Plan Review Details - Permit 00091295
Plan Review Stops For Permit 00091295
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2001-03-12 Cont ID  
Sent By jwitmer Date 2001-03-12 Time 11:44 Rev Time 1.50
Received By jwitmer Date   Time   Sent To  
Notes
2001-03-12 00:00:00PROVISO: PAY COUNTY IMPACT FEES,
 RADON FEES. JW

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2001-02-26 Cont ID  
Sent By jwitmer Date 2001-02-26 Time 09:38 Rev Time 4.00
Received By jwitmer Date   Time   Sent To  
Notes
2001-02-26 00:00:00PERMIT # 00091295
 4700 GEORGIA AV.
 OVERLAND CONSTRUCTION
 PHONE 683-3210
  
 1)- NOTICE OF COMMENCEMENT: OWNER NAME
 ON PROPERTY APPRAISER IS DANIEL M FOWLER
 ON THE PERMIT APPLICATION LISTED AS
 FOWLER SHEET METAL, INC. THE BUILDING
 DEPARTMENT WILL NEED TO SEE PROOF OF
 CHANGE OF OWNERSHIP OR THE PERMIT APPLI-
 CATION WILL NEED TO BE CHANGED, BOTH THE
 NOTICE OF COMMENCEMENT & THE PROPERTY
 APPRAISERS SCREEN MUST AGREE.
  
 2)- SHEET A-5 DETAIL 4/A-5 EXISTING
 BUILDING (LOT 61-64) SOUTH WALL OF NEW
 BUILDING IS A PROPERTYLINE WALL. THE
 OVERHANG AND GUTTER CANNOT OVERHANG THE
 PROPERTYLINE WALL, NOR CAN THE EXISTING
 BUILDING BE JOINED, UNDER DIFFERENT
 QWNERSHIP & PROPERTY CONTROL NUMBER.
 THE SOUTH WALL WILL REQUIRE A MINIMUM OF
 A 3HR. WALL. TABLE 709.3.1 THE MINIMUM
 EQUIVALENT THICKNESS FOR LIMESTONE
 MASONARY WALLS IS A 5.0. SHOW COMPLIANCE
 FIRE RATINGS MUST BE TAKEN FROM BOTH
 SIDES OF THE WALL WHEN THE EXTERIOR
 BUILDING WALL IS 5'-0" OR LESS IN HORI-
 ZONTAL SEPERATION.NO OPENINGS.
  
 3)- SHEET A-5 SECTION 3: (EAST WALL)
 THIS WALL WILL ALSO REQUIRE A 3 HR. WALL
 SHOW COMPLIANCE THE EQUIVALENT THICKNESS
 FOR LIMESTONE MASONARY WALL (MINIMUM) IS
 5.0 TABLE 709.3.1.
  
 JIM WITMER
 BUILDING PLAN REVIEW
 (561) 659-8096 EX 8412

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-01-22 Cont ID  
Sent By jwitmer Date 2001-01-22 Time 07:38 Rev Time 3.00
Received By jwitmer Date   Time   Sent To  
Notes
2001-01-22 00:00:00BUILDING PLAN REVIEW
 1)- DISCREPANCY, SHEET A-1 VS A-3 SITE
 PLAN SHOWS GABLES AT THE NORTH/SOUTH
 ELEVATION WHILE A-3 IN DICATES GABLES AT
 EAST WEST ELEVATIONS?
 2)- ADDITIONAL INFORMATION SBC 104.2.2-
 SHEET A-2 SHOWS A ROOM SIZE OF 16'-0"X
 36'-2" AND NO USEAGE LISTED?
 3)- ENERGY CALCS?
 4)- SBC 1606.2.6.2- COMPONENTS AND CLAD-
 DING, ALL DOORS REQUIRE PRODUCT APPROVAL
 REPORTS EITHER DADE COUNTY OR SBCCI
 REPORT ARE ACCEPTED.
 5)- THIS BUILDING FALLS UNDER ONE OF TWO
 CATEGORIES, MANUFACTURED BUILDINGS THAT
 REQUIRE PLANS APPROVED BY DCA DEPARTMENT
 OF COMMUNITY AFFAIRS OR IT IS A STEEL
 ENGINEERED BUILDING (SBC 2201) THAT
 REQUIRES ENGINEERED DRAWINGS, SIGNED,
 SEALED AND DATED.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 EX 8412

