLS AND CEILINGS | | | IN EXITS SHALL BE CLASS A OR B. | | | 2) INTERIOR FINISH IN OFFICES SHALL BE | | | CLASS A,B, OR C. | | | 3) IF THE BUILDING IS NOT FIRE SPRINKLER | | | PROTECTED, THE UTILITY ROOM IS TO BE | | | SEPARATED BY AT LEAST ONE HOUR FROM | | | OTHER SPACES. THE OWNER MR. SPIEGEL | | | WAS CONTACTED BY TELEPHONE AND HE | | | ADVISED THAT THE BUILDING IS NOT | | | SPRINKLER PROTECTED. FIRE RESCUE RECORDS | | | SEEM TO SUGGEST THAT THE BUILDING MAY | | | BE SPRINKLER PROTECTED. PLEASE CLARIFY | | | ON THE PLANS. IF THE SPACE HAS FIRE | | | SPRINKLERS, THEN THE ONE HOUR FIRE | | | SEPARATION IS NOT REQUIRED FOR THE | | | UTILITY ROOM. | | | APPROVED PROVISO: |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2000-10-21 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-10-21 |
Time |
08:51 |
Rev Time |
0.33 |
| Received By |
ndenmark |
Date |
2000-10-21 |
Time |
08:51 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PROVISO: | | | 1. DUCT SMOKE DETECTORS TO BE TIED TO | | | BLDG FIRE ALARM OR HORN AND STROBE FOR | | | NOTIFICATION PER NFPA 90A 4.4.4 | | | 2. EXHAUST FANS SHOULD RUN WHILE BLDG | | | OCCUPIED FOR AIR BALANCE 1997 SMC 501.2 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2001-01-19 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2001-01-18 |
Time |
19:04 |
Rev Time |
0.50 |
| Received By |
jleech |
Date |
2001-01-19 |
Time |
12:37 |
Sent To |
|
|
| Notes |
| 2001-01-19 00:00:00 | PLANS ARE AS BUILDS. | | 2001-01-18 00:00:00 | REVISED RISER DIAGRAM NOT SEALED. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2000-10-01 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-10-01 |
Time |
09:14 |
Rev Time |
0.50 |
| Received By |
tlarge |
Date |
2000-10-01 |
Time |
08:58 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | *****************PROVISO**************** | | | FIXTURE BRANCHES NOT PERMITTED ON WET | | | VENTS PER COUNTYWIDE AMENDMENTS TO SPC | | | SEC.911.1.1. | | | | | | DRINKING FOUNTAIN SHALL COMPLY W/FACBC | | | SEC.4.1.3.(10)(A). | | | | | | CALL 561-659-8096,EXT.8377 IF YOU HAVE | | | QUESTIONS. | | | TIMOTHY LARGE | | | PLUMBING PLANS EXAMINER. |
|
|
|