| Plan Review Stops For Permit 00091378 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2000-11-27 |
|
|
Cont ID |
|
| Sent By |
drunnels |
Date |
2000-11-27 |
Time |
11:37 |
Rev Time |
1.00 |
| Received By |
drunnels |
Date |
2000-11-27 |
Time |
11:37 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PROVISO | | | | | | ALL DOORS IN RATED SEPERATION WALL | | | SHALL BE 1 1/2 HR DOORS |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2000-10-27 |
|
|
Cont ID |
|
| Sent By |
drunnels |
Date |
2000-10-27 |
Time |
10:27 |
Rev Time |
2.50 |
| Received By |
drunnels |
Date |
2000-10-26 |
Time |
08:19 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1.SHEET A1.0 CODE LISTING DATA CALLS FOR | | | 2-HOUR TENANT SEPERATION SHEET A3.0 | | | SHOWS 1-HOUR WALL.TABLE 701 1997 SBC | | | REQUIRES 2-HOUR TENANT SEPERATION | | | BETWEEN STORAGE, LOW HAZARD S 2 AND | | | BUSINESS OCCUPANCY. | | | 2.SHEET A4.0 & A7.0 DOORS 143A 133 A | | | SHALL COMPLY WIT SECTION 705 AND | | | TABLE 705.1.2 | | | 3.SUBMIT PRODUCT APPROVALS FOR IMPACT | | | RESISTIANCE WINDOWS AND DOORS/METRO DADE | | | COUNTY OR SBCCI | | | 4.TYPE 4 CONSTRUCTION REQUIRES ALL | | | CONCEALED CONBUSTIABLE LUMBER SHALL | | | COMPLY WITH SECTION 707 1997 SBC | | | 5.SUBMIT PLANS SHOWING ACCESS COMPLYING | | | WITH THE FLORIDA ACCESSIBILITY CODE FOR | | | BUILDING CONSTRUCTION 1997 EDITION |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2001-03-26 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-03-26 |
Time |
16:44 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-03-26 |
Time |
16:37 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2001-02-01 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-02-01 |
Time |
14:02 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-02-01 |
Time |
14:02 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2000-10-25 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-10-25 |
Time |
00:48 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-10-25 |
Time |
00:48 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2000-11-21 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-11-21 |
Time |
13:53 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2000-11-21 |
Time |
13:53 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2000-09-28 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-09-28 |
Time |
09:41 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2000-09-28 |
Time |
09:40 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1) PLEASE PROVIDE INTERIOR FINISH | | | INFORMATION FOR SPACE. | | | 2) PLEASE PROVIDE MORE INFORMATION ON | | | ONE AND TWO HOUR FIRE SHUTTERS PLANNED | | | FOR USE. | | | 3) PLEASE INDICATE WHAT TYPE OF STORAGE | | | IS PLANNED FOR THE WAREHOUSE. | | | 4) PLEASE PROVIDE OCCUPANT LOAD | | | CALCULATIONS FOR THE SPACE. | | | 5) PLEASE PROVIDE MORE DETAILS FOR | | | CANOPY | | | 6) STAIRS TO COMPLY WITH NEW STAIR | | | REQUIREMENTS FROM NFPA 101, THE LIFE | | | SAFETY CODE, 1985 EDITION. | | | 7) PLEASE PROVIDE SEPARATE PLANS AND | | | PERMIT FOR THE INSTALLATION OF THE | | | FIRE ALARM SYSTEM SHOWN IN DRAWINGS. | | | 8) HANDRAILS AND GUARDS TO COMPLY WITH | | | NFPA 101, THE LIFE SAFETY CODE, 1985 | | | EDITION. | | | 9) ALL STORAGE ROOMS ARE TO BE SEPARATED | | | BY AT LEAST ONE HOUR FROM OTHER SPACES | | | SINCE NO FIRE SPRINKLERS ARE PRESENT. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2001-03-27 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-03-27 |
Time |
11:11 |
Rev Time |
0.25 |
| Received By |
pkrauss |
Date |
2001-03-27 |
Time |
11:57 |
Sent To |
|
|
| Notes |
| 2001-03-27 00:00:00 | REVISION - ADD 2 FIRE DAMPERS | | | PROVISO ON PLANS - SHALL COMPLY WITH | | | UL555 AS PER 97 SMC 610.1.1 AND | | | APPROVED MEANS OF ACCESS FOR | | | MAINTENANCE & RESETTING AS PER 97 SMC | | | 610.5. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2000-10-21 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-10-21 |
Time |
10:16 |
Rev Time |
1.00 |
| Received By |
ndenmark |
Date |
2000-10-21 |
Time |
10:16 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PROVISO: | | | 1. FRESH AIR INTAKES SHALL BE MIN. 10' | | | FROM ANY EXHAUST OUTLET OR SANITARY | | | RISER ETC. PER 1997 SMC 405 | | | 2. LOCAL AMENDMENT TO THE 1997 SMC | | | REQUIRES MIN. 18" CLEARANCE BETWEEN ROOF | | | SURFACE AND BOTTOM OF MAIN SUPPORT | | | STRUCTURE OF STAND FOR ACCESS UNDER THE | | | UNIT FOR REROOF ACCESS. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2001-01-02 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2001-01-02 |
Time |
12:26 |
Rev Time |
0.50 |
| Received By |
jleech |
Date |
2001-01-02 |
Time |
12:26 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2000-11-21 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2000-11-21 |
Time |
11:30 |
Rev Time |
1.33 |
| Received By |
jleech |
Date |
2000-11-21 |
Time |
11:30 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2000-10-02 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-10-02 |
Time |
15:20 |
Rev Time |
1.25 |
| Received By |
tlarge |
Date |
2000-10-02 |
Time |
15:20 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | SUBMIT OCCUPANT LOAD BASED ON HABITABLE | | | FLOOR SPACE PER SPC TABLE 407.SEE SEC. | | | 407.1.3 FOR ALLOWED DEDUCTIBLE AREAS. | | | | | | 2)WIDTH OF HANDICAP STALLS SHALL COMPLY | | | W/FACBC SEC.4.17.3.(MIN.83"IS REQD.IF | | | LAV.IS ADJACENT TO W.C.) | | | | | | 3)SHT.P0.1-WATER HEATER SHALL BE READILY | | | ACCESSIBLE PER SPC SEC.501.7.SUPPLY | | | SHIP'S LADDER FOR ACCESSIBILITY,REPAIR | | | AND MAINTENANCE. | | | | | | 4)THE DESIGN OF THE EXISTING SANITARY | | | SYSTEM DOESN'T COMPLY W/SPC SEC.914.1. | | | REVISE DESIGN TO COMPLY W/CODE. | | | | | | CALL 561-659-8096,EXT.8377 IF YOU HAVE | | | ANY QUESTIONS. | | | TIMOTHY LARGE | | | PLUMBING PLANS EXAMINER. |
|
|