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2001-09-10 Cont ID  
Sent By dpalmer Date 2001-09-10 Time 18:52 Rev Time 0.00
Received By dpalmer Date 2001-09-10 Time 18:52 Sent To  
Notes
2001-09-10 00:00:00***************** UNSAT ***************
  
 1)NOTE: PLEASE NOTE PLANS NEED TO SHOW
 ALL BRANCH CIRCUIT #`S AND CORRELATE
 WITH SUBMITTED PANEL SCHEDULES.
  
 2)NOTE: PLEASE NOTE PLANS MISSING BLDG.
 STEEL PER 250-50.
  
 3)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 4)NOTE: PLEASE NOTE THAT BOTH PANELS ARE
 SHOWN AS PANELS "LP"??? PLEASE CLARIFY.
  
 5)NOTE: PLEASE NOTE THAT PLANS ONLY SHOW
 LOCATION OF ONE PANEL?? PLEASE SHOW BOTH
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2001-09-10 Cont ID  
Sent By dpalmer Date 2001-09-06 Time 10:05 Rev Time 0.00
Received By dpalmer Date 2001-09-06 Time 10:05 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2001-03-01 Cont ID  
Sent By dpalmer Date 2001-03-01 Time 10:14 Rev Time 0.00
Received By dpalmer Date 2001-03-01 Time 10:14 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2001-02-27 Cont ID  
Sent By dpalmer Date 2001-02-27 Time 18:56 Rev Time 0.00
Received By dpalmer Date 2001-02-27 Time 18:56 Sent To  
Notes
2001-02-27 00:00:00*************** UNSAT ******************
  
 1)NOTE: PLEASE NOTE THAT NO CHANGES
 WERE MADE TO THE PLANS FROM FISRT SET
 OF REVIEW NOTES. PLEASE ADDRESS ORIG
 NOTES AND SUBMIT FOR REVIEW.
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-01-22 Cont ID  
Sent By dpalmer Date 2001-01-22 Time 12:44 Rev Time 0.00
Received By dpalmer Date 2001-01-22 Time 12:44 Sent To  
Notes
2001-01-22 00:00:00***************** UNSAT ****************
  
 1)NOTE: PLEASE SHOW ALL BRANCH CIRCUIT
 #`S ON PLANSAND CORRELATE WITH PANEL
 SCHEDULES.215-5
  
 2)NOTE: PLEASE SHOW GROUNDING ELECTRODE
 CONDUCTOR GOING TO BLDG STEEL PER 250-50
  
  
 3)NOTE"PLEASE LABEL PANEL LOCATIONS ON
 PLANS.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 2 Status N Date 2001-01-29 Cont ID  
Sent By mgonzale Date 2001-01-29 Time 15:55 Rev Time 0.00
Received By dlauderm Date   Time   Sent To  
Notes
2001-01-30 00:00:00SEE SECOND REVIEW FOR COMMENTS.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2001-01-29 Cont ID  
Sent By dlauderm Date 2001-01-29 Time 16:23 Rev Time 0.50
Received By dlauderm Date   Time   Sent To  
Notes
2001-01-29 00:00:00FAILED:
 PLEASE REVISED DUMPSTER AREA AS PER OUR
 STANDARD MINIMUM DETAIL DIMENSION. SEE
 ATTACHED

