| Plan Review Stops For Permit 00091387 |
| Review Stop |
FS |
|
| Rev No |
2 |
Status |
P |
Date |
2000-10-06 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-10-06 |
Time |
07:28 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2000-10-06 |
Time |
07:28 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1) FIRE DEPARTMENT CONNECTION TO BE | | | WITHIN 150 FEET OF A FIRE HYDRANT. | | | 2) SPARE HEAD BOX AND WRENCH TO BE | | | PROVIDED. | | | 3) CUT SHEETS FOR FIRE SPRINKLER HEADS | | | PLANNED FOR USE WERE NOT PROVIDED. | | | APPROVED PROVISO: |
|
|
| Review Stop |
FS |
|
| Rev No |
1 |
Status |
F |
Date |
2000-09-27 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-09-27 |
Time |
14:51 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2000-09-27 |
Time |
14:51 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1) WHERE IS THE FIRE DEPARTMENT | | | CONNECTION LOCATED. | | | 2) ENTIRE BUILDING IS TO BE COMPLETELY | | | FIRE SPRINKLER PROTECTED. THIS INCLUDES | | | ALL ELECTRICAL AND MECHANICAL ROOMS. ALL | | | VERTICAL SHAFTS ARE ALSO TO BE | | | PROTECTED. | | | 3) THE FRONT PORCH SHOWN ON THE FIRST | | | FLOOR PLAN IF COMBUSTIBLE AND EXCEEDS | | | FOUR FEET WIDE IS TO BE FIRE SPRINKLER | | | PROTECTED. | | | 4) SPARE HEAD BOX AND WRENCH IS TO BE | | | PROVIDED. | | | 5) SPRINKLER HEADS LOCATED ON BOTH SIDES | | | OF THE WINDOWS ARE TO BE LOCATED NO | | | FARTHER THAN 1 FOOT OF THE GLASS TO | | | PREVENT CRACKING. | | | 6) PROVIDE CUT SHEETS ON FIRE SPRINKLER | | | HEADS PLANNED FOR USE. |
|
|
|