Plan Review Details - Permit 00091251
Plan Review Stops For Permit 00091251
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2000-11-28 Cont ID  
Sent By mcarsill Date 2000-11-28 Time 15:40 Rev Time 0.00
Received By mcarsill Date 2000-11-28 Time 15:40 Sent To  
Notes
2001-01-08 00:00:001) EXISTING SHAFT FOR THE HOOD EXHAUST
 DUCT TO BE AT LEAST ONE HOUR FIRE
 RATED.
 2) HOOD EXTINGUISHING SYSTEM TO BE
 CONNECTED TO BUILDINGS FIRE ALARM
 SYSTEM.
  
 APPROVED PROVISO:
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-12-04 Cont ID  
Sent By ndenmark Date 2000-12-04 Time 10:27 Rev Time 1.00
Received By ndenmark Date 2000-12-04 Time 10:27 Sent To  
Notes
2001-01-08 00:00:00PROVISO:
 1. SHAFT ENCLOSURE REQUIRES MIN. 6"
 CLEARANCE BETWEEN DUCT AND INSIDE OF
 SHAFT OR APPROVED FIRE BLANKET PER NFPA
 96
 2. FIRE SUPPRESSION SYSTEM REQUIRES
 ADDITIONAL PERMIT SUBMIT PLANS AT TIME
 OF PERMIT APPLICATION.