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2001-09-05 Cont ID  
Sent By mcarsill Date 2001-09-05 Time 15:46 Rev Time 0.00
Received By mcarsill Date 2001-09-05 Time 15:46 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2001-02-21 Cont ID  
Sent By mcarsill Date 2001-02-21 Time 16:46 Rev Time 0.00
Received By mcarsill Date 2001-02-21 Time 16:46 Sent To  
Notes
2001-02-21 00:00:001) BUILDING ADDRESS REQUIRED PER CITY
 CODE REQUIREMENTS.
 2) PROVIDE EMERGENCY LIGHTING IN ALL
 MEANS OF EGRESS.
 3) INTERIOR FINISH INFORMATION NOT
 PROVIDED. INTERIOR FINISH IN EXITS
 SHALL BE CLASS A OR B.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-02-05 Cont ID  
Sent By mcarsill Date 2001-02-05 Time 11:09 Rev Time 0.00
Received By mcarsill Date 2001-02-05 Time 11:09 Sent To  
Notes
2001-02-05 00:00:001) PLEASE INDICATE THE TYPE OF ACTIVTIY
 THAT WILL OCCUR IN THE MANUFACTURING
 AREA OF THE BUILDING.
 2) PLEASE PROVIDE AN OCCUPANT LOAD AND
 A LIFE SAFETY PLAN FOR THE BUILDING.
 3) PLEASE PROVIDE INTERIOR FINISH
 CLASSIFICATION INFORMATION FOR THE
 WALLS AND CEILINGS.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2001-02-27 Cont ID  
Sent By pkrauss Date 2001-02-27 Time 16:34 Rev Time 0.30
Received By pkrauss Date 2001-02-27 Time 16:34 Sent To  
Notes
2001-02-27 00:00:00*****************DENIED*****************
  
 INSUFFICIENT INFORMATION FOR MECHANICAL
 REVIEW.
  
 PROVIDE EQUIPMENT INFORMATION, DUCT
 LAYOUT, AIR BALANCE, FRESH AIR
 CALCULATIONS AND EXHAUST FAN
 SPECIFICATIONS.
  
 SUBMIT PLANS WITH MECHANICAL PERMIT
 APPLICATION PRIOR TO START OF ANY
 MECHANICAL WORK BEING DONE.
  
 NOTE:IF ABOVE CEILING IS RETURN PLENUM
 THERE SHALL BE NO COMBUSTIBLES IN
 THIS SPACE AS PER 97 SMC 609.1.1.
  
 REFERENCE DRAWING M-1, HVAC NOTES
 #5 - EMERGENCY PAN MUST HAVE A
 FLOAT SWITCH AS PER 97 SMC
 304.8.6.1.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2001-02-02 Cont ID  
Sent By ndenmark Date 2001-02-02 Time 09:08 Rev Time 0.33
Received By ndenmark Date 2001-02-02 Time 9:28 Sent To  
Notes
2001-02-02 00:00:00INSUFFICIENT INFORMATION FOR
 MECHANICAL REVIEW.
  
 PROVIDE EQUIPMENT SPECIFICATION, AIR
 BALANCE SCHEDULES, EXHAUST FAN
 SPECIFACTIONS WITH MECHANICAL PERMIT
 APPLICATION.
  
 IF ABOVE CEILING IS RETURN PLENUM,
 THERE SHALL BE NO COMBUSTIBLES IN THIS
 SPACE AS PER 1997 SMC 609.1.1.
  
 REFERENCE DRAWING M-1, HVAC NOTES, #5
 2" EMERGENCY PAN MUST HAVE A FLOAT
 SWITCH AS PER 1997 SMC 304.8.6.1.

Review Stop P PLUMBING
Rev No 5 Status P Date 2001-03-28 Cont ID  
Sent By drunnels Date 2001-03-28 Time 10:21 Rev Time 0.25
Received By drunnels Date   Time   Sent To  
Notes
2001-03-28 00:00:00OK PER JLEACH 3/27/2001 SEE APPDR

Review Stop P PLUMBING
Rev No 4 Status F Date 2001-03-16 Cont ID  
Sent By jleech Date 2001-03-16 Time 07:49 Rev Time 0.50
Received By jleech Date 2001-03-16 Time 07:49 Sent To  
Notes
2001-03-16 00:00:00DENIED;
  
 1.MANUFACTORING AREA SHALL HAVE BATHROOM
 FACILITYS. 94 SPC TABLE 407.
  
 2.SINK IN BREAK ROOM SHALL COMPLY WITH
 FACBC SEC. 4.24.1 THRU 4.24.7. SHOW
 ARCHITECTAL DRAWING.
  
