Plan Review Details - Permit 00091238
Plan Review Stops For Permit 00091238
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2000-12-18 Cont ID  
Sent By jwitmer Date 2000-12-18 Time 09:49 Rev Time 2.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2000-11-01 Cont ID  
Sent By hpiskura Date 2000-11-01 Time 07:38 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2001-01-08 00:00:00SAME AS FIRST CHECKLIST NO CHANGE

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2000-12-14 Cont ID  
Sent By dpalmer Date 2000-12-14 Time 19:15 Rev Time 0.00
Received By dpalmer Date 2000-12-14 Time 19:15 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-11-07 Cont ID  
Sent By dpalmer Date 2000-11-07 Time 21:06 Rev Time 0.00
Received By dpalmer Date 2000-11-07 Time 21:06 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-10-12 Cont ID  
Sent By dpalmer Date 2000-10-12 Time 22:36 Rev Time 0.00
Received By dpalmer Date 2000-10-12 Time 22:36 Sent To  
Notes
2001-01-08 00:00:00************* UNSAT ******************
  
  
 1)NOTE: PLEASE NOTE; PER FL STATE STATUE
 'S. PLANS ARE TO SIGNED AND SEALED BY
 ENGINEER OF RECORD ON TITLE BLOCK.
 61G15-23.002/CHAPTER 471 OF FL AD. CODE
  
 2)NOTE: PLEASE SHOW CLARIFICATION ON
 RISER DIAGRAM,,,METERCAN AND ??? AND
 PANEL SHOWN?? NO WIRE SIZES,CONDUITS ETC
 IS THIS ALL EXISTING?? IF SO PLEASE NOTE
 AND STILL SHOW.
  
 3)NOTE: PLEASE COMPLETE AND (SHOW) LOAD
 CALCULATIONS. PLEASE NOTE THAT ALL
 CONTINUOUS LOADS ARE TO BE SHOWN AT 125%
 LIGHTING ETC. 215-5
  
 GROUNDING SYSTEM?? PER 250 AND 215-5
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2000-12-12 Cont ID  
Sent By mcarsill Date 2000-12-12 Time 10:00 Rev Time 0.00
Received By mcarsill Date 2000-12-12 Time 10:00 Sent To  
Notes
2001-01-08 00:00:00STORAGE ROOMS ARE TO BE AT LEAST ONE
 HOUR FIRE SEPARATED FROM OTHER PORTIONS
 OF THE BUILDING. THE CODE FOR BUSINESS
 OCCUPANCIES INDICATES "ANY AREA USED FOR
 GENERAL STORAGE, BOILER, OR FURNACE
 ROOMS, FUEL STORAGE, JANITOR CLOSETS,
 MAINTENANCE SHOPS, INCLUDING WOODWORKING
 AND PAINTING AREAS, AND KITCHENS SHALL
 BE SEPARATED FROM OTHER PARTS OF THE
 BUILDING BY CONSTRUCTION HAVING A
 FIRE RESISTANCE RATING OF NOT LESS THAN
 1 HOUR, AND ALL OPENINGS SHALL BE
 PROTECTED WITH SELF-CLOSING FIRE DOORS".
 "EXCEPTION: AREAS PROTECTED BY AN
 AUTOMATIC EXTINGUISHING SYSTEM".
  
 APPROVED PROVISO:
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2000-10-27 Cont ID  
Sent By mcarsill Date 2000-10-27 Time 14:32 Rev Time 0.00
Received By mcarsill Date 2000-10-27 Time 14:32 Sent To  
Notes
2001-01-08 00:00:00PREVIOUS COMMENTS NOT ADDRESSED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2000-10-16 Cont ID  
Sent By mcarsill Date 2000-10-16 Time 14:35 Rev Time 0.00
Received By mcarsill Date 2000-10-16 Time 14:35 Sent To  
Notes
2001-01-08 00:00:001) PREVIOUS PLAN REVIEW COMMENTS NOT
 ADDRESSED.
  
 PLANS REVIEWED BY CAPTAIN MIKE CARSILLO
 659-8096,EXT. 8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2000-09-29 Cont ID  
Sent By mcarsill Date 2000-09-29 Time 13:12 Rev Time 0.00
Received By mcarsill Date 2000-09-29 Time 13:12 Sent To  
Notes
2001-01-08 00:00:001) INTERIOR FINISHES IN EXITS SHALL BE
 CLASS A OR B IN EXITS. INTERIOR
 FINISHES IN OFFICES SHALL BE CLASS A,B
 OR C.
 2) OCCUPANT LOADS IN BUSINESS
 OCCUPANCIES IS ONE PERSON PER ONE
 HUNDRED SQUARE FEET. THE PLAN SEEMS TO
 SUGGEST A GREATER OCCUPANT LOAD FOR
 THE SPACE THAN THE CODE ALLOWS. PLEASE
 EXPLAIN RATIONALE.
 3) EXIT SIGN IS TO DIRECT PERSONS TO
 EXIT DOOR LOCATION IN LOUNGE AREA.
 4) STORAGE ROOM DOORS ARE TO BE AT
 LEAST ONE HOUR FIRE SEPARATED FROM
 OTHER SPACES BY AT LEAST ONE HOUR IF
 NO FIRE SPRINKLERS ARE PRESENT.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2000-12-20 Cont ID  
Sent By ndenmark Date 2000-12-20 Time 11:30 Rev Time 0.33
Received By ndenmark Date 2000-12-20 Time 11:30 Sent To  
Notes
2001-01-08 00:00:00PROVISO:
 1. FAN SHUT DOWN BY DUCT SMOKE DETECTOR
 REQUIRED. (RETURN AIR PLENUM SPACE ABOVE
 CEILING IS COMMON AREA FOR ALL AREAS
 AND UNITS.
 CONNECT TO BUILDING FIRE ALARM PER NFPA
 92A 4-4.4.2 OR HORN AND STROBE PER
 4-4.4.3

