Plan Review Details - Permit 00091478
Plan Review Stops For Permit 00091478
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2001-01-08 Cont ID  
Sent By mcarsill Date 2001-01-08 Time 10:37 Rev Time 0.00
Received By mcarsill Date 2001-01-08 Time 10:37 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2000-09-29 Cont ID  
Sent By mcarsill Date 2000-09-29 Time 07:53 Rev Time 0.00
Received By mcarsill Date 2000-10-03 Time 07:55 Sent To  
Notes
2001-01-08 00:00:001) SMOKE DETECTORS TO BE INSTALLED NO
 CLOSER THAN THREE FEET TO ANY AIR
 CONDITIONER DIFFUSER.
 2) SMOKE DETECTOR REQUIRED ABOVE MAIN
 FIRE ALARM CONTROL PANEL.
 3) HORN STROBES ARE TO BE MOUNTED NOT
 LESS THAN 80 INCHES AND NO HIGHER THAN
 96 INCHES FROM THE FLOOR.
 4) MANUAL PULL STATIONS SHALL BE
 INSTALLED NOT LESS THAN 3 1/2 FEET AND
 NO MORE THAN 4 1/2 ABOVE THE FLOOR.
 5) SYSTEM SUBJECT TO INSPECTION BY FIRE
 RESCUE PERSONNEL.