Plan Review Details - Permit 00091378
Plan Review Stops For Permit 00091378
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2000-11-27 Cont ID  
Sent By drunnels Date 2000-11-27 Time 11:37 Rev Time 1.00
Received By drunnels Date 2000-11-27 Time 11:37 Sent To  
Notes
2001-01-08 00:00:00PROVISO
  
 ALL DOORS IN RATED SEPERATION WALL
 SHALL BE 1 1/2 HR DOORS

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2000-10-27 Cont ID  
Sent By drunnels Date 2000-10-27 Time 10:27 Rev Time 2.50
Received By drunnels Date 2000-10-26 Time 08:19 Sent To  
Notes
2001-01-08 00:00:001.SHEET A1.0 CODE LISTING DATA CALLS FOR
 2-HOUR TENANT SEPERATION SHEET A3.0
 SHOWS 1-HOUR WALL.TABLE 701 1997 SBC
 REQUIRES 2-HOUR TENANT SEPERATION
 BETWEEN STORAGE, LOW HAZARD S 2 AND
 BUSINESS OCCUPANCY.
 2.SHEET A4.0 & A7.0 DOORS 143A 133 A
 SHALL COMPLY WIT SECTION 705 AND
 TABLE 705.1.2
 3.SUBMIT PRODUCT APPROVALS FOR IMPACT
 RESISTIANCE WINDOWS AND DOORS/METRO DADE
 COUNTY OR SBCCI
 4.TYPE 4 CONSTRUCTION REQUIRES ALL
 CONCEALED CONBUSTIABLE LUMBER SHALL
 COMPLY WITH SECTION 707 1997 SBC
 5.SUBMIT PLANS SHOWING ACCESS COMPLYING
 WITH THE FLORIDA ACCESSIBILITY CODE FOR
 BUILDING CONSTRUCTION 1997 EDITION

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2001-03-26 Cont ID  
Sent By dpalmer Date 2001-03-26 Time 16:44 Rev Time 0.00
Received By dpalmer Date 2001-03-26 Time 16:37 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-02-01 Cont ID  
Sent By dpalmer Date 2001-02-01 Time 14:02 Rev Time 0.00
Received By dpalmer Date 2001-02-01 Time 14:02 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2000-10-25 Cont ID  
Sent By dpalmer Date 2000-10-25 Time 00:48 Rev Time 0.00
Received By dpalmer Date 2000-10-25 Time 00:48 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2000-11-21 Cont ID  
Sent By mcarsill Date 2000-11-21 Time 13:53 Rev Time 0.00
Received By mcarsill Date 2000-11-21 Time 13:53 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2000-09-28 Cont ID  
Sent By mcarsill Date 2000-09-28 Time 09:41 Rev Time 0.00
Received By mcarsill Date 2000-09-28 Time 09:40 Sent To  
Notes
2001-01-08 00:00:001) PLEASE PROVIDE INTERIOR FINISH
 INFORMATION FOR SPACE.
 2) PLEASE PROVIDE MORE INFORMATION ON
 ONE AND TWO HOUR FIRE SHUTTERS PLANNED
 FOR USE.
 3) PLEASE INDICATE WHAT TYPE OF STORAGE
 IS PLANNED FOR THE WAREHOUSE.
 4) PLEASE PROVIDE OCCUPANT LOAD
 CALCULATIONS FOR THE SPACE.
 5) PLEASE PROVIDE MORE DETAILS FOR
 CANOPY
 6) STAIRS TO COMPLY WITH NEW STAIR
 REQUIREMENTS FROM NFPA 101, THE LIFE
 SAFETY CODE, 1985 EDITION.
 7) PLEASE PROVIDE SEPARATE PLANS AND
 PERMIT FOR THE INSTALLATION OF THE
 FIRE ALARM SYSTEM SHOWN IN DRAWINGS.
 8) HANDRAILS AND GUARDS TO COMPLY WITH
 NFPA 101, THE LIFE SAFETY CODE, 1985
 EDITION.
 9) ALL STORAGE ROOMS ARE TO BE SEPARATED
 BY AT LEAST ONE HOUR FROM OTHER SPACES
 SINCE NO FIRE SPRINKLERS ARE PRESENT.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-03-27 Cont ID  
Sent By pkrauss Date 2001-03-27 Time 11:11 Rev Time 0.25
Received By pkrauss Date 2001-03-27 Time 11:57 Sent To  
Notes
2001-03-27 00:00:00REVISION - ADD 2 FIRE DAMPERS
 PROVISO ON PLANS - SHALL COMPLY WITH
 UL555 AS PER 97 SMC 610.1.1 AND
 APPROVED MEANS OF ACCESS FOR
 MAINTENANCE & RESETTING AS PER 97 SMC
 610.5.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-10-21 Cont ID  
Sent By ndenmark Date 2000-10-21 Time 10:16 Rev Time 1.00
Received By ndenmark Date 2000-10-21 Time 10:16 Sent To  
Notes
2001-01-08 00:00:00PROVISO:
 1. FRESH AIR INTAKES SHALL BE MIN. 10'
 FROM ANY EXHAUST OUTLET OR SANITARY
 RISER ETC. PER 1997 SMC 405
 2. LOCAL AMENDMENT TO THE 1997 SMC
 REQUIRES MIN. 18" CLEARANCE BETWEEN ROOF
 SURFACE AND BOTTOM OF MAIN SUPPORT
 STRUCTURE OF STAND FOR ACCESS UNDER THE
 UNIT FOR REROOF ACCESS.

Review Stop P PLUMBING
Rev No 3 Status P Date 2001-01-02 Cont ID  
Sent By jleech Date 2001-01-02 Time 12:26 Rev Time 0.50
Received By jleech Date 2001-01-02 Time 12:26 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2000-11-21 Cont ID  
Sent By jleech Date 2000-11-21 Time 11:30 Rev Time 1.33
Received By jleech Date 2000-11-21 Time 11:30 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-10-02 Cont ID  
Sent By tlarge Date 2000-10-02 Time 15:20 Rev Time 1.25
Received By tlarge Date 2000-10-02 Time 15:20 Sent To  
Notes
2001-01-08 00:00:00SUBMIT OCCUPANT LOAD BASED ON HABITABLE
 FLOOR SPACE PER SPC TABLE 407.SEE SEC.
 407.1.3 FOR ALLOWED DEDUCTIBLE AREAS.
  
 2)WIDTH OF HANDICAP STALLS SHALL COMPLY
 W/FACBC SEC.4.17.3.(MIN.83"IS REQD.IF
 LAV.IS ADJACENT TO W.C.)
  
 3)SHT.P0.1-WATER HEATER SHALL BE READILY
 ACCESSIBLE PER SPC SEC.501.7.SUPPLY
 SHIP'S LADDER FOR ACCESSIBILITY,REPAIR
 AND MAINTENANCE.
  
 4)THE DESIGN OF THE EXISTING SANITARY
 SYSTEM DOESN'T COMPLY W/SPC SEC.914.1.
 REVISE DESIGN TO COMPLY W/CODE.
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 ANY QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.