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2000-11-15 Cont ID  
Sent By ndenmark Date 2000-11-15 Time 17:02 Rev Time 0.50
Received By ndenmark Date 2000-11-15 Time 17:02 Sent To  
Notes
2001-01-08 00:00:00PRIOR COMMENTS NOT ADDRESSED ON NEW DRAW
 INGS EXCEPT ENGINEERS SEAL. PROVIDE INFO
 ON OTHER COMMENTS

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2000-10-21 Cont ID  
Sent By ndenmark Date 2000-10-21 Time 08:25 Rev Time 0.33
Received By ndenmark Date 2000-10-21 Time 08:25 Sent To  
Notes
2001-01-08 00:00:00***********DENIED***********************
 1. CONFLICT BETWEEN M-1 AND A-1.0 ON
 EQUIPMENT TYPE
 2. MECH DRAWINGS NOT SIGNED AND SEALED.
 3. NO INFORMATION ON DUCT SMOKE DETECTOR
 OR FAN SHUT DOWN
 4. EXHAUST AIR FANS TO RUN WHEN BUILDING
 IS OCCUPIED TO COMPLY WITH 1997 SMC
 501.2 (AIR BALANCE) NOT OPERATED BY WALL
 SWITCH.
 5. ANY PIPING RELATED TO MEDICAL EQUIP-
 MENT SHALL COMPLY WITH NFPA 99C AND
 REQUIRES MECHANICAL PERMIT. PROVIDE
 DETAILED PLANS FOR WORK SHOWING CODE
 COMPLIANCE PRIOR TO COMENCEMENT OF WORK.

Review Stop P PLUMBING
Rev No 5 Status P Date 2000-12-10 Cont ID  
Sent By pschmitz Date 2000-12-10 Time 10:07 Rev Time 1.50
Received By pschmitz Date   Time   Sent To  
Notes
2001-01-08 00:00:00PLUMBING PLAN REVIEWPROVISO
 (1) SHT P-1WTR HTR DETAIL,PAN DRAIN
 TO A FLOOR SINK,SPC 94 SEC 802 ALL
 INDIRECT WASTE TO FLR SINKS.
 (2) SHT P-3 H20 SUPPLY,SPC 94 AMND 607.7
 NO MORE THAN 2 FIXTURES ON1/2" COLD H20.
 BACK FLOW PREVENTER REQ. ON WATER SUPPLY
 ORDINANCE # 2853-95.
 END OF COMMENTSPAUL SCHMITZ
 561-659-8096 X 8233

Review Stop P PLUMBING
Rev No 4 Status F Date 2000-10-28 Cont ID  
Sent By tlarge Date 2000-10-28 Time 05:17 Rev Time 0.75
Received By pschmitz Date 2000-10-28 Time 05:08 Sent To  
Notes
2001-01-08 00:00:001)FOR THE FOURTH TIME-THE GRAB BAR
 BEHIND THE WATER CLOSETS IN TOILET ROOMS
 SHALL BE A MIN. OF 36"WIDE PER FACBC
 SEC.4.16.4 AND FIG.29.I SUGGEST YOU READ
 THIS SECTION.
  
 2)FOR THE FOURTH TIME-SHOW THE REQD.
 CLEAR WHEELCHAIR TURNING SPACE IN THE
 TOILET ROOMS.THE WATER CLOSETS CANNOT
 INFRINGE IN THIS CLEAR SPACE PER FACBC
 SEC.4.2.3.
  
 3)THE PLUMBING DRAWINGS STILL SHOW THE
 DOORS OF THE TOILET ROOMS SWINGING INTO
 THE CLEAR FLOOR SPACE REQD.FOR THE
 ACCESSIBLE FIXTURES.
 FOR THE FOURTH TIME-DOORS CANNOT SWING
 INTO THE CLEAR FLOOR SPACE REQD.FOR ANY
 FIXTURE.FACBC SEC.4.22.2.
  
 CALL IF YOU HAVE QUESTIONS.
 561-659-8096,EXT.8377.
  
