Plan Review Details - Permit 00091385
Plan Review Stops For Permit 00091385
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2000-11-27 Cont ID  
Sent By hpiskura Date 2000-11-27 Time 09:39 Rev Time 0.00
Received By hpiskura Date 2000-11-27 Time 08:15 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2000-10-25 Cont ID  
Sent By lmartine Date 2000-10-25 Time 15:13 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
2001-01-08 00:00:00BUILDING COMMENTS
 -------------------
  
 1] SUBMIT ENERGY EFFIC. CALCULATIONS.
 2] PROVIDE CERTIFIED ENGINEERING FOR NEW
 10'OPENING AND EXISTING TIE BEAM.
 3] EXTERIOR SITE WORK WILL NOT BE
 INCLUDED WITH THIS PERMIT.
 4] PROVIDE 18"MANUVERING CLEARENCE AT
 PULL SIDE OF DOOR 106,SEE SECT.4.13.6
 FL.ACC.CODE.
  
  
 REVIEWED BY:
 LUIS MARTINEZ
 561-659-8096
 EXT. 8456

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-02-13 Cont ID  
Sent By dpalmer Date 2001-02-13 Time 09:25 Rev Time 0.00
Received By dpalmer Date 2001-02-13 Time 09:25 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2000-10-13 Cont ID  
Sent By dpalmer Date 2000-10-13 Time 11:56 Rev Time 0.00
Received By dpalmer Date 2000-10-13 Time 11:56 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2000-10-24 Cont ID  
Sent By mcarsill Date 2000-10-24 Time 13:23 Rev Time 0.00
Received By mcarsill Date 2000-10-24 Time 13:23 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2000-12-04 Cont ID  
Sent By ndenmark Date 2000-12-04 Time 11:12 Rev Time 0.33
Received By ndenmark Date 2000-12-04 Time 11:12 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2000-10-21 Cont ID  
Sent By ndenmark Date 2000-10-21 Time 09:08 Rev Time 0.33
Received By ndenmark Date 2000-10-21 Time 09:08 Sent To  
Notes
2001-01-08 00:00:00PROVIDE INFORMATION ON EF-2 OPERATION
 AND WHERE MAKE UP AIR FOR THIS FAN IS
 OBTAINED FROM. 2000CFM ON TOP OF THE CFM
 FROM THE BATH EXHAUST FANS FAR EXCEED
 THE AMOUNT OF OUTSIDE AIR PROVIDE TO THE
 SPACE FOR AIR BALANCE
 NOTE: DUCT SMOKE DETECTORS TO BE TIED TO
 BLDG FIRE ALARM OR HORN AND STROBE FOR
 NOTIFICATION PER NFPA 90A 4-4.4

Review Stop P PLUMBING
Rev No 2 Status P Date 2000-12-03 Cont ID  
Sent By pschmitz Date 2000-12-03 Time 12:42 Rev Time 1.00
Received By pschmitz Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-10-15 Cont ID  
Sent By tlarge Date 2000-10-15 Time 05:59 Rev Time 2.00
Received By pschmitz Date 2000-10-15 Time 05:58 Sent To  
Notes
2001-01-08 00:00:001)DRINKING FOUNTAIN SHALL COMPLY W/FACBC
 SEC.4.1.3.(10)(A).PROVISIONS SHALL BE
 MADE FOR PEOPLE WHO HAVE TROUBLE BENDING
 OR STOOPING.
  
 2)LOUNGE SINK SHALL COMPLY W/FACBC SEC.
 4.24.1-4.24.7.CLEARLY SHOW COMPLIANCE ON
 PLANS.
  
 3)SHT.A-5-DETAIL #A/6-H.C.LAVATORY SHALL
 COMPLY W/FACBC SEC.4.19.2.(MIN.29"TO
 BOTTOM OF APRON AND MAX.34"TO RIM.)
  
 4)SUBMIT MANUF.SHEETS/VENDOR DRAWINGS
 FOR R/O SYSTEM.COUNTYWIDE AMENDMENTS TO
 SPC SEC.104.2.1.
  
 5)SUBMIT UPDATED U.L.ASSEMBLY DETAIL/#
 FOR PIPE PENETRATION DETAIL ON P-1.
 COUNTYWIDE AMENDMENTS TO SPC SEC.104.2.4
  
 6)WATER HEATER SHALL BE READILY ACCESS-
 IBLE PER SPC 501.7.IF HEATER IS ELEVATED
 SUPPLY SHIP'S LADDER W/PLATFORM OR
 RELOCATE HEATER TO FLOOR.
  
 7)VACUUM RELIEF VALVE SHALL BE INSTALLED
 PER MANUF.RECOMMENDATIONS AND IN
 COMPLIANCE W/ANSI Z21.22.SPC SEC.507.1.2
  
 8)DRY VENTS ARE NOT PERMITTED PER SPC
 SEC.906.2.1.(SEE WATER CLOSETS.)
  
 9)WATER CLOSETS NOT PERMITTED ON HORIZ.
 WET VENTS PER COUNTYWIDE AMENDMENTS TO
 SPC SEC.911.1.1.TWO WATER CLOSETS MAY BE
 VENTED PER COUNTYWIDE AMENDMENTS TO SPC
 SEC.911.1.3.
  
 10)INDICATE SIZE OF PVC SLEEVE FOR
 CONCENTRATE PIPING.SLEEVE SHALL BE LARGE
 ENOUGH FOR REMOVAL/REPLACEMENT OF PIPING
 PER SPC SEC.601.7.
  
 11)BFP DEVICE SHALL BE RPZ TYPE.RELIEF
 VALVE SHALL BE PIPED TO APPROVED POINT
 OF DISPOSAL.SPC 606.4.1.
  
 12)ROOM 103-(H.C.TOILET ROOM)-WHEELCHAIR
 TURNING DIAMETER SHALL BE A CLEAR SPACE
 OF 60".(PLAN SHOWS INFRINGEMENT OF W.C.
 AND DOOR OPENING.)FACBC SEC.4.2.3.
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.