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT.8377

Review Stop P PLUMBING
Rev No 3 Status F Date 2001-03-16 Cont ID  
Sent By jleech Date 2001-03-16 Time 07:16 Rev Time 1.50
Received By jleech Date 2001-03-16 Time 07:16 Sent To  
Notes
2001-03-16 00:00:00DENIED;
  
 1.PAGE A-2 NOTE; AREA DATA, SHOWS OFFICE
 1168 SQ. FT. NEW LAYOUT SHOWS 576 SQ.
 FT. (GARAGE), MANUFACTURING THAT
 LEAVES 4774 SQ. FT. OF OFFICE SPACE.
 94 SPC TABLE 407. 48 PEOPLE EQUALS
 2 W/C AND 2 LAVS. FOR MALE& 2 AND 2
 FOR FEMALE.
  
 2.SINK IN BREAK ROOM SHALL COMPLY WITH
 FACBC SEC. 4.24.1 THRU 4.24.7. MAKE
 NOTE OR SHOW ARCHITECTAL DRAWING.
  
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT.8377

Review Stop P PLUMBING
Rev No 2 Status F Date 2001-02-27 Cont ID  
Sent By jleech Date 2001-02-27 Time 13:40 Rev Time 1.00
Received By jleech Date 2001-02-27 Time 13:40 Sent To  
Notes
2001-02-27 00:00:00DENIED;
  
 1.BATHROOM FACILITIES ARE REQUIRED IN
 MANUFACTURING AREA. SUBMIT INFORMATION
 SHOWING NUMBER OF EMPLOYEES PER SHIFT
 AND INDICATE LIGHT OR HEAVY MANUFACT-
 URING.
  
 2.PAGE M-1 NOTE 8;
 A. FLOOR DRAINS ARE NOT SHOWN ON
 SANITARY RISER DIAGRAM.
 B.SPECIFY TYPE OF AIR ARRESTERS TO
 BE USED. AIR ARRESTERS MUST BE
 ASSESIBLE 607.8.2 AND 607.8.3.
  
 3.SINK IN BREAK ROOM; SHOW ARCHITECTAL
 DRAWING MEETING ALL REQUIREMENTS OF
 97 FACBC SEC. 4.24.1 THRU 4.24.7.
  
 4. PLUMBING RISER NOT CORRECT.
  
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT.8377

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-01-18 Cont ID  
Sent By jleech Date 2001-01-18 Time 08:59 Rev Time 1.00
Received By jleech Date 2001-01-18 Time 08:59 Sent To  
Notes
2001-01-18 00:00:00DENIED;
  
 1.PAGE A-2 29" REQUIRED FROM FLOOR TO
 BOTTOM OF HANDICAP LAV.
  
 2.94 SPC TABLE 407 REQUIRES ONE DRINKING
 FOUNTAIN IN OFFICE AREA.
  
 3.ADDITIONAL INFORMATION REQUIRED TO
 FINE THE NUMBER OF PLUMBING FIXTURES
 REQUIRED IN MANUFACTURING AREA.
 A.LIGHT OR HEAVY MANUFACTORING.
 B.NUMBER OF EMPLOYEES PER SHIFT.
 TABLE 407.
  
 4.PAGE M-1 NOTE 8;
 A.NO FLOOR DRAINS ARE SHOWN ON
 SANITARY RISER. ARE FLOOR DRAINS
 IN BATHROOMS?
 B.AIR CHAMBERS MUST COMPLY TO 94 SPC
 607.8.2.
  
 5.DRAWINGS SHOW SINK IN BREAK ROOM. THAT
 SINK IS NOT SHOWN ON SANITARY RISER.
 IF IS INSTALLED IT MUST COMPLY TO THE
 97 FACBC SEC. 4.24.1 THRU 4.24.7.
  
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT. 8377

Review Stop Z ZONING
Rev No 1 Status P Date 2001-03-12 Cont ID  
Sent By gjoyce Date 2000-10-05 Time 09:44 Rev Time 0.15
Received By sgraham Date   Time   Sent To  
Notes
2001-01-08 00:00:00NEEDS LEVEL 1 SITE PLAN REVIEW