Plan Review Details - Permit 00091446
Plan Review Stops For Permit 00091446
Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2001-07-05 Cont ID  
Sent By pkrauss Date 2001-07-05 Time 13:57 Rev Time 0.30
Received By pkrauss Date 2001-07-05 Time 13:57 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2001-05-22 Cont ID  
Sent By pkrauss Date 2001-05-22 Time 13:33 Rev Time 1.00
Received By pkrauss Date 2001-05-22 Time 11:59 Sent To  
Notes
2001-05-22 00:00:00******************PROVISO***************
  
 DRAWING M2.1 - THIS SPACE IS NO LONGER
 APARTMENS BUT BEING UTILIZED AS OFFICE
 SPACE,LINE 14 INDICATES A WALL WITH
 TO SETS OF DOUBLE DOORS GOING TO
 ELEVATORS.IS THIS WALL A RATED WALL
 FOR TENANT SEPARATION?(FIRE DAMPER
 FOR DUCT PENETRATION.)
  
 AIR COOLED SPLIT SYSTEM SCHEDULE ON
 DRAWING M5.1 REFLECTS THREE SANYO SPILT
 SYSTEMS (1-1 THRU 1-3), BUT SUBMITTAL
 DATA FOR UNITS 1-1 & 1-2 ARE SANYO
 WHERE AS 1-3 IS FIRST CO.PLANS AND
 NEED TO REFLECT THAT OF THE SUBMITTAL
 DATA.
  
 DRAWING M4.1 DETAIL NEEDS TO REFLECT
 REFRIGERANT LINES GOING TO CONDENSERS
 ON THE ROOF INSTEAD OF GARAGE.
  
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2001-05-09 Cont ID  
Sent By pkrauss Date 2001-05-09 Time 11:43 Rev Time 2.00
Received By pkrauss Date 2001-05-09 Time 11:42 Sent To  
Notes
2001-05-09 00:00:00NOTES ON MASTER PERMIT 98009083

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-10-02 Cont ID  
Sent By ndenmark Date 2000-10-02 Time 15:10 Rev Time 0.33
Received By ndenmark Date 2000-10-02 Time 15:10 Sent To  
Notes
2001-01-08 00:00:00PROVISO:
 PROVIDE SUBMITTAL ON BOOSTER FANS AND
 DUCT RUN FOR DRYER FANS
 SUGNED AND SEALED DRAWINGS FROM ENGINEER
 OF RECORD REQUIRED FOR APPROVAL
 INFORMATION REQUIRED PRIOR TO 1ST INSPEC
 TION ON THIS WORK