| Plan Review Stops For Permit 00091251 |
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2000-11-28 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-11-28 |
Time |
15:40 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2000-11-28 |
Time |
15:40 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1) EXISTING SHAFT FOR THE HOOD EXHAUST | | | DUCT TO BE AT LEAST ONE HOUR FIRE | | | RATED. | | | 2) HOOD EXTINGUISHING SYSTEM TO BE | | | CONNECTED TO BUILDINGS FIRE ALARM | | | SYSTEM. | | | | | | APPROVED PROVISO: | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2000-12-04 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-12-04 |
Time |
10:27 |
Rev Time |
1.00 |
| Received By |
ndenmark |
Date |
2000-12-04 |
Time |
10:27 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PROVISO: | | | 1. SHAFT ENCLOSURE REQUIRES MIN. 6" | | | CLEARANCE BETWEEN DUCT AND INSIDE OF | | | SHAFT OR APPROVED FIRE BLANKET PER NFPA | | | 96 | | | 2. FIRE SUPPRESSION SYSTEM REQUIRES | | | ADDITIONAL PERMIT SUBMIT PLANS AT TIME | | | OF PERMIT APPLICATION. |
|
|
|