 TIMOTHY LARGE
 PLUMBINGPLANS EXAMINER

Review Stop P PLUMBING
Rev No 3 Status F Date 2000-10-21 Cont ID  
Sent By tlarge Date 2000-10-21 Time 12:37 Rev Time 0.65
Received By tlarge Date 2000-10-21 Time 12:37 Sent To  
Notes
2001-01-08 00:00:001)SHTS.A-1.1,1.2-DOORS CANNOT SWING INTO
 THE CLEAR FLOOR SPACE REQD.FOR THE
 LAVATORIES.FACBC SEC.4.22.2.
  
 2)SHOW THE REQD.WHEELCHAIR TURNING SPACE
 IN EACH TOILET ROOM.COMPLY W/FACBC SEC.
 4.2.3.
  
 3)EACH COMMON AND PUBLIC USE TOILET
 ROOM SHALL BE FULLY ACCESSIBLE PER
 FACBC SEC.4.1.3.(11).
  
 4)SHT.A-1.0-NOTE #F-GRAB BAR BEHIND THE
 WATER CLOSET SHALL BE 36"MIN.PER FACBC
 4.16.4.
  
 5)SUBMIT MANUF.SHEETS FOR TUBAL GAS
 MACHINE,SUCTION MACHINE AND STERILIZ-
 ATION MACHINE.
  
 CALL IF YOU HAVE QUESTIONS.
 561-659-8096,EXT.8377.
  
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.

Review Stop P PLUMBING
Rev No 2 Status F Date 2000-10-18 Cont ID  
Sent By tlarge Date 2000-10-18 Time 11:22 Rev Time 1.00
Received By tlarge Date 2000-10-18 Time 10:58 Sent To  
Notes
2001-01-08 00:00:001)SHTS.A-1.1,1.2-CORRECT THE DOOR SWING
 ON THE TOILET ROOMS.DOORS CANNOT SWING
 INTO THE CLEAR FLOOR SPACE REQD. FOR THE
 LAVATORIES.FACBC SEC.4.22.2.
  
 2)SHOW THE REQD.WHEELCHAIR TURNING SPACE
 IN EACH TOILET ROOM.COMPLY W/FACBC SEC.
 4.2.3.
  
 3)MAX.HEIGHT OF STAFF SINK CABINET SHALL
 COMPLY W/FACBC SEC.4.24.2.SHOW ON SHT.
 A-3.
  
 4)SHT.A-1-GRAB BAR BEHIND WATER CLOSET
 SHALL BE A MIN. OF 36" NOT 24" AS NOTED
 PER FACBC SEC.4.16.4
  
 5)SHT.A-1.0-SHOW THE CLEAR INSIDE
 DIMENSIONS (LXW)OF EACH TOILET ROOM.
 COMPLY W/FACBC SEC.4.16.2.AND FIG.28.
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-09-30 Cont ID  
Sent By tlarge Date 2000-09-30 Time 07:31 Rev Time 1.25
Received By tlarge Date 2000-09-30 Time 07:08 Sent To  
Notes
2001-01-08 00:00:001)SUBMIT SIGNED,DATED AND SEALED WATER
 AND SANITARY RISER DIAGRAMS FOR REVIEW.
 COUNTYWIDE AMENDMENTS TO SPC SEC.104.2.1
  
 2)EACH PUBLIC AND COMMON USE TOILET ROOM
 SHALL COMPLY W/FACBC SEC.4.22.
  
 3)SUBMIT OCCUPANT LOAD BASED ON
 HABITABLE FLOOR SPACE PER TABLE 407 OF
 THE SPC.SEE SPC SEC.407.1.3.FOR ALLOWED
 DEDUCTIBLE AREAS.
  
 4)DOORS TO ACCESSIBLE TOILET ROOMS SHALL
 COMPLY W/FACBC SEC.4.13.DOORS SHALL NOT
 SWING INTO THE CLEAR FLOOR SPACE REQD.
 FOR ANY FIXTURE.FACBC SEC.4.22.2.
  
 5)FLOOR DRAINS W/TRAP PRIMERS ARE REQD.
 IN ALL TOILET ROOMS PER SPC SEC.409.4.1.
  
 6)SINK IN STAFF LOUNGE SHALL COMPLY W/
 FACBC SECS.4.24.1-4.24.7.
  
 7)CLEARLY SHOW REQD.WHEELCHAIR TURNING
 SPACE IN ALL TOILET ROOMS PER FACBC SEC.
 4.2.3.
  
 8)A MIN.OF 1 DRINKING FOUNTAIN IS REQD.
 PER SPC TABLE 407.BOTTLED WATER IS NOT
 AN ACCEPTED SUBSTITUTE FOR THE D.F.
 PROVISIONS SHALL BE MADE FOR PEOPLE WHO
 HAVE TROUBLE BENDING OR STOOPING PER
 FACBC SEC.4.1.3(10)(A).
  
 9)WALLS IN TOILET ROOMS SHALL BE NON-
 ABSORBENT TO A HEIGHT OF 4'PER SBC SEC.
 1204.2.
  
 10)WATER HEATER SHALL BE READILY ACCESS-
 IBLE PER SPC SEC.501.7.
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 ANY QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.